FSDLC-220-047 

 

17

 
 

5.5 Setting value 

№ 

Contents 

Mark 

Default setting value 

Setting range 

2 contact 

outputs 

3 contact 

outputs 

4 contact 

outputs 

1  Unit display 

UNIT 

 

% 

 

,m,℃,m

/h,ppm,pH,TPm,×10kg,

Ω,kW,No unit 

2  Minimum value scaling 

MIN 

 

0.0 

 

-9999 to 9999    -9.99 to 99.99 
-99.9 to 999.9    0.000 to 9.999 

3  Maximum value scaling 

MAX 

 

100.0 

 

AL1 

Output mode 

ALMD1 

High 

High 

High 

High:H operation,Low:L operation,

 

OFF :With no operation 

Operation value 

COMP1 

70.0 

80.0 

80.0 

Measurement display range -25 to 
+125% (Real scale) 

Dead band 

D.B.1 

 

3.0 

 

0.5 to 50.0% 

Excitation mode 

EXMD1 

 

0N 

 

ON:Excitation,OFF:Non-excitation 

Contact delay time (CD)  C.D.1 

 

 

0 to 180s 

AL2 

Output mode 

ALMD2 

Low 

High 

High 

High:H operation,Low:L operation,

 

OFF :With no operation 

10 

Operation value 

COMP2 

30.0 

70.0 

70.0 

Measurement display range -25 to 
+125% (Real scale) 

11 

Dead band 

D.B.2 

 

3.0 

 

0.5 to 50.0% 

12 

Excitation mode 

EXMD2 

 

0N 

 

ON:Excitation,OFF:Non-excitation 

13 

Contact delay time (CD)  C.D.2 

 

 

0 to 180s 

14 

AL3 

Output mode 

ALMD3 

- 

Low 

Low 

High:H operation,Low:L operation,

 

OFF :With no operation 

15 

Operation value 

COMP3 

- 

30.0 

30.0 

Measurement display range -25 to 
+125% (Real scale) 

16 

Dead band 

D.B.3 

- 

3.0 

0.5 to 50.0% 

17 

Excitation mode 

EXMD3 

- 

ON 

ON:Excitation,OFF:Non-excitation 

18 

Contact delay time (CD)  C.D.3 

- 

0 to 180s 

19 

AL4 

Output mode 

ALMD4 

- 

Low 

High:H operation,Low:L operation,

 

OFF :With no operation 

20 

Operation value 

COMP4 

- 

20.0 

Measurement display range -25 to 
+125% (Real scale) 

21 

Dead band 

D.B.4 

- 

3.0 

0.5 to 50.0% 

22 

Excitation mode 

EXMD4 

- 

ON 

ON:Excitation,OFF:Non-excitation 

23 

Contact delay time (CD)  C.D.4 

- 

0 to 180s 

24  Starting delay time (SD) 

S.D. 

 

 

1 to 180s 

25  Bias point calibration 

CBIAS 

 

0.00 

 

-9.99 to 9.99% (% of input span) 

26  Span point calibration 

CSPAN 

 

0.00 

 

-9.99 to 9.99% (% of input span) 

27  Average number 

AVE 

 

 

1,4,8,16,32 

28  Pre-alarm 

PREAL 

 

OFF 

 

ON:Pre-alarm ON, OFF:Pre-alarm OFF 

< Notes of setting > 
・The decimal point position change of scaling is made by the minimum value scaling.  

If the decimal point position is changed, the decimal point position of maximum value scaling and operation 
values 1 to 4 will also change.  If the decimal point position is changed, please be sure to check the set 
value of a maximum value scaling and an operation value. 

・When changing the scaling, set the operation values 1 to 4 within the measurement display range (see below).  

Even if the output mode is set to OFF, keep it within the measurement display range.

 

・An operation value can be set up in -25 to +125% of the measurement display range (minimum value scaling  

to maximum value scaling).  
(Example) Input 4 to 20mA,  
          Operation value -25.0,  
          Output mode is "Low" setting. 

 

Becomes the L detected at the input 0mA, 
can also be used as a disconnection 
detection. 

 

 

・After setting change, in case a set value combination error occurs, it becomes a setting error display.  

Please push the 

 key and set up the right set value (in set value change mode). 

125% 

100% 

50% 

0% 

-25% 

24mA 

20mA 

12mA 

 4mA 

 0mA 

Содержание FINE Series

Страница 1: ...FSDLC 220 047 INSTRUCTION MANUAL PLUG IN TRANSDUCER FINE SERIES ALARM SETTER FSDLC...

