40
Bypass: This zone is shielded for the arming, when disarm, the zone will resume non -bypass
status.
Isolate: The zone is stop, when device arm again after disarming, the isolated zone is still
stop
Operation method: [Encode c[OK]+[Admin password/operator password]
Encode command is composed as follows:
1 001
①
②
No.
Note
①
Bypass/isolation type code.
②
Zone number
,
range is 001~256. Such as zone
1
,
number is 001
5.7 Zone Setup
5.7.1 Type Setup
You can set zone parameter.
Operation method: [encode c[OK]+[Installer password].
Encode command is as follows:
1
④
1
③
001
①
00
②
No.
Note
Zone number
,
range is 001~256. Such as zone
1
,
no. is 001
Zone type code
Enter delay
,
range is 0~240
,
unit is s
,
besides
delay zone, when set other zone, you can ignore
this parameter.
Exit delay
,
range is 0~240
,
unit is s
,
besides
delay zone, other zone setup can ignore this
parameter.