![D+H CDP 1500 BSY+ Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/d-h/cdp-1500-bsy/cdp-1500-bsy_original-instructions-manual_494703009.webp)
99.825.20 2.0/07/12
9/28
English
CDP 1500 BSY+
Normal operation =
SHEV- fast running =
Clamping protection
In the "CLOSED" position, the drive has adjustable clamping
protection in the closing zone III and II
(see Technical Data). If an overload occurs in these zones,
the drive travels to the "OPEN" position for 10 seconds if
protection is activated. The drive then travels back to the
"CLOSED" position, if closing is not possible after three
attempts, the drive remains in this position. The drive also
has passive protection, meaning the closing speed is
reduced to 5 mm/s in the closing zone II and I. There are still
substantial forces that pose a risk to life and limb.
Significantly greater forces can be exerted at
the secondary closing edges. Danger of
crushing hands and fingers!
Main closing edge
Beside
closing
edge
Beside
closing
edge
Type
CDP 1500-BSY+
Power supply
24 V DC, ±15 %
Nominal current
4 A
Nominal force
1500 N
Nominal locking force
1500 N
Lifetime
>10 000 double strokes
Duty cycle
30 % (With cycle time 15 minutes)
Housing
Aluminium, Polycarbonate (End covers)
Ingress protection
IP 32
Temperature range
-5 ... +75 °C
Fire stability
30 min / 300 °C
Nominal stroke length *
See type plate
Additional functions *
Clamping protection activated (3 stroke repeatings),
locking relief activated (0,3 mm)
* Programmable with software SW-BSY+
Running speed and forces
OPEN
Forces
SB
III
SB
II
SB
I
1500 N
1000 N
1000 N
500 N
CDP 1500
Technical data
CLOSE
Closure
Ranges
~6
mm/s
/
~17
mm/s
6 mm/s
5 mm/s
5 m
m/s
77
mm
23
mm
All forces
+ app. 20 % switch-off
reserve (temporary)