5.5 Setting value
№
Contents
Mark
Default setting value
Setting range
2 contact
outputs
3 contact
outputs
4 contact
outputs
1 Unit display
UNIT
%
%
,m,℃,m
3
/h,ppm,pH,TPm,×10kg,
Ω,kW,No unit
2 Minimum value scaling
MIN
0.0
-9999 to 9999 -9.99 to 99.99
-99.9 to 999.9 0.000 to 9.999
3 Maximum value scaling
MAX
100.0
4
AL1
Output mode
ALMD1
High
High
High
High:H operation,Low:L operation,
OFF :With no operation
5
Operation value
COMP1
70.0
80.0
80.0
Measurement display range -25 to
+125% (Real scale)
6
Dead band
D.B.1
3.0
0.5 to 50.0%
7
Excitation mode
EXMD1
0N
ON:Excitation,OFF:Non-excitation
8
Contact delay time (CD) C.D.1
0
0 to 180s
9
AL2
Output mode
ALMD2
Low
High
High
High:H operation,Low:L operation,
OFF :With no operation
10
Operation value
COMP2
30.0
70.0
70.0
Measurement display range -25 to
+125% (Real scale)
11
Dead band
D.B.2
3.0
0.5 to 50.0%
12
Excitation mode
EXMD2
0N
ON:Excitation,OFF:Non-excitation
13
Contact delay time (CD) C.D.2
0
0 to 180s
14
AL3
Output mode
ALMD3
-
Low
Low
High:H operation,Low:L operation,
OFF :With no operation
15
Operation value
COMP3
-
30.0
30.0
Measurement display range -25 to
+125% (Real scale)
16
Dead band
D.B.3
-
3.0
0.5 to 50.0%
17
Excitation mode
EXMD3
-
ON
ON:Excitation,OFF:Non-excitation
18
Contact delay time (CD) C.D.3
-
0
0 to 180s
19
AL4
Output mode
ALMD4
-
Low
High:H operation,Low:L operation,
OFF :With no operation
20
Operation value
COMP4
-
20.0
Measurement display range -25 to
+125% (Real scale)
21
Dead band
D.B.4
-
3.0
0.5 to 50.0%
22
Excitation mode
EXMD4
-
ON
ON:Excitation,OFF:Non-excitation
23
Contact delay time (CD) C.D.4
-
0
0 to 180s
24 Starting delay time (SD)
S.D.
5
1 to 180s
25 Bias point calibration
CBIAS
0.00
-9.99 to 9.99% (% of input span)
26 Span point calibration
CSPAN
0.00
-9.99 to 9.99% (% of input span)
27 Average number
AVE
1
1,4,8,16,32
28 Pre-alarm
PREAL
OFF
ON:Pre-alarm ON, OFF:Pre-alarm OFF
< Notes of setting >
・The decimal point position change of scaling is made by the minimum value scaling.
If the decimal point position is changed, the decimal point position of maximum value scaling and operation
values 1 to 4 will also change. If the decimal point position is changed, please be sure to check the set
value of a maximum value scaling and an operation value.
・When changing the scaling, set the operation values 1 to 4 within the measurement display range (see below).
Even if the output mode is set to OFF, keep it within the measurement display range.
・An operation value can be set up in -25 to +125% of the measurement display range (minimum value scaling
to maximum value scaling).
(Example) Input 4 to 20mA,
Operation value -25.0,
Output mode is "Low" setting.
Becomes the L detected at the input 0mA,
can also be used as a disconnection
detection.
・After setting change, in case a set value combination error occurs, it becomes a setting error display.
Please push the
key and set up the right set value (in set value change mode).
125%
100%
50%
0%
-25%
24mA
20mA
12mA
4mA
0mA