Caution for Diagnosis
Service Diagnosis
165
Caution:
Operation stops suddenly. (Operation lamp blinks.)
Cause of above trouble could be "Operation mode butting".
Check followings;
Are the operation modes all the same for indoor units connected to Multi system outdoor unit?
If not set all indoor units to the same operation mode and confirm that the operation lamp is not
blinking.
Moreover, when the operation mode is in "Auto", set all indoor unit operation mode to "Cool" or
"Heat" and check again if the operation lamp is normal.
If the lamp stops blinking after the above steps, there is no malfunction.
Operation stops and operation lamp blinks only for indoor unit which the different operation
mode is set later. (The first set operation mode has priority.)
Troubleshooting
with the LED
Indication
Outdoor Unit
There are green and red LEDs on the PCB. The flashing green LED indicates normal equipment
condition, and the OFF condition of the red LED indicates normal equipment condition.
(Troubleshooting with the green LED)
The LED A (green) of the outdoor unit indicate microcomputer operation condition.
Even after the error is cancelled and the equipment operates in normal condition, the LED
indication remains.
Содержание 2MKD58BVM
Страница 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A ...
Страница 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v ...
Страница 7: ...Si12 411A vi Table of Contents ...
Страница 67: ...Specifications Si12 411A 56 Specifications ...
Страница 81: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 70 Printed Circuit Board Connector Wiring Diagram ...
Страница 131: ...Instruction Si12 411A 120 System Configuration CDK X D 25 35 50 60 C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 173: ...Instruction Si12 411A 162 System Configuration ...
Страница 227: ...Check Si12 411A 216 Service Diagnosis ...
Страница 268: ...Si12 411A Others 257 Part 8 Others 1 Others 258 1 1 Test Run from the Remote Controller 258 1 2 Jumper Settings 259 ...
Страница 295: ...Si12 411A iv Index ...
Страница 298: ...Si12 411A Printed in Singapore 03 2005 AK COS ...