background image

DACELL CO., LTD 

http://www.dacell.com

 

TEL:+82-43-2602242, FAX : +82-43-2602245 

 

11

 

 
8. TECHNICAL DATA

   

     

item

 

data

 

allowed time temperature 

40 

 80

 

operating temperature 

    0  

 50  

 

power of sensor 

5Vdc or 10Vdc 

input signal type 

   1 

 3mV/V 

max. load current 

10Vdc/60

, 5Vdc/120

 

frequency response 

Max 5

 

analog output 

0

10V,0

20

,1

5V, 4

20

   

relay output 

220V/5A (a,b contact) 

relay response 

Max 66

/sec 

nonlinear characteristics 

±

0.02

/F.S 

temperature coefficient 

±

0.02

F.S/

 

display size 

14

×8

 

sampling time 

15 times/sec, 30 times/sec 

filter frequency 

1

, 10

, 100

, 4

 

short protection circuit 

protection circuit (insert) 

max. display range 

-19999 

 19999 

size 

w 96

×h 48

×d 126

 

power 

110Vac, 220Vac (50

60

 
 
9. Unit Label change

   

      * Unit label is optional.   
      * In the case of exchanging label, refer to as follows   
        1, Separate P.C.B from the case.   
        2, Remove Conventional unit label and then adhere new   label.   

         

3, Put together indicator in reverse process.   

 
 
 
 
 
 

Содержание SM110

Страница 1: ...LTD http www dacell com TEL 82 43 2602242 FAX 82 43 2602245 1 DIGITAL INDICATOR SM110 150 INSTRUCTION MANUAL DACELL CO LTD TEL 82 43 260 2242 FAX 82 43 260 2242 WEBSITE http www dacell com EMAIL info...

Страница 2: ...ricity DACELL is not liability for mistake to use that change a property voluntarily change design adjustment voluntarily user carelessness cause defect 1 Installation 1 Product Spec Spec 96 48 3 78 1...

Страница 3: ...on mode 3 ANALOG OUTPUT 4 GND 5 Analog output is as following voltage or current DIP switch 5 on voltage output DIP switch 5 off current output ON Voltage Output 0 5V 1 5V 0 10V 2 10V OFF Current Outp...

Страница 4: ...ed on only one in accordance with kind of sensor Under 0 700mV V or over 3 500mV V are option SOFTWARE setting In cal mode input as follows according to sensor output 5 RELAY OUTPUT A NO and B NC cont...

Страница 5: ...Display operation mode of high relay HI setting Confirm and adjust high data operation Display operation mode of low relay LO setting Confirm and adjust low data FS setting Confirm and adjust full sca...

Страница 6: ...2 3 4 5 6 7 8 9 0 Input 8 Input data After setting up must press key therefore become input Auto zero 9 Sensor No load state 0V 4 10 Display 0 4 PROTECTION mode Use this mode for protection and secur...

Страница 7: ...AUTO CALIBRATION mode Convenience to use when do not know calibration data of sensor or displayed the measurement value differently 1 Adjust zero point of indicator 2 Apply known load to sensor Large...

Страница 8: ...calibration Check function Relay output analog output reset hold peak Press key data protection mode 5 HARDWARE 1 Selection of AC input power 1 Separate P C B from case 2 The following label is exist...

Страница 9: ...calibration execution 1 mV V range 0 700 1 249 mV V 1 5 mV V range 1 250 1 749 mV V 2 mV V range 1 750 2 499 mV V 3 mV V range 2 500 3 500 mV V 2 Adjustment of display time and measurement data unit 1...

Страница 10: ...y x 1 x x display to signal and display indicate opposite ex 20mA display 760 0 x x 0 x standard type Display 0 trace minute signal to 0 Tracking mode of zero point x x 1 x Display 0 display minute si...

Страница 11: ...ct relay response Max 66 sec nonlinear characteristics 0 02 F S temperature coefficient 0 02 F S display size 14 8 sampling time 15 times sec 30 times sec filter frequency 1 10 100 4 short protection...

Страница 12: ...rt of sensor in output line Check DIP switch about sensor output Check sensor wiring Display change Exchange of sensor input line data setting error Check sensor connection refer to 6 3 Not able to se...

Отзывы: