CDP 1500-BSY+

CDP 1500-BSY+

250 mm / 9.8"

500 mm / 19.7"

750 mm / 29.5"

1000 mm / 39.4"

1250 mm / 49.2"

1500 mm / 59.1"

1750 mm / 68.9"

2000 N / 450 lbf

1500 N / 337 lbf

1000 N / 225 lbf

500 N / 112 lbf

0

max. Load

Stroke

Operating voltage 24 V DC!

Do not connect directly to the mains supply!
-   Connection has to be carried out only by an

   authorized electrical specialist

-   Danger of violent pressure in handaccessible area
-   Keep away People from the operating area of the

   drive

-   Keep away children from the control
-   Observe pressure load diagram of the chain!
-   Use only in dry rooms
-   Only for inside mounting.

   Use rain detector with danger of rain
   (e.g. at domelights or roof windows)

-   Just use unchanged original D+H parts
-   Observe mounting instructions of bracket set!

Observe enclosed r

  

ed safety slip!

Safety notes

Intended use

-   Chain drive for electric opening and closing of

   heavy windows and roof area

-   Operating voltage 24 V DC
-   Useable for smoke ventilation, D+H Euro-SHEV

   according to DIN EN 12101-2 as well as daily
   natural ventilation

-   Only for inside mounting

Performance features

-   Micro processor controlled  synchro electronics

   BSY + for a precise     synchronous run of  up to
   4 drives

-   Individually programmable (via software SCS)
-   SHEV-high speed function (fast-running   

   feature in OPEN-direction)

-   Protection system for the main closing edge
-   Locking relief after closing
-   Especially quiet motor running in ventilation mode
-   Symmetrical chain outlet
-  Connection via pin-and-socket connector
-  Optinal with "-AS2" = protection class 2 and 

   "-AS3" as well as "-LS" = protection class 3

Type 

CDP 800-BSY+ 

 

CDP 1000-BSY+   

CDP 1500-BSY+

 

Power supply 

24 V DC / ±15 % 

 

24 V DC / ±15 % 

 

24 V DC / ±15 %

Nominal current 

2 A 

 

 

 

2 A 

 

 

 

2 A

Nominal force 

800 N  

 

 

1000 N 

 

 

1500 N

 

Nominal locking force 

1500 N

Lifetime *** 

>10 000 double strokes

Reliability 

Re = 400

Duty cycle 

30 % (With cycle time 10 minutes)

Housing 

Aluminium, PC/ABS (end covers)

Ingress protection 

IP 32

Temperature range 

-5 ... +75 °C

Fire stability 

30 min / 300 °C

Nominal stroke length *; **  See type plate
Additional functions * 

Closing edge protection activated (3 stroke repeatings),

   

 

 

locking relief activated (0.3 mm)

 

*   Programmable with software SCS
**  1000 mm max. according to VdS 2580
*** (500 mm) according to VdS 2580

Technical data

OPEN

Forces

CR 

III

CR 

II

CR 

I

C

L

O

S

E

Running speed and forces 

Normal operation

 =

Fast running =

All  approx. 20 % switch-off reserve (temporary)

Closure Ranges

English

English

Observe maximum pressure load 
of the chain!
Maximum  pressure  load  of  the 
c h a i n   i s   n o t   a u t o m a t i c a l l y 
identical with maximum pressure 
force of the drive!

Pressure load diagram

Drive unit with 2.5 m (98.5'') silicone cable.
Dependent on the type of window, different bracket 
sets are available separately.

Scope of supply

OPEN direction

Running speed

11.8 mm/s

10.0 mm/s

6.8 mm/s

6 mm/s
6 mm/s
6 mm/s

OPEN direction

CDP 800-BSY+

CDP 1500-BSY+

CDP 1000-BSY+

CDP 800-BSY+

CDP 1500-BSY+

CDP 1000-BSY+

800 N
800 N
800 N
500 N

1500 N
1000 N
1000 N

500 N

1000 N
1000 N

1000 N

500 N

! IMPORTANT ! Safety Notes

1.  Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is 

ensured by regular in-house training.

2.  All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3.  For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4.  Observe enclosed red safety slip!
5.  Danger of violent pressure in handaccessible area.
6.  The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7.  A suitable field wiring means should be provided in the end use application.
8.  The mounting and routing of external wiring should be determined in the end product.
9.  The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above 

the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be 
determined during the end product investigation.

13. The drive shall be connected to a Class 2 power supply.

For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.

Содержание CDP 800-BSY+

Страница 1: ...rder bracket sets separately Rogamos que pidan los juegos de fijaci n por separado E 222052 C US en Original instructions Page 2 Connection Page 14 19 Dimensions Page 20 es Manual original P gina 8 Co...

