Set AO Upper Limit
Data Format
✦
N = 1 to 4
✦
Allowed AO Upper Limit Values: 0 to 100%
✦
Data-L = AO Upper Limit / 1%
Command Format
Query
CC100
0
Addres
s
16
Reg-H Reg-L
0
N
Nx2
0
Data1-L
. . .
0
DataN-L
CRC-L CRC-H
Reply
CC1000
Address
16
Reg-H
Reg-L
0
N
CRC-L
CRC-H
LT to Register Address Conversion
❖
Reg = (LT + 703) x 4 + (AO - 1)
Set AO Lower Limit
Data Format
✦
N = 1 to 4
✦
Allowed AO Lower Limit Values: 0 to 100%
✦
Data-L = AO Lower Limit / 1%
Command Format
Query
CC100
0
Addres
s
16
Reg-H Reg-L
0
N
Nx2
0
Data1-L
. . .
0
DataN-L
CRC-L CRC-H
Reply
CC1000
Address
16
Reg-H
Reg-L
0
N
CRC-L
CRC-H
LT to Register Address Conversion
❖
Reg = (LT + 767) x 4 + (AO - 1)
CC1000 Modbus Reference 2.10e
!