Troubleshooting
Si10-417
160
Service Diagnosis
5.4.7 Discharge Pressure Check
Check No.8
5.4.8 Outdoor Unit Fan System Check
Check No.9
With DC Motor
Discharge pressure check
Replace compessor.
Open the stop valve.
Replace the pipe
installed at the site.
Clean.
Replace the
compressor.
(R1443)
YES
YES
YES
NO
NO
NO
NO
At
the heat exchanger and
air filter dirty?
Is the stop valve open?
Is the connection
pipe deformed?
YES
High
Check the outdoor unit fan
system.
Reconnect.
(R2857)
Outdoor unit fan running?
YES
Fan motor
lead wire connector
disconnected?
YES
NO
NO
Outdoor unit fan
system
functioning.
Go to
Check No. 15-1·2
.
A
A