Страница 2: ...ning of the screw Preparation This product must be set before use Please set correctly after reading this instruction manual Maintenance and inspection Inspection in energized state is dangerous This...

Страница 3: ...part 7 3 2 Each display mode and operation 7 3 3 Measurement mode 8 3 4 Display mode 9 3 5 Setting mode 10 3 6 Calibration 12 4 Block diagram and principle of operation 4 1 Block diagram 12 4 2 Princi...

Страница 4: ...setting accuracy is 0 1 of input span The display accuracy is 0 1 1 digit of input span 0 2 for voltage input less than 1V Various settings can be changed with the front switch The measured value rea...

Страница 5: ...1 2 3 4 UR 2 INPUT Voltage input Electrical wire Attach as nameplate surface is upward Attach as the main body case is downward Mounting base UR 2 combines an alarm setter of voltage input and please...

Страница 6: ...work Touching terminals etc while wet hands may cause electric shock Because burnout accident may be caused by wiring differences please be careful of wiring Also it is dangerous to inspect it in pla...

Страница 7: ...e power line used as the source of a noise and steep voltage and current as much as possible Please use shielding wire for the bottom of the remarkable environment of a noise Environmental condition 1...

Страница 8: ...s to each mode by those with four type and the following switch operations Measurement mode Input value maximum value and minimum value are displayed Display mode Setting item is displayed in order an...

Страница 9: ...y push 3 seconds of ENT key Reset by push 3 seconds of ENT key Reset of minimum value display Measurement value Unit 5 0 0 Maximum value display P E A K 1 0 0 0 Reset of maximum value display P E A K...

Страница 10: ...UP UP SHIFT Measurement value display U N I T M I N 0 0 0 0 M A X 1 0 0 0 C B I A S 0 0 0 0 C S P A N 0 0 0 0 S D 0 0 0 s A V E MODE SHIFT C D 1 0 0 0 s A L M D 1 H i g h D B 1 0 3 0 E X M D 1 O N A L...

Страница 11: ...e simultaneously Mode Measurement setting change Movement of the setting item of AL1 to AL4 and the shift of set value Measurement value display Blinking Pushed for 3 seconds simultaneously 5 0 0 UP M...

Страница 12: ...other digits decimal point does not display U N I T Middle omission U N I T U N I T m U N I T m U N I T k W U N I T k W ENT ENT ENT UP UP UP After deciding set value change a setting item symbol is b...

Страница 13: ...otection circuit and becomes the DC voltage below constant voltage This voltage goes into an amplifier 2 The input is converted into the suitable voltage range in an amplifier This voltage constitutes...

Страница 14: ...Relay excitation status display MAX 4 contacts Monitor lamp lights when each relay is excited The monitor lamp blinks during the delay time when the pre alarm setting is ON Relay and monitor lamp oper...

Страница 15: ...ly OFF or relay non excitation Relay excitation Terminal AL2 AL1 C1 6 5 7 AL4 AL3 C2 6 5 7 UNIT n UNIT n 1 Terminal AL2 AL1 C1 6 5 7 AL4 AL3 C2 6 5 7 UNIT n UNIT n 1 Terminal AL2 AL1 C1 6 5 7 AL4 AL3...

Страница 16: ...Starting delay function After an auxiliary supply apply detection action is performed after a starting delay time Operation value setting Relay action ON OFF Setting value Input Contact delay setting...

Страница 17: ...arm function constitutes OFF Relay action and pre alarm in over input detection Output mode setting Excitation H Pre alarm setting ON Action of the pre alarm in contact delay time blinking Operation v...

Страница 18: ...tion 20 Operation value COMP4 20 0 Measurement display range 25 to 125 Real scale 21 Dead band D B 4 3 0 0 5 to 50 0 22 Excitation mode EXMD4 ON ON Excitation OFF Non excitation 23 Contact delay time...

Страница 19: ...inute There must not be malfunction 4 contacts Between AL1 AL2 and AL3 AL4 10 Impulse withstand voltage Between electric circuit and case 5kV 1 2 50 s Both positive and negative polarity for 3 times e...

Страница 20: ...ulation range Please check power supply voltage and give as regulation range Input is abnormal Please give a measurement value as a check and a normal input Error of set value Please confirm set value...

Страница 21: ...ormally open contact a contact AC200 220V 50 60Hz A8 DC1 to 5V About 1M 3 Alarm output 3 contacts DC100 110V B3 DC 60mV About 1M Normally close contact b contact B5 DC 1V About 1M 4 Alarm output 4 con...

Страница 22: ...fice 11 13 Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 Fax 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 Fax 81 774...

Отзывы: