Installing the Downdraft Vent in 

the Cutout

1.  Cut a hole in the cabinet to allow the duct work to pass 

through to the floor or wall for the planned duct system 

layout. Use the dimensions on pages 9 and 10 to 

determine the hole center line locations. If using the 2” x 

16” to 3 1/4” x 10” transition (REMP and ILHSF blower 

installations), the hole may need to be enlarged slightly.

 

2.  Gently slide the vent into the rear of the countertop cut-

out with the electrical access panel toward the front.

3.  Adjust the anchoring leg height so that the top of the 

downdraft vent rests on the counter, then tighten the 

hex nuts. Secure the anchoring legs to the cabinet floor 

with the provided wood screws.

Adapter Installation for CABP3 Blower: 

(optional, ERV3015 and ERV3615 only)

1.  Remove the front cover so that the AERVCAB cabinet 

blower adapter can be installed. To do so, remove and 

retain the three (3) wing nuts and three (3) flat washers 

on the front of the unit. Discard the three (3) lock wash-

ers (they will be replaced). Tilt the cover out and pull 

up. to remove it.

2.  Peel the backing off of some of the foam tape included 

with the adapter. Attach it to the right and left flanges. 

3.  Hold the adapter in front of the opening on the front 

of the unit with the adapter’s studs on top and all the 

flanges closest to the downdraft vent chassis.

4.  Slide the bottom flange on the adapter into the bottom 

retainer bracket on the downdraft vent at an angle. 

Attach the adapter using the three (3) wing nuts and 

Installation Instructions

Cover

Front of unit

Rear corner of cutout

(back of downdraft vent)

plumbed down

Exhaust: size and location 

varies with installation type

Front of unit

Floor

Top of vent resting 

on countertop

Electrical access 

panel

Anchor leg

Adapter

Front of unit

Studs

Bottom retainer bracket

Insert bottom 

flange into 

bottom retainer 

bracket

Attach foam

to right/left

flanges

flat washers removed in 

step 1 and three (3) of 

the lock washers from the 

adapter kit.

Содержание ERV3015

Страница 1: ...RV46 Part No 107736 Rev B Use these downdraft vents only with approved Dacor appliances See the installation instructions for the particular appliance model being installed to determine suitability Includes installation instructions for cabinet blower Dacor model CABP3 which is an option for models ERV3015 and ERV3615 ...

Страница 2: ...Service Team For repairs to Dacor appliances under warranty call the Dacor Distinctive Service line Whenever you call have the model and serial number of the appliance ready The model and seri al number are printed on the product data label on the front of the unit The product data label also specifies the power sup ply requirements Dacor Customer Service Phone 800 793 0093 ex 2813 U S A and Canad...

Страница 3: ...rom the power cord Use an adapter plug Use an extension cord Use a power cord that is frayed or damaged Use of a ground fault interrupter GFI is not recommended DANGER IMPORTANT Do not store or use combustible flammable or explosive vapors and liquids such as gasoline inside or in the vicinity of this or any other appliance Also keep items that could explode such as aerosol cans away from the rang...

Страница 4: ... not tamper with the controls Never allow the filters or vent openings to become blocked or clogged Do not allow foreign objects such as cigarettes or napkins to be sucked into the vent holes Clean the filters and all grease laden surfaces often to prevent grease fires and maintain performance Clean this appliance only as specified in the use and care manual Do not leave children or pets alone or ...

Страница 5: ... 1 4 94 6 cm Adjustable anchor legs Product data label Tolerances 1 16 1 6 mm unless otherwise stated Model Number A Top Cap Width B Chassis Width ERV3015 30 76 2 cm 27 3 8 69 5 cm ERV3615 36 91 4 cm 33 3 8 84 8 cm See pages 9 and 10 for exhaust locations and dimensions Maximum height of downdraft vent must not exceed maximum specified counter height for cooking appliance See installation instruct...

Страница 6: ... mm Top cap with vent down Tolerances 1 16 1 6 mm unless otherwise stated Model Number A Top Cap Width B Chassis Width ERV48 48 121 9 cm 43 3 8 110 2 cm PRV30 30 76 2 cm 27 3 8 69 5 cm PRV36 36 91 4 cm 33 3 8 84 8 cm PRV46 46 116 8 cm 43 3 8 110 2 cm See page 9 for exhaust locations and dimensions Maximum height of downdraft vent must not exceed maximum specified counter height for cooking applian...

Страница 7: ...unit 6 15 2 cm 2 9 16 6 5 cm 2 1 2 6 4 cm 1 15 16 4 9 cm B A Adjustable anchor legs 2 13 16 7 1 cm 1 4 6 mm Top cap with vent down Tolerances 1 16 1 6 mm unless otherwise stated Model Number Top Cap Width A Chassis Width B ERV36 ER 36 91 4 cm 33 3 8 84 8 cm ERV48 ER 48 121 9 cm 43 3 8 110 2 cm See page 9 for exhaust locations and dimensions Maximum height of downdraft vent must not exceed maximum ...

Страница 8: ...ion and service Any drawers or shelves must be easy to remove for access to the cooktop downdraft vent and utilities There are 7 8 access holes in the bottom and side of the downdraft vent for connecting the blower wiring and strain relief Wire the blower to turn on when the down draft vent is turned on When installing a remote or in line blower run the blower wiring conduit parallel to the duct w...

Страница 9: ... conduit from downdraft to remote blower Cabinet blower option on ERV3015 and ERV3615 only Cooktop Floor 12 min 30 5 cm 3 1 4 x 10 90 elbow Wall Downdraft vent Wall cap Backsplash ILHSF series in line blower 3 x 10 to round transition Duct work Duct work Outside wall Range Wall cap on outside wall Downdraft vent Downdraft vent configured for bottom exhaust Floor Wiring conduit from downdraft to in...

Страница 10: ...y require the use of makeup air systems with ventilation systems that move air greater than the specified movement rate CFM The specified rate var ies based on locale Consult a qualified HVAC specialist when designing the system for the requirements in your area and to assure optimal performance You must install one of the Dacor blower models listed below for the downdraft vent to operate properly...

Страница 11: ...knock out lines up with vertical center line of chassis On 30 and 36 wide models the vertical center line of bottom knock out is offset 3 Side Exhaust Knock Outs 1 5 8 x 16 Bottom Exhaust Knock Out 1 5 8 x 16 Motor cover Front of unit 26 66 0 cm 6 1 4 15 9 cm 1 1 8 2 9 cm C L C L C L Exhaust Knock out Locations for Use with REMP and ILHSF Series Blowers Use sheet metal screws as required to suppor...

Страница 12: ... Countertop 3 1 4 x 10 duct connection Duct connection center line B Downdraft vent center line Countertop 3 1 4 x 10 duct connection 15 3 8 39 1 cm Duct connection center line A Downdraft vent center line Countertop 3 1 4 x 10 duct connection 26 1 4 66 7 cm Exhaust Locations and Side Dimensions for CABP3 Cabinet blower Exhaust Locations and Dimensions for CABP3 Cabinet Blower Installations ERV301...

Страница 13: ...t 2 feet 36 feet The maximum amount of straight duct that can be used with a REMP16 and the above components is 60 feet 34 feet 24 feet Equivalent Number of Feet Nominal Duct Elbows and Transitions 45 elbow 8 inch 3 feet 3 x 10 45 elbow 7 feet 45 elbow 10 inch 2 feet 3 x 10 90 elbow 15 feet 90 elbow 8 inch 7 feet 3 x 10 90 flat elbow 20 feet 90 elbow 10 inch 5 feet 3 x 10 to 8 round transition 4 f...

Страница 14: ... cut out separate from the range or cooktop Install the down draft vent before installing the range or cooktop 2 Start by loosely attaching the anchoring legs to the studs on the left and right sides of the downdraft vent using the provided Keps nuts and washers Installation Preparation for Downdraft Vent with ILHSF or REMP Series Blower NOTE For units using the CABP3 cabinet blower skip to Instal...

Страница 15: ...he three 3 wing nuts and three 3 flat washers on the front of the unit Discard the three 3 lock wash ers they will be replaced Tilt the cover out and pull up to remove it 2 Peel the backing off of some of the foam tape included with the adapter Attach it to the right and left flanges 3 Hold the adapter in front of the opening on the front of the unit with the adapter s studs on top and all the fla...

Страница 16: ... the blower installation instructions Duct Work Installation warning Tape all duct joints securely to prevent combustion by products smoke or odors from entering the home Doing so will also improve system efficiency Install the duct work according to the Installation Specifications section Use sheet metal screws and duct tape to connect and seal all of the pieces Support the duct weight as necessa...

Страница 17: ...ical Installation CABP3 Cabinet Blower Downdraft Vent Electrical Access Panel Front of unit Wire Colors Black Line L White Neutral N Green Ground Gnd Electrical connection from downdraft vent match Wire Colors CABP3 cabinet blower Downdraft vent blower wiring access hole Ground Power Input Blower Output Blower power wiring conduit Connect other end of wires to blower terminal block Wires to power ...

Страница 18: ...hat power is being supplied to the unit Make sure that power is being supplied to the blower from the downdraft vent If the vent will not raise properly or makes a scraping sound check for obstructions interfering with the raising of the unit If the downdraft vent still does not function after perform ing the above checks do not attempt to repair it yourself Contact Dacor Distinctive Service at 79...

Страница 19: ...BLK WHT WHT Wiring Diagram All Models CABP3 Cabinet Blower Ratings CABP3 Cabinet blower Airflow Nominal 600 CFM Actual 585 6 CFM At zero inches static pressure Performance varies based on duct system configuration Electrical Rating 4 Amps 120 Vac 60 Hz For ILHSF or REMP series blower ratings see the blower installation instructions Airflow CFM Cubic feet minute Static pressure inches of water 0 1 ...

Страница 20: ...Dacor 14425 Clark Avenue City of Industry CA 91745 Phone 800 793 0093 Fax 626 403 3130 www dacor com ...

Отзывы: