Daewoo DSB-F0969GLH-V Скачать руководство пользователя страница 33

 

31 

The air and humidity left inside  the refrigerant circulation 

can  cause  compressor  malfunction.  After  having 
connected the indoor  and outdoor units, bleed  the air and 
humidity    from    the    refrigerant    circulation    using    a 
vacuum pump.  
(1)

 

Unscrew and remove the caps from the  2 - way and       
3-way valves.  

(2)

 

Unscrew and  remove  the cap from the service port. 

(3)

 

Connect  the  vacuum pump hose to the service port. 

(4)

 

Operate the vacuum pump for  10 - 15  minutes until       
an absolute vacuum of 10 mm Hg has been reached. 
(5) With the vacuum pump still in operation ,  close 
the       low - pressure  knob on the vacuum pump 
coupling.       Stop the vacuum pump.  

(6)

 

Open the 2 - way valve by 1/4  turn and then close it       
after10 seconds. Check all the joints for leaks using       
liquid soap or an electronic leak device.  

(7)

 

Turn the body of the 2-way and 3-way valves.       
Disconnect the vacuum pump hose.  

(8)

 

Replace and tighten all the caps on the valves.  

INSTALLATION MANUAL--- final 

stages  

1.

 

Wind insulating covering around the joints of 

the ind    oor unit and fix it with insulating tape. 

2.

 

Fix  the  exceeding  part  of  the  signal  cable  

to  the     piping or to the outdoor unit. 

3.

 

Fix the piping to the wall ( after having coated 

it with    insulating tape) using clamps or insert  them 
into pla    stic slots. 

4.

 

Seal the hole  in  the wall through which the 

piping is    passed so that no air or water can fill. 

Indoor unit test 

 Do the ON/OFF and FAN  operate normally? 
 Does the MODE  operate normally? 
 Do the set point and TIMER function properly? 
 Does each lamp light normally? 
 Do the flap  for air flow direction operate normally?  

Is the condensed water drained regularly?  

Outdoor unit test 

 Is  there  any  abnormal  noise  or  vibration  during      

operation? 

 Could the noise ,  the air flow or the condensed water      

drainage disturb the neighbours?  Is there any coolant 
leakage? 

Note:  the  electronic controller allows  the compressor to          
start    only    three    minutes    after  voltage  has  reached          
the system.

 

Содержание DSB-F0969GLH-V

Страница 1: ......

Страница 2: ...CONTENTS SAFETY PRECAUTIONS 1 NAMES OF THE PARTS 4 INDOOR UNIT DISPLAY 5 EMERGENCY FUNCTION AUTO RESTART FUNCTION 6 REMOTE CONTROL 7 MODES OF OPERATION 10 ...

Страница 3: ...1 PROTECTION 17 INSTALLATION MANUAL 18 MAINTENANCE 27 TROUBLESHOOTING 28 ...

Страница 4: ...Carry out a test cycle after installing the air conditioner and record the operating data The ratings of the fuse installed in the built in control unit are T 5A 250V The user must protect the indoor unit with a fuse of suitable capacity for the maximum input current or with another overload protection device Ensure that the mains voltage corresponds to that stamped on the rating plate Keep the sw...

Страница 5: ...is appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by childre...

Страница 6: ...t the Service Centre The prolonged use of the device in such conditions could cause fire or electrocution Have repairs carried out only by an authorised Service Centre of the manufacturer Incorrect repair could expose the user to the risk of electric shock etc Unhook the automatic switch if you foresee not to use the device for a long time The airflow direction must be properly adjusted The flaps ...

Страница 7: ...uced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Do not climb onto or place any heavy or hot objects on top of the appliance Do not leave windows or doors open for long when the air conditioner is operating Do not direct the airflow onto pl...

Страница 8: ...6 NAMES OF THE PARTS ...

Страница 9: ...7 The conditioner is made up of two or more units ...

Страница 10: ... copper pipes properly insulated and an electrical con necting cable The indoor unit is installed on the walls of the room to be conditioned The outdoor unit is installed on the floor or on the wall on suitable brackets INDOOR UNIT DISPLAY ...

