Installer/Configuration Menu

To enter the configuration menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Config touch key. This dis

-

plays screen reference #1 in the table below. Screen Reference numbers appear in top right corner of display. Press 

 to advance 

to the next menu item or 

 to return to a previous menu item. Press 

 or 

 to change a menu item option. Shaded items are not 

available if selected for Non-Programmable.

Screen 

Reference 

Number

HP1

HP2

Press 

Key

Displayed Factory 

(Default)

Press 

 or 

 to select 

from listed options

Comments

1

HP2

HP1

Selects Heat Pump 1 (HP1, 1 compressor), Heat Pump 2  

(HP2, 2 compressor or 2 speed compressor)

2

Days, (7) P

5 or 0

Programs per week. (7 days, 5-1-1 days or non-programmable)

3

(4) PS

2

Programs per day.

4 = Morning, Day, Evening, Night, 2 = Day, Night, Not available if 4 is 0

4

Cool-Off-Heat-Auto

Cool-Off-Heat, 

Off-Auto

System switch configuration

5

(On) E

OFF

Selects Energy Management Recovery. Not available if 4 is 0

6

(FA) Heat, Cr

SL

Selects Adjustable Anticipation, cycle rate, Heat

7

(FA) Cool, Cr

SL

Selects Adjustable Anticipation, cycle rate, Cool

8

(FA) AU/Cr

SL

Selects Adjustable Anticipation, cycle rate auxiliary

9

(OFF) CL

On

Selects Compressor Lockout

10

(On) dL

OFF

Selects Continuous Display backlight.

11

0 (Temperature)

5, LO to 5, HI

Selects Adjustable Ambient Temperature Display {range -5 (LO) to +5 (HI)}.

12

°F

°C

Selects °F/°C Display (temperature units in Fahrenheit or Celsius)

13

(On) b

OFF

Selects audible Beeper On/Off.

14

(On) ds

OFF

Selects Daylight Saving Time calculation.

15

(On) Heat, AS

OFF

Selects Automatic Schedule for comfort temperature  

programming, heat mode. Not available if 4 is 0.

16

(On) Cool, AS

OFF

Selects Automatic Schedule for comfort temperature  

programming, cool mode. Not available if 4 is 0.

17

(OFF) CS

On

Selects Cool Savings Feature On or Off.

18

CS Cool Savings (3)

1-2-3-4-5-6

Selects amount of Cool Savings adjustment.CS will not be displayed if CS 

is Off

19

(99) Heat, HL

 62-98

TEMPERATURE LIMIT, HEAT (max. heat set point). The limit can be 

adjusted up to 99°

20

(45) Cool, LL

46-82

TEMPERATURE LIMIT, COOL (min. cool set point). The limit can be 

adjusted down to 45°

21

OFF, 

 Keypad Lockout

L (total),  P (partial),

Temperature Limit

(limited temperature range)

Selects Keypad Lockout.

22

000

001-999

Selects Keypad Lockout Combination (active only if keypad Lockout is 

selected)

23

(On) Heat, FS

OFF

Fast second stage of heat

24

(On) Cool, FS

OFF

Fast second stage of cool

25

Remote (OFF)

On

Remote temperature sensor, enable/disable

26

Remote, in

Outdoor Remote

Remote temperature sensor (Indoor/Outdoor)

27

(On) LS

OFF

Local temp. Sensor enable/disable (only when Indoor Remote is

selected On)

28

(80) AO

-5 – 79

Selects Auxiliary Heat cut-out temperature. This item appears if outdoor 

sensor is installed and enabled

29

dM

dM and EC

Selects dehumidification or economizer thermostat option

30

(OFF) Hd

On

Selects Humidity Display alternate with time

31

Humidity 00 

(Room Humidity)

-18 LO, 20 HI

Selects Humidity Display adjustment

32

(OFF) Change UV Lamp

On

Selects Change UV Lamp feature

33

350 Days

25–1975

Change UV Lamp duration days

34

OFF Change Filter

On

Selects Change Filter feature

35

200 Hrs

25–1975

Selects Change Filter feature

Содержание 910121750

Страница 1: ...And Configuration Items 6 Installer Configuration Menu 7 Operating Your Thermostat 10 Heating 10 Cooling Dehumidifier 11 Choose The Fan Setting Auto or On 11 Choose The System Setting Cool Off Heat Au...

Страница 2: ...izontal Enfinity W CCH CCW MicroTech III Unit Controller Yes Vertical W VFC VFW Vertical Stacked W VHC Console W MHC MHW Horizontal Vertical SmartSource 1 Stage W GSH GSV MicroTech III SmartSource Uni...

Страница 3: ...rews Lev eling is for appearance only and will not affect thermostat operation 5 Connect wires to terminal block on base using appropri ate wiring schematic 6 Push excess wire into wall and plug hole...

Страница 4: ...ower for heating 24V power for heating C 24V common 24V common Y Compressor cool 1st stage Compressor cool 1st stage Y2 No output Compressor cool 2nd stage W1 Compressor heat 1st stage Compressor heat...

Страница 5: ...h the following heat pump systems Heat Pump Type 1 HP1 Single stage compressor system with electric backup Heat Pump Type 2 HP2 2 stage compressor system with electric backup Note After wiring see Ins...

Страница 6: ...iguration menu to change selections 9 Hold Until indicates the time when a temporary hold period will end 10 Hours and Days displays during steps in installer configuration 11 The words Hold At are di...

Страница 7: ...4 On ds OFF Selects Daylight Saving Time calculation 15 On Heat AS OFF Selects Automatic Schedule for comfort temperature programming heat mode Not available if 4 is 0 16 On Cool AS OFF Selects Automa...

Страница 8: ...ostat compressor time delay is activated it will flash the set point for up to five minutes 10 Select Continuous Display Lighting dL In low lighting conditions display backlight improves the display c...

Страница 9: ...ss to advance the menu Three security settings are available in this menu item Use the or keys to select the lockout desired Lockout selections are Keypad Lockout and L Total Lockout Total Lockout loc...

Страница 10: ...32 33 Change UV Lamp This feature allows the thermostat to display the words Change UV Lamp Call for Service of UV bulb after a set time of UV bulb operation This is a reminder to maintain your UV sys...

Страница 11: ...ling may be required on the same day AUTO allows the thermostat to automatically select heating or cooling depending on the indoor temperature and the selected heat and cool temperatures When using AU...

Страница 12: ...h to copy this same program into other days press Copy and repeat steps 3 4 and 5 7 Press Run Schedule to return to normal operation Fill in the blank schedule on page 14 then Enter the Heating Progra...

Страница 13: ...d with the energy saving set tings shown in the table below for all days of the week If this program suits your needs simply set the thermostat clock and press the RUN key The Table 4 shows the factor...

Страница 14: ...24 VAC Common connection to terminal C for the remote sensor to operate The remote sen sor can be enabled or disabled in the Installer Configuration menu item 29 When remote sensor Remote is selected...

Страница 15: ...he thermostat the current temperature displayed will be the weighted average of the local sensor and the remote sensor using the formula local sensor weight local sensor temperature remote sensor weig...

Страница 16: ...he heating is operating correctly No Cool 1 Cooling system requires service or thermostat requires replacement Same as diagnostic for No Heat condition except set the thermostat to COOL and lower the...

Отзывы: