INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08
21
Instruction manual edition 1 for EP104 version 4.08
• Commissioning of drive unit 2
Preparation:
Set C999 to 2. Open gate leaf 1 and set L001 to 0 to maintain the gate leaf in open position. Set C033 to 5,
Service mode.
Direction of movement:
Set L002 to 4, hold-to-run without limit switches. Check that the drive arm mounting is moving in
the right direction while pressing OPEN or CLOSE button on the controll board. If the direction of movement is wrong, see
section "Connections" in the "Instruction Manual EP104".
Open and closed position:
Engage gate leaf of drive unit 2 and set the positions for open and closed. After this is done
L002 should be set to 1, Encoder.
L110=1, Drive unit 1 Left position
L120=2; Drive unit 2 Right position
L123, Closed position
L122, Open position
L121, Position readout
Motor protection:
Read out motor current in C261 under operation and apply appropriate values in C262 och C263.
Opening
/
Closing
C262
/
C263
150%
(50%)
Current(A)
Time
Opening
/
Closing
C262
/
C263
150%
(50%)
Current(A)
Time
C221
C221, Motor protection delay
C261, Read out current
E202
C261, Read out current
Opening
/
Closing
C262
/
C263
150%
(50%)
Current(A)
C221, Motor protection delay
Opening
/
Closing
C262
/
C263
150%
(50%)
Current(A)
C221
E207
Time
Time
C261, Read out current
C261, Read out current
Load guard:
Set C999 to 3. A swing gate application usually does not require personal protection, if so C240 is set to
0.00. Set C033 to 3, impulse, to activate the load guard. Make sure that the settings of the C242 and C243 is low enough to
prevent material damage, but at the same time that it is guaranteed to open due to weather, wind and mechanical changes.
Opening
/
Closing
C242
/
C243
Power(kW)
Time
Opening
/
Closing
C242
/
C243
Power(kW)
Time
C212, Load guard start
C211, Load guard delay
Reversing
C241, Power read out
-0,30kW
C212
C241, Power read out
Safety edges:
Check the safety edges on gate leaf 2 by pressing the safety edges during movement. Please note that the
safety function in opening direction is switched off in C141. If the safety edges are activated during closing movement the
gate should reverse to fully opened position, while in opening movement it should reverse to closed position during the time
in C494. A flashing indication at SE.C2 or SE.O2 means that the safety edge was activated but no longer is.
Completion:
Set L001 to 1, Encoder and fine-tune both gate leaf's in closed position using L113 and L123.
Use channel C999 set to 1 to look for changed channels and enter all changed channels in the "Instruction Manual".