All the ducts must be installed in such a way that they are not stressed. The ducts must not
exert stress on the station. Check that the electropump is securely fixed to the pipes and that
all the hydraulic connections are tightened and watertight.
Where necessary provide suitable means for avoiding the transmission of vibrations and for protecting the
pipes against the formation of ice.
5.1 Placing the tank inside the building
The tank may be laid on the floor, under the ground or housed in a masonry pit. Fig.2, Fig.3
In any case the surface on which it is laid must be perfectly horizontal and it must be ensured that
the whole bottom of the tank is in contact with the surface.
For Fekabox 110 the cover of the tank is trafficable
(max. weight 100 Kg, see fig. 1).
In indoor installations (garage, basement, technical room), the tank must be fixed to the
ground using the slots provided to prevent rotations, as indicated in figure 4.
Leave a free space of at least 60 cm around and above the station for installation and
maintenance.
5.2 Placing the tank outside the building
If the tank would not buried, to prevent damage to itself and to the seals, you should not expose it to heat
sources such as direct sunlight can be at certain times of the year.
Do not position the lifting station directly on the ground. The site chosen must not have ground
water and must not be subject to flooding. Suitable anchor the station so as to avoid rotation
and floating. For this you can use the slots on the base of the tank.
There must be a horizontal base suitable to bear the weight of the station during its operation.
Depending on the characteristics of the terrain it may be necessary to create walls with bricks,
prefabricated components or concrete. Fill the space between the ditch and the station with
sand and compact it suitably. Protect the station suitably against frost.
Do not drive vehicles over the cover (see fig. 3).
You can close the ditch with a cover (manhole) or other means for facilitating subsequent maintenance. Put
up suitable signals indicating the presence of the station so as to avoid possible damage caused
unintentionally. Ensure that there is sufficient space for installation and maintenance around and above the
lifting station.
Position any capacitor holder and/or electric control panel in a place sheltered from the
elements.
After having completed the hydraulic and electric connection, it is recommended to place clean sand around
the container to reduce any movements caused by the system and/or by the surrounding terrain.
5.3 Making holes for the collection, delivery and ventilation pipes
Choose the inlet duct already prepared for the inlet pipe so that the arrival of the liquid does not disturb the
operation of the pump float.
The Fekabox 110 tanks have multiple inlets, all marked with the symbol:
Make a hole in the tank in the determined areas, indicated by the symbols shown above.
Fig. 4
FIX THE TANK TO THE GROUND
BEFORE USE
Use screws TE M8 with respective
fixture, use specific washers for soft
materials ISO 7093