SALC-212-174
25
(5) Setting of analog output.
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Sets the analog
output sensitivity
(% of a rated
input power value
to an output upper
limit) of current.
(224A)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press MODE
(211) (221A)
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
(222A) (223A) (224A)
Select a output sensitivity by + and -
Press SET
Selected output sensitivity is entered
Press DISPLAY
Returns to display mode.
34
Sets the output cut
function at the
case in minute
input (0.5% or
less) of analog
output.
(225A)
Press SET and RESET/SHIFT together for longer than 3 seconds
Press MODE
(211) (221A)
Press RESET/SHIFT
Press RESET/SHIFT
Press RESET/SHIFT
(222A) (223A) (224A)
Press RESET/SHIFT
Select a low Input cut ON/OFF by + and -
Press SET
(225A)
Selected action is entered
Press DISPLAY
Returns to display mode.
34
(6) Setting of alarm output.
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Sets the reset
method of alarm
output.
(122AL)
Press SET for longer than 3 seconds
Press MODE
Press RESET/SHIFT
(111) (121AL) (122AL)
Select a reset method by + and -
Press SET
The selected reset method is entered
Press DISPLAY
Returns to display mode.
29
Sets the contact
delay time of
alarm output.
(123AL)
Press SET for longer than 3 seconds
Press MODE
Press RESET/SHIFT
(111) (121AL) (122AL)
Press RESET/SHIFT
Select an contact delay time by + and -
Press SET
(123AL)
The selected contact delay time is entered
Press DISPLAY
Returns to
display mode.
29
(7) Demand current detection setting.
Each parenthesized number shows a setting number and this number is displayed on the setting screen.
Items
Setting and operation procedures
Page
Sets the upper
limit alarm value
of demand current.
(131H)
Press SET for longer than 3 seconds
Press MODE
(111) (121AL)
Press MODE (It is operation needlessness if there is no option)
(131H)
Select a upper limit alarm value by + and -
Press SET
Selected upper limit alarm value is entered
Press DISPLAY
Returns to
display mode.
30