SMLC-213-154
37
(2) 321 Dead band setting
Set the dead band of measurement display.
◆ 321 Measurement dead band
Set the dead band of measurement display.
By this setting, variation of less than this set value
is disregarded by 3-phase voltage, and zero-phase
voltage measurement display.
Setting range. 0.0 to 2.0% (0.1% step).
Selection by + and - , set value is updated by SET .
Default setting:0.0% (Nothing)
(3) 331 Analog output specification setting 【With an analog output option (DC0 to 5V or DC1 to 5V)】
Set the specification of analog output (DC0 to 5V/DC1 to 5V).
Selection by + and - , set value is updated by SET .
Default setting:DC1 to 5V or DC0 to 5V (Designation)
(4) 341 to 348 Analog output adjustment 【With an analog output option】
The bias and span of each analog output are adjusted.
341
Ao1 BIAS
adjustment
RESET/
SHIFT
348
Ao4 SPAN
adjustment
RESET/
SHIFT
RESET/
SHIFT
342
Ao1 SPAN
adjustment
343
Ao2 BIAS
adjustment
344
Ao2 SPAN
adjustment
347
Ao4 BIAS
adjustment
346
Ao3 SPAN
adjustment
345
Ao3 BIAS
adjustment
RESET/
SHIFT
RESET/
SHIFT
RESET/
SHIFT
RESET/
SHIFT
RESET/
SHIFT
◆ 341 AO (Analog output) 1 bias adjustment,
343 AO (Analog output) 2 bias adjustment,
345 AO (Analog output) 3 bias adjustment,
347 AO (Analog output) 4 bias adjustment.
The bias of each analog output is adjusted.
Setting range:±10.0% (0.1% step)
Selection by + and - , set value is updated by SET .
◆ 342 AO (Analog output) 1 span adjustment,
344 AO (Analog output) 2 span adjustment,
346 AO (Analog output) 3 span adjustment,
348 AO (Analog output) 4 span adjustment.
The span of each analog output is adjusted.
Setting range:±10.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Dead band of measurement
New setting
Current setting
Setting No.
Setting factor
Analog output specification
New setting
Current setting
Setting No.
Setting factor
0 to 5V
+
-
1 to 5V
-
+
Ao1 span adjustment
New setting
Current setting
Setting No.
Setting factor