SALC-212-174
29
(2) 121AL~123AL Alarm output setting 【With option】
Various setting and an output test are performed about an alarm output.
121AL
Alarm factor
122AL
Alarm reset method
123AL
Alarm contact delay time
RESET/
SHIFT
MAX/MIN
RESET/
SHIFT
MAX/MIN
RESET/
SHIFT
MAX/MIN
◆ 121AL Alarm output factor setting
Sets the factor of alarms outputs. Selection by + and - , set value is updated by SET .
Default setting:1 (Demand current, OR of each phase)
OFF:Nothing
-
+
1:Demand current
(OR of each phase)
2:Demand current
A(U)
-
+
-
+
3:Demand current
A(V)
-
+
4:Demand current
A(W)
+
-
5:Demand current
OR of A(U) and A(W)
+
-
3-phase 3-wire
OFF:Nothing
-
+
1:Demand current
-
+
Single-phase
◆ 122AL Alarm reset method setting.
Action at the case of a reset of alarm output can be selected
from AUTO (automatic reset) and HOLD (manual reset).
In "AUTO (automatic reset)", an alarm output is OFF according
to a reset of an alarm. In "HOLD (manual reset)", even after
an alarm reset, an output holds ON.
It performs a return (output OFF) in RESET/SHIFT .
Selection by + and - , set value is updated by SET .
Default setting:AUTO (Automatic reset)
AUTO
(Automatic reset)
-
+
-
+
HOLD
(Manual reset)
◆ 123AL Alarm contact delay time
Sets the contact delay time of alarm. The setting range is 0 to 300 seconds (1-second step).
Selection by + and - , set value is updated by SET .
Default setting:0 second (With no contact delay)
New setting
Setting № Now setting
Alarm factor