Страница 2: ...l as LS protection class 3 English Drive unit with 2 5 m 98 5 silicone cable Dependent on the type of window different bracket sets are available separately Scope of supply IMPORTANT Safety Notes 1 Mo...

Страница 3: ...ditional functions Closing edge protection activated 3 stroke repeatings locking relief activated 0 3 mm Programmable with software SCS 1000 mm max according to VdS 2580 500 mm according to VdS 2580 T...

Страница 4: ...re numbered downwards Example In a group composed of 3 drives there is a master 3 a slave 2 and a slave 1drive Attention only applies by factory set As soon as the drives were reprogrammed with SCS th...

Страница 5: ...bigger null balance with software SCS or special magnet MAG 502 is neccesary Closure Ranges will shift in relation to new zero point At vertical active pulling application e g for a skylight the force...

Страница 6: ...rain on glass can cause the glass to break Cordon off the danger area Take personal safety precautions A second person must be able to interrupt the drive voltage at any time If repeat zeroing of a dr...

Страница 7: ...ion into national right electrcal devices that are no longer usable must be collected separately and disposed of in an environmentally correct manner Disposal Guarantee You will get 2 years guarantee...

Страница 8: ...eden obtenerse porseparado diferentesjuegosdefijaci n Extensi n de suministro IMPORTANTE Advertencias de seguridad 1 El montaje del actuador deber efectuarse por un distribuidor autorizado de D H que...

Страница 9: ...nes adicionales Activada la proteccion en el borde al cerrar tres carreras de repetici n alivio de la presi n de las gomas activado 0 3 mm Programable con el software SCS 1000 mm m x seg n VdS 2580 50...

Страница 10: ...otor de un grupo sincronizado es el maestro que controla los dem s motores en este caso esclavos Las diferencias de fuerza entre los motores de un grupo se compensan mediante una regulaci n inteligent...

Страница 11: ...a m s uniforme entre todos los accionamientos Instrucciones de montaje Master 1 99 826 62 1 1 10 15 11 20 CDP 1500 BSY Espa ol Si al finalizar el montaje la cota X es igual o superior a 23 mm 0 9 ser...

Страница 12: ...didas de protecci n individual para la propia seguridad Es necesario que una segunda persona pueda interrumpir la tensi n en los actuadores en cualquier momento Es necesario para el montaje cadena en...

Страница 13: ...ees Junta directiva Apoderado Director t cnicor 01 04 2015 Declaraci ndeconformidad Recomendamos que los aparatos el ctricos accesorios y embalajes sean sometidos a un proceso de recuperaci n que resp...

Страница 14: ...Connection Conexi n 1 5 4 6 10 mm 0 4 3 2 1 1 2 3 1 4 5 6 99 826 62 1 1 10 15 14 20 CDP 1500 BSY Cable mounting Montaje del cable Cabledismounting Desmontajedelcable English Espa ol...

Страница 15: ...Est ndar Option Opci n SGI SKS YE SGI GN SKS GY SKS WH n c BN n c GN green verde YE yellow amarillo BU blue azul BN brown marr n BK black negro WH white blanco PK pink rosa GY grey gris WH Mot a GY n...

Страница 16: ...SGI GN SKS GY SKS Option Opci n SA SZ Option Opci n SGI SKS SA SZ OG n c PK SA YE SA GN SZ GY SZ WH n c BN n c s r WH Mot a GY n c PK n c BN Mot b OG HS GN Data B YE Data A max 50 V 0 5 A OG n c PK SA...

Страница 17: ...00 BSY Connection Conexi n PinAssignment Asignaci n de cables Option Opci n DS WH Mot a GY n c PK n c BN Mot b OG HS GN Data B YE Data A Max 1x Standard 1x DS WH Mot a GY n c PK n c BN Mot b OG HS GN...

Страница 18: ...t a Mot b MOT Junction box Caja de conexi n WH BN OG YE GN Mot a Mot b HS Data A Data B CDP BSY Master 1 99 826 62 1 1 10 15 18 20 English Espa ol CDP 1500 BSY Protect against short circuit Proteger c...

Страница 19: ...N BN OG OG YE YE GN GN Mot a Mot a Mot b Mot b HS HS Data a Data A Data b Data B CDP BSY CDP BSY Slave s Master Junction box Caja de conexi n 99 826 62 1 1 10 15 19 20 English Espa ol CDP 1500 BSY GN...

Страница 20: ...1200 mm 1500 mm B A Weight Peso 7 5 kg 16 5 lb 8 3 kg 18 3 lb 9 2 kg 20 3 lb 10 2 kg 22 5 lb 11 4 kg 25 1 lb D H MechatronicAG Georg Sasse Str 28 32 Germany 22949Ammersbek 49 239 Tel 40 605 65 49 Fax...

Отзывы: