31
The air and humidity left inside the refrigerant circulation
can cause compressor malfunction. After having
connected the indoor and outdoor units, bleed the air and
humidity from the refrigerant circulation using a
vacuum pump.
(1)
Unscrew and remove the caps from the 2 - way and
3-way valves.
(2)
Unscrew and remove the cap from the service port.
(3)
Connect the vacuum pump hose to the service port.
(4)
Operate the vacuum pump for 10 - 15 minutes until
an absolute vacuum of 10 mm Hg has been reached.
(5) With the vacuum pump still in operation , close
the low - pressure knob on the vacuum pump
coupling. Stop the vacuum pump.
(6)
Open the 2 - way valve by 1/4 turn and then close it
after10 seconds. Check all the joints for leaks using
liquid soap or an electronic leak device.
(7)
Turn the body of the 2-way and 3-way valves.
Disconnect the vacuum pump hose.
(8)
Replace and tighten all the caps on the valves.
INSTALLATION MANUAL--- final
stages
1.
Wind insulating covering around the joints of
the ind oor unit and fix it with insulating tape.
2.
Fix the exceeding part of the signal cable
to the piping or to the outdoor unit.
3.
Fix the piping to the wall ( after having coated
it with insulating tape) using clamps or insert them
into pla stic slots.
4.
Seal the hole in the wall through which the
piping is passed so that no air or water can fill.
Indoor unit test
Do the ON/OFF and FAN operate normally?
Does the MODE operate normally?
Do the set point and TIMER function properly?
Does each lamp light normally?
Do the flap for air flow direction operate normally?
Is the condensed water drained regularly?
Outdoor unit test
Is there any abnormal noise or vibration during
operation?
Could the noise , the air flow or the condensed water
drainage disturb the neighbours? Is there any coolant
leakage?
Note: the electronic controller allows the compressor to
start only three minutes after voltage has reached
the system.
Содержание DSB-F0969GLH-V
Страница 1: ......
Страница 3: ...1 PROTECTION 17 INSTALLATION MANUAL 18 MAINTENANCE 27 TROUBLESHOOTING 28 ...
Страница 8: ...6 NAMES OF THE PARTS ...
Страница 9: ...7 The conditioner is made up of two or more units ...
Страница 13: ...11 REMOTE CONTROL ...
Страница 15: ...13 REMOTE CONTROL ...
Страница 20: ...18 MODES OF OPERATION ...
Страница 21: ...19 ...
Страница 24: ...22 ...
Страница 25: ...23 ...
Страница 35: ...33 3 8 9 52 31 35 arm strength Protection caps 25 30 1 2 12 35 45 arm strength 5 8 15 88 75 80 arm strength ...