8.4 Manual Menu
From the main menu, hold down simultaneously the “SET” and “^” and “
˅
“keys until the manual menu page appears (or use the selection menu
pressing ^ or
˅
).
The menu allows you to view and modify various configuration parameters: the MODE key allows you to scroll through the menu pages, the ^
and
˅
keys allow you respectively to increase and decrease the value of the parameter concerned. Press SET to leave this menu and return to
the main menu. Entering the manual menu by pressing the SET ^
˅
keys puts the machine into forced STOP condition. This function can be
used to force the machine to stop. In manual mode, irrespective of the parameter displayed, it is always possible to perform the following
controls:
Temporary starting of the electropump
Pressing the MODE and ^ keys at the same time causes the pump to start at speed RI and this running status remains as long as the two keys
are held down.
When the pump ON of pump OFF command is given, a communication appears on the display.
Starting the pump
Holding down the MODE
˅
^ keys simultaneously for 2 sec. causes the pump to start at speed RI. The running status remains until the SET key
is pressed. The next time the SET key is pressed the pump leaves the manual menu. When the pump ON of pump OFF command is given, a
communication appears on the display. In case of operation in this mode for more than 5’ with no flow of liquid, an alarm overheating alarm will
be triggered, with the error PH shown on the display. Once the PH error condition is no longer present, the alarm will be reset automatically
only. The reset time is 15’; if the PH error occurs more than 6 times consecutively, the reset time increases to 1h.
Once it has reset further to this error, the pump will remain in stop status until the user restarts it using the “MODE” “
˅
” “^”keys.
8.4.1
Status
Displays the pump status.
8.4.2
RI: Speed setting
Sets the motor speed in rpm. Allows you to force the number of revolutions at a predetermined value.
8.4.3
VP: Pressure display
Plant pressure measured in [bar] or [psi] depending on the measuring system used.
8.4.4
VF: Flow display
Displays the flow in the chosen unit of measure. The measuring unit may be [l/min] o [gal/min] see par. 8.5.4 - MS: Measuring system.
8.4.5
PO: Absorbed power display
Power absorbed by the electropump in [kW]. A flashing round symbol may appear under the symbol of the measured power PO. This symbol
indicates the pre-alarm for exceeding the allowed maximum power.
8.4.6
C1: Phase current display
Motor phase current in [A]. A flashing round symbol may appear under the symbol of the phase current C1. This symbol indicates the pre-alarm
for exceeding the allowed maximum current. If it flashes at regular intervals it means that the motor overload protection is about to trip and it will
very probably go into protection status.
8.4.7
RS: Rotation speed display
Motor rotation speed in rpm.
8.4.8
TE: Heat sink temperature display
8.5 Installer Menu
From the main menu, hold down simultaneously the “MODE” and “SET” and “
˅
”
keys until the first parameter of the installer menu appears on
the display (or use the selection menu pressing ^ or
˅
).
The menu allows you to view and modify various configuration parameters: the MODE key allows you to scroll through the menu pages, the ^
and
˅
keys allow you respectively to increase and decrease the value of the parameter concerned. Press SET to leave this menu and return to
the main menu.
8.5.1
RP: Setting the pressure fall to restart
Expresses the fall in pressure with respect to the SP value which causes restarting of the pump.