■ Wait:
Set the length of time, in seconds, to wait after this CEC
Automation Event has been activated before ANY other Automation
Event can be detected.
■ CEC Command:
Set the CEC command to send when the specified
Automation Event is activated. Clicking the “Test” button will send the
command immediately. Available CEC commands are:
– Power Off:
Turn off the connected HDMI display device.
– Power On:
Turn on the connected HDMI display device.
– Active Source:
Force the connected HDMI display device to
switch to the HDMI input that this unit is connected to.
Note: Not all HDMI devices support all CEC commands.
■ RS-232:
Enable or disable sending an RS-232 command when the
currently selected Automation Event is activated.
Note: The RS-232 port must be in “Control” mode to send commands
to external devices.
■ Delay:
Set the length of time, in seconds, that the specified
Automation Event must continue to be true before sending the
defined RS-232 command.
■ Wait:
Set the length of time, in seconds, to wait after this RS-232
Automation Event has been activated before ANY other Automation
Event can be detected.
■ RS-232 Command:
Click the Edit icon ( )
to define the RS-232
command to send when the specified Automation Event is activated.
Clicking the “Test” button will send the command immediately.
2) RS-232 Setting:
Provides controls to configure the settings and behavior
of the RS-232 port.
■ Mode:
Switch the behavior of the RS-232 port between “Console”
and “Control”. When “Console” is selected, the unit can receive and
be controlled directly via RS-232 commands. When “Control” is
selected the RS-232 port can send Automation commands to control
other devices.
■ RS-232 Setting Edit:
Click on the Edit icon ( )
to configure the
various RS-232 port settings including baud rate, data length, parity
and stop bits.