19
Application Information
* The
fi
gures shown in the table are for information purpose only. They should be checked and selected to comply with
the local/national codes of regulations. This is also subject to the type of installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.
Model
FTXN25/35MV1
FTXN50MV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of core
mm
2
3.0
3
3.0
3
Interconnection cable size*
Number of core
mm
2
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
Model
FFQ25CXV1
FFQ35CXV1
FFQ50CXV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of conductors
mm
2
3.0
3
3.0
3
3.0
3
Interconnection cable size*
Number of conductors
mm
2
1.5
4
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
25
Model
FDMQ25C2XV1
FDMQ35CXV1
FDMQ50CXV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of conductors
mm
2
3.0
3
3.0
3
3.0
3
Interconnection cable size*
Number of conductors
mm
2
1.5
4
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
25
Model
FLQ35EXV1
FLQ50EXV1
Voltage Range**
220V - 240V / 1Ph / 50Hz+
Power supply cable size*
Number of conductors
mm
2
3.0
3
3.0
3
Interconnection cable size*
Number of conductors
mm
2
1.5
4
2.5
4
Recommended time delay fuse*
A
25
25
Содержание 2MX45BGXV1
Страница 2: ......
Страница 4: ...ii ...
Страница 11: ...7 Application Information Refrigerant Circuit Diagrams Model 2MX45BGXV1 2MX50BGXV1 Model 3MX60BGXV1 4MX80BGXV1 ...
Страница 33: ...29 Outline Dimension Indoor Unit Model FLQ35 50 1080 0 928 0 218 0 65 0 630 0 400 0 230 0 Note Dimension in mm ...
Страница 36: ...32 Wiring Diagram Indoor Unit Model FTXN25 35MV1 Indoor Unit Model FTXN50MV1 ...
Страница 37: ...33 Wiring Diagram Indoor Unit Model FFQ25 35 50CXV1 Indoor Unit Model FDMQ25 35C2XV1 ...
Страница 38: ...34 Wiring Diagram Indoor Unit Model FDMQ50CXV1 Indoor Unit Model FLQ35EXV1 ...
Страница 39: ...35 Wiring Diagram Indoor Unit Model FLQ50EXV1 ...
Страница 50: ......