36
Service & Maintenance
Service & Maintenance
• Disconnect from main supply before servicing the air conditioner.
• The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly
checked and the following items should be given due attention.
Components
Maintenance Procedures
Period
Air Filter
(Indoor Unit)
1. Remove any dust adhering to the
fi
lter by using a vacuum
cleaner or wash in lukewarm water (below 40°C) with a neutral
cleaning detergent.
2. Rinse the
fi
lter well and dry before placing it back onto the
unit.
3. Note: Never use gasoline, volatile substances or chemicals to
clean the
fi
lter.
At least once every 2
weeks.
More frequently if
necessary.
Indoor Unit
1. Clean any dirt or dust on the grille or panel by wiping it with a
soft cloth soaked in lukewarm water (below 40°C) and a neutral
detergent solution.
2. Note: Never use gasoline, volatile substances or chemicals to
clean the indoor unit.
At least once every 2
weeks.
More frequently if
necessary.
Condense Drain
Pan & Pipe
1. Check the cleanliness and clean it if necessary.
2. Check the condensate water
fl
ow.
Every 3 months.
Indoor Fan
Check if there is any abnormal noise.
If necessary.
Indoor / Outdoor
Coil
1. Check and remove the dirt between the
fi
ns.
2. Check and remove any obstacles which hinder air
fl
ow through
the indoor or outdoor.
3. Note: Avoid direct contact of any coil treatment material on the
plastic part. This may cause plastic part to deform as a result
of chemical reaction.
Every month.
Power Supply
1. Check the running current and voltage for indoor and outdoor
unit.
2. Check the electrical wiring and tighten the wire onto the terminal
block if necessary.
Every 2 months.
Every year.
Compressor
No maintenance needed if refrigerant circuit remains sealed.
However, check for refrigerant leak at joint and
fi
tting.
Every 6 months.
Indoor Models
1. Open the front panel
• Hold the panel at the recesses on the main unit
(2 recesses on right and left sides) and lift it until
it stops.
2. Remove the front panel
• While lifting the front panel further, slide it to the
right and pull it to the front side. The left rotating
shaft is detached. Slide the right rotating shaft to
the left and pull it to the front side to remove it.
3. Attach the front panel
• Align the right and left rotating shafts of the front
panel with the grooves and push them all the
way in.
• Gently close the front panel. (Push both ends
and the center on the front panel.)
Rotating
shaft
Recess on
main unit
Содержание 2MX45BGXV1
Страница 2: ......
Страница 4: ...ii ...
Страница 11: ...7 Application Information Refrigerant Circuit Diagrams Model 2MX45BGXV1 2MX50BGXV1 Model 3MX60BGXV1 4MX80BGXV1 ...
Страница 33: ...29 Outline Dimension Indoor Unit Model FLQ35 50 1080 0 928 0 218 0 65 0 630 0 400 0 230 0 Note Dimension in mm ...
Страница 36: ...32 Wiring Diagram Indoor Unit Model FTXN25 35MV1 Indoor Unit Model FTXN50MV1 ...
Страница 37: ...33 Wiring Diagram Indoor Unit Model FFQ25 35 50CXV1 Indoor Unit Model FDMQ25 35C2XV1 ...
Страница 38: ...34 Wiring Diagram Indoor Unit Model FDMQ50CXV1 Indoor Unit Model FLQ35EXV1 ...
Страница 39: ...35 Wiring Diagram Indoor Unit Model FLQ50EXV1 ...