SMLC-213-154
21
Setting mode 2. Function table
Set No.
Function
Functional description
Default
setting
Important
setting
Page
211
Voltage range
Set the voltage measurement range (VT ratio).
6600V
○
32
212
Zero-phase voltage
scale
Display ON/OFF of ×1/√
3
is set as a scale of zero-phase
voltage.
×1/√3
display OFF
○
32
213
Frequency range
Set the full scale of frequency meter. And, set this
output range of analog output.
45.0 to
65.0Hz
32
221A (
9
) AO1 output factor
Set the output factor of AO1 (analog output 1).
MVo
○
33
222A (
9
) AO2 output factor
Set the output factor of AO2 (analog output 2).
V(RS)
○
33
223A (
9
) AO3 output factor
Set the output factor of AO3 (analog output 3).
V(ST)
○
33
224A (
9
) AO4 output factor
Set the output factor of AO4 (analog output 4).
V(TR)
○
33
225A (
9
) Low input cut
Set the function which makes a lower limit the output at
the case of small input (3-phase voltage is 0.5% or less.
zero-phase voltage is 1.0% or less) in analog output.
OFF
(No
operation)
33
231 (
9
)
External operation
input 1 function
Set the function of the external operation input 1.
Alarm reset
(
10
)
○
34
232 (
9
)
External operation
input 2 function
Set the function of the external operation input 2.
Maximum /
Minimum reset
(
10
)
○
34
241
Phase voltage ON/OFF Set the ON/OFF of phase voltage measurement display.
ON (
11
)
35
242
Line voltage ON/OFF Set the ON/OFF of line voltage measurement display.
ON
35
243
Zero-phase voltage
ON/OFF
Set the ON/OFF of zero-phase voltage measurement display. ON
35
244
Frequency ON/OFF
Set the ON/OFF of frequency measurement display.
ON
35
251
Initialization of
setting value
All set values are initialized. (Return to initial set
value)
-
35
Setting mode 3. Function table
Set No.
Function
Functional description
Default
setting
Important
setting
Page
311
Zero-phase input
voltage
Set the zero-phase input voltage.
190V (
13
)
○
36
312
Rated frequency
Set the rated frequency of a zero-phase input is set. 50Hz
○
36
321
Measurement dead
band
Set the dead band of measurement display.
0.0%
37
331 (
9
)
(
12
)
Analog output
specification
Set the analog output specification.
DC1 to 5V or
DC0 to 5V
(Designation)
37
341 (
9
) AO1 BIAS adjustment Set the BIAS value of AO1 (Analog output 1).
0.0%
37
342 (
9
) AO1 SPAN adjustment Set the SPAN value of AO1 (Analog output 1).
100.0%
37
343 (
9
) AO2 BIAS adjustment Set the BIAS value of AO2 (Analog output 2).
0.0%
37
344 (
9
) AO2 SPAN adjustment Set the SPAN value of AO2 (Analog output 2).
100.0%
37
345 (
9
) AO3 BIAS adjustment Set the BIAS value of AO3 (Analog output 3).
0.0%
37
346 (
9
) AO3 SPAN adjustment Set the SPAN value of AO3 (Analog output 3).
100.0%
37
347 (
9
) AO4 BIAS adjustment Set the BIAS value of AO4 (Analog output 4).
0.0%
37
348 (
9
) AO4 SPAN adjustment Set the SPAN value of AO4 (Analog output 4).
100.0%
37
Note(
9
) Setting item is not displayed in case there is no corresponding option.
Note(
10
) This is initial value with an alarm output option. An initial value when there is no alarm output option
constitutes the following.
Input 1:Maximum / Minimum reset
Input 2:Measurement factor change
Note(
11
) In the case of line voltage input specification, a initial value constitutes OFF.
Note(
12
) Setting item is not displayed other than analog output DC0 to 5V or DC1 to 5V specification.
Note(
13
) An initial value is set to 110V in case a zero-phase voltage channel range is 150V.