FSDLC-220-047
18
5.6 Performance
Item
Specification
Setting accuracy (
6
)
±0.1% (% of input span)
Display accuracy (
7
)(
8
) ±0.1% (% of input span) ±1digit
Reproducibility of the
operating point (
6
)
±0.1% (% of input span)
Operating time
±0.25 seconds of set value (Setting value 0 seconds = 0.5 ± 0.25 seconds)
Set value is contact delay time (
9
)
Reset time
0.5 seconds or less (
9
)
Starting delay time
±0.25 seconds of set value
Influence of temperature 0.2% (For input span) / 23±10℃
Influence of auxiliary
supply voltage variation
0.1% (For input span) / Within variation range
Operation period
About 0.1 second
Response time
About 0.5 second (
9
)
When a step change of 90% to 110% of the operating value setting is given (at CD = 0 seconds)
Overload
capacity
Voltage input 2 times 10 seconds and 1.5 times continuation of rated voltage.
Current input 10 times 5 seconds and 1.5 times continuation of rated current.
Aux. supply
1.5 times 10 seconds of rated voltage. Variable range upper limit continuous.
Insulation resistance
Between electric circuit and case.
Above 50MΩ at DC500V
Between input, output terminals and auxiliary supply
terminals.
Between input terminals and output terminals.
Between
output
terminals
2 contacts Between AL1 and AL2
3 contacts Between AL1 and AL2 and AL3
4 contacts Between AL1・AL2 and AL3・AL4 (
10
)
Power frequency
withstand voltage
Between electric circuit and case.
AC2000V (50/60Hz) 1 minute.
There must not be malfunction.
Between input, output terminals and auxiliary supply
terminals.
Between input terminals and output terminals.
Between
output
terminals
2 contacts Between AL1 and AL2
3 contacts
Between AL1 and AL2
AC1000V (50/60Hz) 1 minute.
There must not be malfunction.
Between AL1・AL2 and AL3
AC2000V (50/60Hz) 1 minute.
There must not be malfunction.
4 contacts Between AL1・AL2 and AL3・AL4 (
10
)
Impulse withstand
voltage
Between electric circuit and case.
5kV 1.2/50μs. Both positive and negative polarity
for 3 times each. There must not be malfunction.
Vibration
Vibration of vibration frequency 16.7Hz,Double amplitude 1mm.
In the direction of X Y Z for each 10 minutes. There must not be malfunction.
Shock
Error:98m/s
2
, X, Y, Z direction for each 3 times.
Duration:294m/s
2
, X, Y, Z direction for each 3 times.
Power failure guarantee
Each set value is data-saved by non-volatilized memory.
Material of case
Case:Flame resisting ABS resin , Name plate:Polyester film
Color
Munsell N1.5 (Black)
Operating temperature
and humidity limits
-10 to +55℃ , 5 to 90%RH (Non condensing)
Storage temperature limits
-25 to +70℃
Mass
Approx.
180g
Accessories
Unit symbol sheet,Instruction manual
Note(
6
) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% of input span)
Note(
7
) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% of input span) ±1digit.
Note(
8
) If the scaling span is 10,000 or more (5 digits excluding the decimal point), it is
±
0.1
%
(for input
span)
±
2 digits. If the scaling span is 10,000 or more and the input is less than 1V, it is
±
0.2
%
(for
input span)
±
2 digits.
Note(
9
) When the average number is once. If the average number is 4, 8, 16, or 32, the operating time and
reset time will vary depending on the conditions.
Note(
10
) In case of 4-contact output, there is no insulation between AL1 and AL2 and between AL3 and AL4.
● About transition of a contact
In DC load switching, transition of a contact may start and a contact may not return by uneven connection.
A contact evaporates locally with arc heat, what carried out contact evaporation to + polarity → - polarity
carries out the adhesion deposition of this, and a single-sided convex opposite side serves as a concave.
〈Measure〉Be sure to use each relay within a rated load.