Figure 3. DXS-3610-54S Rear Panel (AC PSU)
Figure 4. DXS-3610-54S Rear Panel (DC PSU)
This following table lists the rear panel components on the Switch:
Component
Description
Switch GND
Use an electrical grounding wire and connect one end of the wire to the switch
GND and the other end of the wire to an electrical grounding point most commonly
found on the Switch mounting rack itself.
Fan Modules
These are five hot-swappable, redundant (4+1) fan module slots on the rear panel
of the Switch. The following fan modules can be installed in these slots:
•
DXS-FAN200
(Fan module with Front-to-Back airflow)
When five fans modules are installed, four fan modules will be active and the fifth
fan module will be passive until one of the four active fan modules fail.
Power Supply Module Slots
There are two load-sharing power supply module slots on the rear panel of the
Switch. The following power supply modules can be installed in these slots:
•
DXS-PWR700AC
(AC PSU with Front-to-Back airflow)
•
DXS-PWR1000DC
(-48V DC PSU with Front-to-Back airflow)
Rear Panel LED Indicators
The LED indicators provide valuable information in a variety of ways like their color, blinking times, and
location.
Figure 5. DXS-3610-54S Rear Panel LED Indicators
The rear panel LED indicators are described in the following table:
LED
Color
Status
Description
Power Supply Module
Green
On (Solid)
Normal power supply module operation
On (Blinking)
PSU module is off but standby power is supplied
Amber
On (Solid)
PSU/Fan failed or PSU shutdown due to critical event
On (Blinking)
Warning event occurred (Power/Current/Temperature
too high or fan is too slow)
-
Off
Power off or PSU is on but with warning events
Fan Module
Green
On (Solid)
Fan operation is normal
On (Blinking)
Fan error occurred
-
Off
Power off
5
Содержание DXS-3610-54S
Страница 19: ...0 45 C C 5 c 2 6 7 2012 D 2013 E 2014 F 2015 G 2016 H 2017 I 2018 J 2019 0 2020 1 2021 1 2 9 A B D Link 19...
Страница 20: ...DXS 3610 54S DXS 3610 54S 2 AC DXS PWR700AC 5 DXS FAN200 AC RJ45 RS 232 USB 4 2 20...
Страница 24: ...5 DXS 3610 54S 6 24...
Страница 25: ...19 DXS 3610 54S 19 7 8 9 25...
Страница 26: ...10 DGS 3610 54S QSFP28 SFP QSFP QSFP28 100GE QSFP28 11 QSFP QSFP28 QSFP28 26...
Страница 27: ...SFP SFP 10GE SFP 12 SFP SFP SFP AC DXS 3610 54S AC 27...
Страница 28: ...13 AC 14 AC PSU 2 AC AC 100 240 50 60 DC DXS 3610 54S DC 28...
Страница 29: ...15 DC 16 DC PSU 2 DC DC 48 5 2 A 17 DC DC 29...
Страница 30: ...DGS 3610 54S DXS FAN200 18 19 30...
Страница 31: ...DXS 3610 54S 12 IP Telnet Web RJ45 SFP QSFP28 SNMP 20 21 31...
Страница 38: ...38...