99.826.62 1.1/10/15
99.826.62 1.1/10/15
2/20
3/20
CDP 1500-BSY+
CDP 1500-BSY+
250 mm / 9.8"
500 mm / 19.7"
750 mm / 29.5"
1000 mm / 39.4"
1250 mm / 49.2"
1500 mm / 59.1"
1750 mm / 68.9"
2000 N / 450 lbf
1500 N / 337 lbf
1000 N / 225 lbf
500 N / 112 lbf
0
max. Load
Stroke
Operating voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the chain!
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed r
ed safety slip!
Safety notes
Intended use
- Chain drive for electric opening and closing of
heavy windows and roof area
- Operating voltage 24 V DC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Performance features
- Micro processor controlled synchro electronics
BSY + for a precise synchronous run of up to
4 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
- Locking relief after closing
- Especially quiet motor running in ventilation mode
- Symmetrical chain outlet
- Connection via pin-and-socket connector
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
Type
CDP 800-BSY+
CDP 1000-BSY+
CDP 1500-BSY+
Power supply
24 V DC / ±15 %
24 V DC / ±15 %
24 V DC / ±15 %
Nominal current
2 A
2 A
2 A
Nominal force
800 N
1000 N
1500 N
Nominal locking force
1500 N
Lifetime ***
>10 000 double strokes
Reliability
Re = 400
Duty cycle
30 % (With cycle time 10 minutes)
Housing
Aluminium, PC/ABS (end covers)
Ingress protection
IP 32
Temperature range
-5 ... +75 °C
Fire stability
30 min / 300 °C
Nominal stroke length *; ** See type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings),
locking relief activated (0.3 mm)
* Programmable with software SCS
** 1000 mm max. according to VdS 2580
*** (500 mm) according to VdS 2580
Technical data
OPEN
Forces
CR
III
CR
II
CR
I
C
L
O
S
E
Running speed and forces
Normal operation
=
Fast running =
All approx. 20 % switch-off reserve (temporary)
Closure Ranges
English
English
Observe maximum pressure load
of the chain!
Maximum pressure load of the
c h a i n i s n o t a u t o m a t i c a l l y
identical with maximum pressure
force of the drive!
Pressure load diagram
Drive unit with 2.5 m (98.5'') silicone cable.
Dependent on the type of window, different bracket
sets are available separately.
Scope of supply
OPEN direction
Running speed
11.8 mm/s
10.0 mm/s
6.8 mm/s
6 mm/s
6 mm/s
6 mm/s
OPEN direction
CDP 800-BSY+
CDP 1500-BSY+
CDP 1000-BSY+
CDP 800-BSY+
CDP 1500-BSY+
CDP 1000-BSY+
800 N
800 N
800 N
500 N
1500 N
1000 N
1000 N
500 N
1000 N
1000 N
1000 N
500 N
! IMPORTANT ! Safety Notes
1. Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is
ensured by regular in-house training.
2. All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3. For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4. Observe enclosed red safety slip!
5. Danger of violent pressure in handaccessible area.
6. The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7. A suitable field wiring means should be provided in the end use application.
8. The mounting and routing of external wiring should be determined in the end product.
9. The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above
the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be
determined during the end product investigation.
13. The drive shall be connected to a Class 2 power supply.
For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.