Command
Description
Read Authorization Mode
[
讀取強制模式
]
• Reads the IR operating mode
• Each DO can have its own mode.
• There are four possible modes for each DO: Local On, Local Off, Forced On,
Forced Off.
• Note that reading has 4 possibilities, but setting only has 3 possibilities.
• There is a corresponding command to set the authorization mode, see the
Set
Authorization Mode
command for more details.
• This command is available for the LT3384 with firmware version 23 or higher
only.
Read AO Upper Limit
[
讀取
AO
高階設定
]
• Reads the value of the upper limit for an AO channel.
• See also the
Set AO Upper Limit
command to set this value.
Read AO Lower Limit
[
讀取
AO
低階設定
]
• Reads the value of the lower limit for an AO channel.
• See also the
Set AO Upper Limit
command to set this value.
Set Group On/Off
[
控制群控
]
• Commands all the DO belonging to a given group to turn On or Off at the same
time.
Activate Pattern
[
觸發情境
]
• Commands all the DO belonging to a given pattern to arrange themselves into a
formation consisting of On and Off elements.
• Note that a pattern can only be activated, a pattern cannot be turned Off.
Set DO On/Off
[
控制單點
]
• Commands a single DO to turn either On or Off.
Single DO Pulse Out
[
控制單
DO Pulse]
• Commands a single DO to output a pulse. The pulse is low->high->low.
Dual DO Pulse Out
[
控制雙
DO Pulse]
• Commands a pair of DO to each output a pulse simultaneously. The pulse is
low->high->low.
Clear Latched DI
[
清除保全
DI]
• Clears the latched DI flag.
• The latched DI flag is sticky, it is set when the DI goes high, the flag will remain
set even when the DI goes back low.
Clear Pattern Activation Map
[
清除場景
]
• Clears the bit map representing the activation status of each pattern.
• The bit representing a pattern is sticky, once activated (set to 1), the bit will
always remain in that state since a pattern cannot be turned off. This command
is needed in order to clear this sticky bit.
• See also the command
Read Pattern Activation Map
.
Set AO Value
[
寫入
AO
數值
]
• Writes a value to the analog output.
• The value can be any percent from 0 to 100. There is no decimal place.
Set Authorization Mode
[
寫入強制模式
]
• Sets the IR operating mode.
• Each DO can have its own mode.
• There are three possible modes that can be set for each DO: Local, Forced On,
Forced Off.
• Note that reading has 4 possibilities, but setting only has 3 possibilities.
• There is a corresponding command to read the authorization mode, see the
Read Authorization Mode
command for more details.
• This command is available for LT3384 with firmware version 23 or higher only.
Set AO Upper Limit
[
寫入
AO
高階設定
]
• Sets the value of the upper limit for an AO channel.
• See also the
Read AO Upper Limit
command to read the value that is set
from this command.
Set AO Lower Limit
[
寫入
AO
低階設定
]
• Sets the value of the lower limit for an AO channel.
• See also the
Read AO Lower Limit
command to read the value that is set
from this command.
CC1000 Modbus Reference 2.10e
!