Page 8 of 16 / IOM 1178-1

Installer/Configuration Menu

1.  This control can be configured for:

 

HP1

 – Heat Pump with one stage of compressor 

 

(2 heat/1 cool) 

HP2

 – Heat Pump with two stage compressor system, 

Electric backup; (4 heat/2 cool)

2. 

Programs per week

 – This control can be configured for 

7 independent day or 5/1/1 day programming or non-
programmable modes. Default is 7-day mode. The display 
indicates “7 Days” as default. Other options “5 Days” or 
“0 Days” can be selected. If “0 Days” is selected for non-
programmable mode, the step for EMR will be skipped, as 
this feature will not be available in this mode.

3. 

Program Steps per day

 – Not available if configured for 

non-programmable. This control can be configured for 4 

or 2 program steps per day. Default is “4 PS” and can be 
toggled between 4 PS and 2 PS.

4. 

System Switch Configuration

 – This thermostat is 

configured for Heat and Cool with Auto changeover 

default (Cool-Off-Heat-Auto). It can be configured as 

Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or 

Cool Only (Cool-Off).

5. 

Energy Management Recovery (EMR)

 – (this step is 

skipped if configured as non-programmable). When set 

to “On” causes the thermostat to start heating or cooling 
early to make the building temperature reach the program 
setpoint at the time you specify. 
Example: The heating program is 65°F at night and 70° at 
7 AM. If the building temperature is 65°F, the difference 
is 5°F. Allowing 5 minutes per °F rise, the thermostat 
setpoint will change to 70° at 6:35 AM. Cooling allows 
more time per °F, because it takes longer to reach 
temperature.

6, 7 & 8. 

Cycle Rate Selection

 – The factory default setting 

is fast cycle (FA Cr) in all modes (Heat, Cool, Em). 

To change to slow cycling (SL, Cr), press touch 
keys 

 or toggle 

 between FA & SL. The cycle 

rates are below:

Mode  

Med  

Slow

Heat  

0.6°F  

1.5°F

Cool  

1.2°F  

1.7°F

Heat Pump  

1.2°F  

1.7°F

Emer Heat  

0.6°F  

1.7°F

9. 

Select Compressor Lockout (CL)

 – Selecting (CL On 

will cause the thermostat to wait 5 minutes between 
cooling cycles. This is intended to help protect the 
compressor from short cycling. The water source heat  
pump MicroTech® III unit controller has a time delay 
built in and does not require this feature to be activated 

in the thermostat. When the thermostat compressor time 

delay is activated, it will flash the set point for up to five 

minutes.

10. 

Select Continuous Display Lighting (dL)

 – In low 

lighting conditions, display backlight improves the display 

contrast. When C terminal is connected, selecting dL On 

will turn the display light on continuously. Selecting dL 
Off will turn the display light on momentarily after any 

key is pressed. When C terminal is not powered (battery 

only), dL On enables the momentary backlight whenever a 
key is pressed.

 

Continuous Display Lighting without common wire 

connection

 – When thermostat is Battery Powered with 

Power Stealing assist with low voltage 24V connections 

to both W and Y terminals, selecting dL “On” will provide 

continuous display light.

Note:

  If power stealing operation is not compatible with 

either the W or Y connection (see 

"Power Stealing 

Switches" on page 3

), or if only a single connection 

to W or Y, continuous display light will be interrupted 

when the active power stealing connection (W or Y) 

is operating the system. In power stealing mode, the 

continuous display light will increase in brightness 

when a button is pressed. And on some systems with 

high impedance, the display light may dim slightly 

when thermostat is calling for heat or cool.

11. 

Select Temperature Display Adjustment 5 LO to 5 HI.

 

This allows you to adjust the room temperature display by 
-5°F to +5°F in 1° steps. Your thermostat was accurately 
calibrated at the factory, however you have the option 
to change the display temperature value to match the 
previous thermostat, if you so prefer.

12. 

Select °F or °C Readout 

– Changes the display readout to 

Celsius or Fahrenheit as required.

13. 

Select Audio Prompting (Beeper) On or Off

 – Factory 

default setting is b, On. If you wish to turn off the beeper 
select OFF.

14. 

Select Daylight Saving Time Calculation

 – This 

feature will allow the thermostat to calculate the DST 
automatically and apply it to the Real Time Clock display. 
Default is On.

15 & 16. 

Select Automatic Schedule

 – Not available if 

configured for non-programmable. This feature 

allows programming a “Comfort Temperature” 
into all program periods with the Auto Schedule 

key. When Heat AS (for Heat mode) or Cool AS 

(for Cool mode) is selected On, the Auto Schedule 
feature is ready to be set. Off indicates that the 
feature is not ready to be used or a “Comfort 
Temperature” is already set. See Auto Schedule in 
Programming section.

Содержание 910121750

Страница 1: ...And Configuration Items 6 Installer Configuration Menu 7 Operating Your Thermostat 10 Heating 10 Cooling Dehumidifier 11 Choose The Fan Setting Auto or On 11 Choose The System Setting Cool Off Heat Au...

Страница 2: ...izontal Enfinity W CCH CCW MicroTech III Unit Controller Yes Vertical W VFC VFW Vertical Stacked W VHC Console W MHC MHW Horizontal Vertical SmartSource 1 Stage W GSH GSV MicroTech III SmartSource Uni...

Страница 3: ...rews Lev eling is for appearance only and will not affect thermostat operation 5 Connect wires to terminal block on base using appropri ate wiring schematic 6 Push excess wire into wall and plug hole...

Страница 4: ...ower for heating 24V power for heating C 24V common 24V common Y Compressor cool 1st stage Compressor cool 1st stage Y2 No output Compressor cool 2nd stage W1 Compressor heat 1st stage Compressor heat...

Страница 5: ...h the following heat pump systems Heat Pump Type 1 HP1 Single stage compressor system with electric backup Heat Pump Type 2 HP2 2 stage compressor system with electric backup Note After wiring see Ins...

Страница 6: ...iguration menu to change selections 9 Hold Until indicates the time when a temporary hold period will end 10 Hours and Days displays during steps in installer configuration 11 The words Hold At are di...

Страница 7: ...4 On ds OFF Selects Daylight Saving Time calculation 15 On Heat AS OFF Selects Automatic Schedule for comfort temperature programming heat mode Not available if 4 is 0 16 On Cool AS OFF Selects Automa...

Страница 8: ...ostat compressor time delay is activated it will flash the set point for up to five minutes 10 Select Continuous Display Lighting dL In low lighting conditions display backlight improves the display c...

Страница 9: ...ss to advance the menu Three security settings are available in this menu item Use the or keys to select the lockout desired Lockout selections are Keypad Lockout and L Total Lockout Total Lockout loc...

Страница 10: ...32 33 Change UV Lamp This feature allows the thermostat to display the words Change UV Lamp Call for Service of UV bulb after a set time of UV bulb operation This is a reminder to maintain your UV sys...

Страница 11: ...ling may be required on the same day AUTO allows the thermostat to automatically select heating or cooling depending on the indoor temperature and the selected heat and cool temperatures When using AU...

Страница 12: ...h to copy this same program into other days press Copy and repeat steps 3 4 and 5 7 Press Run Schedule to return to normal operation Fill in the blank schedule on page 14 then Enter the Heating Progra...

Страница 13: ...d with the energy saving set tings shown in the table below for all days of the week If this program suits your needs simply set the thermostat clock and press the RUN key The Table 4 shows the factor...

Страница 14: ...24 VAC Common connection to terminal C for the remote sensor to operate The remote sen sor can be enabled or disabled in the Installer Configuration menu item 29 When remote sensor Remote is selected...

Страница 15: ...he thermostat the current temperature displayed will be the weighted average of the local sensor and the remote sensor using the formula local sensor weight local sensor temperature remote sensor weig...

Страница 16: ...he heating is operating correctly No Cool 1 Cooling system requires service or thermostat requires replacement Same as diagnostic for No Heat condition except set the thermostat to COOL and lower the...

Отзывы: