Troubleshooting
Si10-417
154
Service Diagnosis
(3) Valve does not
open fully.
(Symptom)
The unit does not
cool nor heat (only for
heat pump model.)
IT is actuated.
Abnormal discharge
pipe temperature
Check the number of rotation
of shaft if it is 5 and half from
full open to complete close
using manual coil for
electronic expansion valve.
When the number of rotation
of shaft is less than the above
value, the valve may catch
anywhere of the body.
Valve Body Condition
(Symptom)
Check Method / Measure