Страница 11: ...tors may vary according to the model but their function is the same No Led Function POWER Shows that the unit is powered 1 2 3 4 5 Temperature display if present Indicates the set temperature in or SLEEP mode TIMER mode Unit working SLEEP TIMER RUN ...

Страница 12: ... FUNCTION AUTO RESTART FUNCTION The shape and position of the emergency button may vary according to the model but their function is the same Remark the external static pressure of heat pumps is 0 Pa for all models ...

Страница 13: ...11 REMOTE CONTROL ...

Страница 14: ...shape and position of buttons and indicators may vary according to the model but their function is the same The unit confirms the correct reception of each press button with a beep Functions of horizontal swing and health are optional Remote control DISPLAY Meaning of symbols on the liquid crystal display ...

Страница 15: ...13 REMOTE CONTROL ...

Страница 16: ...ton when the symbol is displayed the COOL remote control is adjusted in only cooling mode If you push whatever button when the symbol is displayed HEAT the remote control is adjusted in heating mode Cooling only models only symbol is displayed COOL whatever button you press the remote control is adjusted in only cooling mode BE CAREFUL For heat pumps if you adjust the remote control in cooling mod...

Страница 17: ...t by the vertical deflectors The air outlet flow is uniformly distributed in the room It is possible to position the direction of the air in the optimal solution The key activates the FLAP the air flow is directed alternatively from up to down In order to guarantee an even diffusion of the air in the room In cooling mode orient the flaps in horizontal direction In heating mode orient the flaps dow...

Страница 18: ...ir To activate the heating function HEAT press the MODE button until the symbol appears on the display With the keys or set a temperature higher than that of the room To optimize the functioning of the conditioner adjust the temperature 1 the speed 2 and the direction of the air flow 3 by pressing the keys indicated The appliance is fitted with a Hot Start function which delays appliance to startu...

Страница 19: ...start program the working mode with the key MODE 2 and the fan speed with the key FAN 3 Switch the conditioner off with the key ON OFF Note To cancel the setted function press the TIMER button again Note In case of power off it is necessary to set TIMER ON again TIMER MODE TIMER OFF To set the automatic switching off of the air conditioner The timed stop is programmed with the appliance on Press T...

Страница 20: ...18 MODES OF OPERATION ...

Страница 21: ...19 ...

Страница 22: ... 20 26 DRY 18 26 COOL 23 To optimize the working of the conditioner adjust the temperature only 1 the speed 2 and the direction of the air flow 3 by pressing the buttons indicated SLEEP MODE To activate the SLEEP mode of operation press the SLEEP button on the remote control until the symbol Daewoo s appears in the display The function SLEEP automatically adjusts the temperature to make the room m...

Страница 23: ...perature is gradually decreased by 2 during the first 2 hours of work During the next 8 hours temperature will keep as the decreased temperature After 10 hours running in sleep mode the air conditioner is swicthed off automatically ...

Страница 24: ...22 ...

Страница 25: ...23 ...

Страница 26: ...perature is over 43 Room temperature is below 21 Room temperature is below 18 C No MODE 2 1 3 Heating Cooling Dry No MODE Outdoor air temperature is over 24 Room temperature is over 27 Outdoor air temperature is below 7 Outdoor air temperature is over 52 Room temperature is below 21 Room temperature is below 18 C After stopping and restarting the air coditioner or after changing the mode during op...

Страница 27: ...rce of heat steam or flammable gas Install the unit near an electric socket or private circuit Do not install the unit where it will be exposed to direct sunlight Install the unit where connection between indoor and outdoor unit is as easy as possible Install the unit where it is easy to drain the condensed water Check the machine operation regularly and leave the necessary spaces as shown in the ...

Страница 28: ...ting installation decide on the position of the indoor and outdoor units taking into account the minimum space required around the units Install the indoor unit in the room to be air conditioning avoiding to install in corridors or communal areas Install the indoor unit at a height of at least 2 5 m from the ground To install proceed as follows 1 By using a level put the mounting plate in a perfec...

Страница 29: ...iciure by removing a screw or by breaking the hooks 3 For the electrical connections see the circuit diagram on the right part of the unit under the front panel 4 Connect the cable wires to the screw terminals by following the numbering Use wire size suitable to the electric power input see name plate on the unit and according to all current national safety code requirements 5 The cable connecting...

Страница 30: ...indoor unit pipe cap check that there is no debris inside 2 Insert the fare nut and create a flange at the extreme end of the connection pipe 3 Tighten the connections by using two wrenches working in opposite directions The indoor unit condensed water drainage is fundamental for the success of the installation 1 Place the drain hose below the piping taking care not to create siphons 2 The drain h...

Страница 31: ...he following procedure must be observed before co nnecting the pipes and connecting cables decide which is the best position on the wall and leave enough space to be able to carry out maintenance easily Fasten the support to the wall using screw anchors which are particularly suited to the type of wall Use a larger quantity of screw anchors than normally required for the weight they have to bear t...

Страница 32: ...leakage pay attention to the following points 1 Tighten the flare nuts using two wrenches Pay atten tion not to damage the pipes 2 If the tightening torque is not sufficient there will probably be some leakage With excessive tightening torque there will also be some leakage as the flange could be damaged 3 The surest system consists in tightening the connecti on by using a fix wrench and a torque ...

Страница 33: ... Replace and tighten all the caps on the valves INSTALLATION MANUAL final stages 1 Wind insulating covering around the joints of the ind oor unit and fix it with insulating tape 2 Fix the exceeding part of the signal cable to the piping or to the outdoor unit 3 Fix the piping to the wall after having coated it with insulating tape using clamps or insert them into pla stic slots 4 Seal the hole in ...

Страница 34: ... standard charge 3m 3m 3m 4m 4m 4m Maximum distance between indoor and outdoor unit 15m 15m 15m 15m 15m 15m Additional refrigerant charge 20g m 20g m 20g m 30g m 30g m 30g m Max diff in level between indoor and outdoor unit 5m 5m 5m 5m 5m 5m Type of refrigerant 1 R410A R410A R410A R410A R410A R410A INVERTER TYPE MODEL capacity Btu h 9k 12k 15 18k 22 24k Liquid pipe diameter 1 4 6 1 4 6 1 4 6 3 8 9...

Страница 35: ...33 3 8 9 52 31 35 arm strength Protection caps 25 30 1 2 12 35 45 arm strength 5 8 15 88 75 80 arm strength ...

Страница 36: ...pasted diagram instruction on the unit first Note The cable wires hasbeen connected to the main PCB of indoor unit by manufacturer according to the model without terminal block see the wiring diagram on the right part of the unit under the front panel and the back of the outdoor cover ...

Страница 37: ...1 0mm2 1 0mm2 1 5mm2 1 5mm2 0 75mm2 0 75mm2 1 1 0mm2 1 0mm2 1 0mm2 1 0mm2 1 5mm2 1 5mm2 0 75mm2 0 75mm2 2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 3 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 0 75mm2 INVERTER TYPE MODEL capacity Btu h 9k 12k 18 22k 24k sectional area Power supply cable N 1 0mm2 1 5mm2 AWG18 AWG16 1 0mm2 1 ...

Страница 38: ...he filter with water if the filter is soiled with oil it can be washed with warm water not exceeding 45 Leave to dry in a cool and dry place 4 Keeping the front panel raised with one hand insert the air filter with the other hand 5 Close The electrostatic and the deodorant filter if installed cannot be washed or regenerated and must be replaced with new filters once every 6 months CLEANING THE HEA...

Страница 39: ... the cover at back Place the new batteries respecting the symbols and N B Use only new batteries Remove the batteries from the remote control when the conditioner is not in operation WARNING Do not throw batteries into common rubbish they should be disposed of in the special containers situated in the collection points ...

Страница 40: ...e to variations in temperature and does not indicate a problem Insufficient airflow either hot or cold Unsuitable temperature setting Obstructed air conditioner intakes and outlets Dirty air filter Fan speed set at minimum Other sources of heat in the room No refrigerant The appliance does not respond to commands Remote control is not near enough to indoor unit The batteries of remote control near...

Страница 41: ...39 flashes once The fault of indoor temperature senser flashes twice The fault of indoor pipe temperature senser flashes 6 times Malfunction of indoor fan motor ...

Отзывы: