Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) 

Condition 

 

Temp. Time 

Compressor Outdoor 

fan 

T> TE6 

 

On 

On 

Temp. up 

T< TE6 

>5 Minutes 

Off 

Off 

T> TE5 

 

On 

On 

Temp. down 

T< TE5 

>5 Minutes 

Off 

Off 

 

8.7 Dehumidifying 

mode 

8.7.1 

The 4-way valve is off in dehumidifying mode 

8.7.2 

Compressor and Indoor Fan actions in dehumidifying mode 

NO 

  Conditions 

Indoor Fan 

Compressor and Outdoor Fan 

TA 

 TS+2 

LOW 

BREEZE 

ON  6minutes 

OFF 4minutes 

TS 

TA

TS+2 

LOW 

BREEZE 

ON  5minutes 

OFF 5minutes 

TA 

 TS 

LOW 

BREEZE 

ON  4minutes 

OFF 6minutes 

Repeat on and off cycle.

 

 

 

8.7.3 

Low room temperature protection: 

When room temperature decreases to below 10

, compressor and outdoor fan will stop(indoor fan 

is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13

8.7.4 

At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that 

of cooling mode. 

8.7.5 

At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode. 

8.8 

Heating mode(only for heat pump model) 

8.8.1 

Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve 

must delay 2 minutes compared with compressor if the compressor changed into non-heating mode 

or turned off. 4-way valve doesn't delay in dehumidifying mode. 

8.8.2 

Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except 

for the defrosting mode or the end of defrost. 

8.8.3 

Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes 

after starting and then judge temperature. Meanwhile other protections are still valid. 

 Condition 

Compressor 

Outdoor 

fan 

T> Ts+3 

Off 

Off 

Room temp. up 

T<Ts+3 On 

On 

T< Ts+2 

On 

On 

Room temp. down 

T>Ts+2 Off 

Off 

 

8.8.4 

Indoor Fan actions at heating mode 

Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind 

function prevails. 

Содержание DMA-2703L

Страница 1: ...Manual de servicio ACONDICIONADOR DE AIRE TIPO MULTI SPLIT Modelo ...

Страница 2: ...2 1 Features 3 2 Specification 4 3 Dimensions 5 4 Refrigeration cycle diagram 6 5 Operation limits 7 6 Wiring diagram 8 7 Troubleshooting 11 8 Electronic function 12 ...

Страница 3: ...3 1 Features 1 1Compact design 1 2High efficiency and quiet operation ...

Страница 4: ...ve tube Ф7 Innergroove tube Indoor coil Number of circuits 2 2 Indoor air flow Hi Mi Lo m3 h 420x3 Indoor noise level Hi Mi Lo dB A 39 39 Dimension W H D mm 750 250 188 750 250 188 Packing W H D mm 830X336X280 830X336X280 Indoor unit Net Gross weight Kg 8 5 10 8 5 10 Model YDK51 6D YDK51 6D Input W 130 130 Capacitor uF 3 3 Outdoor fan motor Speed r min 750 750 Number of rows 2 2 Fin type code Hydr...

Страница 5: ...3 Dimensions 3 1 Indoor unit 3 2 Outdoor unit 5 ...

Страница 6: ...4 Refrigeration cycle diagram 4 1 Cooling for MS2G 18CR Compressor Compressor Condenser Evaparator Evaparator 4 1 Cooling for DMA 2703L 6 ...

Страница 7: ...tdoor unit air temp DB 45 7 DRY COOLING 40 35 30 25 20 10 15 20 25 30 35 40 Indoor air temp DB Note The chart is the result from the continuous operation under constant air temperature conditions However excludes the initial pull down stage ...

Страница 8: ...6 Wiring diagram 6 1 MS2G 18CR Indoor unit Outdoor unit 8 ...

Страница 9: ...6 2 DMA 2703L Indoor unit 9 ...

Страница 10: ...Outdoor unit 10 ...

Страница 11: ...f the compressor occurs 4 times X Indoor fan speed has been out of control for over 1 minute X X Zero cross error Indoor evaporator sensor is open circuit or short circuit X X Indoor room temp sensor is open circuit or short circuit X X Temp fuse broken X EEROM error On On On r Extinguish Flash at 5Hz ...

Страница 12: ...door fans when they change from higher wind to lower wind IRESTORE Amp self protection return value THDEFROST High wind defrosting temperature difference TMDEFROST Middle wind defrosting temperature difference TLDEFROST Low wind defrosting temperature difference TE1 Anti cold wind from Fan Off to Breeze temperature TE2 Anti cold wind from Breeze to Setting Fan Speed temperature TE3 Anti cold wind ...

Страница 13: ...fan Remark I IRESTORE On On On Low speed On On Cooling mode IFAN I I5MIN Off Off After 5 Minutes Current up I5MIN I I3SEC Off Off After 3 Seconds I5MIN I I3SEC Off Off After 3 Seconds IFAN I I5MIN Off Off After 5 Minutes Low speed On On Cooling mode Current down I IRESTORE On On On If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor On the unit s...

Страница 14: ...or heat exchanger is the same as that of cooling mode 8 7 5 At dehumidifying mode the action of fans of indoor is the same as that of air only mode 8 8 Heating mode only for heat pump model 8 8 1 Generally the 4 way valve is open in heating mode but it is closed in defrosting mode 4 way valve must delay 2 minutes compared with compressor if the compressor changed into non heating mode or turned of...

Страница 15: ...n On 8 8 7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time 8 9 Defrosting operation Available for heating only 8 9 1 Defrosting condition Defrosting starts when either of the following A and B are satisfied A The compressor keeps running for 40 minutes or more B The temperature difference of evaporator and room temperature meets one of the following Temp of evaporat...

Страница 16: ...ous 6 minute defrost the fourth should be 10 minutes defrost The circulation is as following 6 minute defrost 6 minute defrost 6 minute defrost 10 minute defrost 8 9 3 Ending condition of defrosting If one of following conditions is satisfied end the defrost and turn into heating mode A The defrost time has reached to 6 or 10 minutes B The compressor current has reached to IDEFROST or above IDEROS...

Страница 17: ...ed out for at least 15 minutes once selected If the compressor cannot start for 15 minutes reselect the operation mode according to the room temp and set temp or reselect when the set temp varies 8 11 Forced cooling function 8 11 1 Select forced cooling function with the forced cooling button or the switch 8 11 2 The compressor is unconditionally turned on after 30 minutes cooling operation whose ...

Страница 18: ...s later the set temperature will maintain as a constant and the air circulation is kept at low speed Cold air proof function takes precedence over all 8 14 4 Auto The economic running function operates in accordance with selected running mode by auto mode 8 15 Auto restart function optional In case of a sudden power failure this function automatically sets the unit to previous settings before the ...

Страница 19: ...19 8 16 Models and Parameters Indoor unit Model DMA 2703L CSPEEDH 1100 CSPEEDM 1020 CSPEEDL 950 CSPEEDS 800 TE5 2 TE6 7 ...

Страница 20: ... Certificate Nu mber CC 454 GD M idea Ref rigeration Equipme nt Co Ltd have received environm ental man agement sy stem stand ard certification ISO 1 4001 Certificate Nu mber CC 1417 Please note that the data in this bookmay be changed without notice for further i mprovement on q uality and performance 20 ...

Отзывы: