
INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08
47
Instruction manual edition 1 for EP104 version 4.08
Programmable input 2
No.
Name
Range
Factory Setting Ref.
page
P200
Channels in programmable input 2
0 - 1
1
0
Disabled
1
Enabled
P260
Control function
0-5
2
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
S
P261 Type of control signal when activated
1 - 2
1
1
Pulse (hold-to-run mode not possible)
2
Signal for as long as the input is activated
P262
Half operation
1 - 3
3
1
Motor 1
2
Motor 2
3
Motors 1 and 2
P263
Limited opening
0 - 1
0
0
Disabled
1
Opening according to set time in channel C412/C414 or number of degrees in L116/L126 if encoder
is used.
P270
Motor lock
0 - 1
0
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 2. If the signal disappears the
barrier is stopped.
P275
Opening via input after activation during set time,
input will not open the barrier until it has been
activated for the set time.
0.0-9.9 seconds
0.0
P280
Keep opened
0 - 2
0
0
Disabled
1
Automatic closing disabled after the input is activated, reset by another control signal
2
Automatic closing disabled by a constant signal
P290
Interlock opening
0 - 1
0
0
Disabled
1
Opens the local door if P260 is set to open, and passes the signal on to the remote door
P296
Blocking disabled for local and remote doors. Works
only with a constant signal.
0 - 1
0
0
Disabled
1
Active
P298
Automatic closing disabled for remote door Only
works if there is a constant signal
0 - 1
0
0
Disabled
1
Active
Содержание EP104
Страница 60: ......