  FUNCTIONAL TEST 

 

AC Mode 

The UPS delivers power to the loads derived from the utility and maintains proper battery charge. It also 
regulates the output voltage to within a narrow range. 
 

On-Battery Mode 

The UPS operates on battery when the line voltage or frequency has fallen outside the limits. Local 
users are alerted to this mode of operation by visual and audible indicators. The UPS provides power to 
the load from the battery and through its inverter and the output voltage and frequency of the UPS are 
regulated within a narrow range 
 

1. 

Switch On 

Press the power switch on the front panel then the status LED will

 

light up.   

 

2. 

Switch Off 

Press again the power switch, the status LED on the front panel will go off.   

 

3. 

Cold Start / Start on Battery:   

          This UPS can be turned on even when AC is not present. 

 

Press the power switch on the front panel then the status LED will light up.   
 

ROUTINE MAINTENANCE AND STORAGE

 

 

ROUTINE MAINTENANCE

 

1. 

Use dry soft clothes to clean the front panel and plastic parts. Do not use any detergent that 
contains alcoholic ingredient.   

 
2. 

The expected lifetime of the battery is around 3 years. Improper operation and harsh environment 
will reduce the actual lifetime. 

 
3. 

Unplug the UPS from power inlet if the UPS will not operate for long period of time. 

 

STORAGE

 

1. 

First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables 
connected the UPS to avoid battery drain.   

 
2. 

The UPS should be stored in a cool dry location. 

 
3. 

Make sure the battery is fully charged before the UPS is stored. 

 

4.

 

For extended storage in moderate climates, the battery should be charged for 12 hours every 3 
months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat 
it every 2 months in high temperature locations.

 

 

 

 

TROUBLE SHOOTING

 

 

Problem 

Possible Cause 

Solution 

The UPS does 
not perform 
expected 
runtime. 

Batteries are not fully 
charged. 

Recharge the battery by leaving the UPS 
plugged in. 

Battery is slightly worn out. 

Contact CyberPower Systems Technical 
Support. 

The UPS will not 
turn on. 
 

The unit is not connected to 
an AC outlet.

 

The unit must be connected to a 
220-240V 50/60Hz outlet.   

 

The battery is worn out. 

Contact CyberPower Systems Technical 
Support. 

Mechanical problem. 

Contact CyberPower Systems Technical 
Support. 

Outlets do not 
provide power to 
equipment 

Fuse is blown due to 
overload 

Turn the UPS off and unplug at least one 
piece connected equipment. Unplug the 
power cord of the UPS then remove the 
fuse compartment beneath the power inlet 
of the UPS and replace the blown fuse 
with a spare one. Lock the compartment 
back to the UPS. Connect power cord 
then turn the UPS on. Make sure that your 
spare fuse meets the specification. 

Batteries are discharged 

Allow the unit to recharge for at least 4 
hours. 

Unit has been damaged by 
a surge or spike. 

Contact CyberPower Systems Technical 
Support. 

PowerPanel® 
Personal Edition 
is inactive (all 
icons are gray). 

The serial/USB cable is not 
connected. 

Connect the serial/USB cable to the UPS 
unit and an open serial port on the back 
of the computer. You must use the cable 
that came with the unit. 

The serial/USB cable is 
connected to the wrong 
port. 

Try another serial/USB port of your 
computer. 

The unit is not providing 
battery power. 

Shutdown your computer and turn the 
UPS off. Wait 10 seconds and turn the 
UPS back on. This should reset the unit. 

The serial cable is not the 
cable that was provided with 
the unit. 

You must use the cable included with the 
unit for the software. 

 

 

 

 

 

 

 

 

 

 

 

 

TECHNICAL SPECIFICATIONS 

Model 

 

Value600EI-AU 

Value800EI-AU

 

Value1000EI-AU 

Capacity    (VA) 

600VA 

800VA 

1000VA 

Capacity    (Watts) 

360W 

480W 

550W 

Input 
Frequency Range 

47~63Hz(Auto Sensing) 

Output 
On Battery Output 
Voltage 

Simulated Sine Wave at /-5% 

On Battery Output 
Frequency   

50/60 Hz +/-1% 

Overload Protection 

On Utility: Fuse, On Battery: Internal Current Limiting 

Physical

 

Total # of UPS 
Receptacles 

Maximum Dimensions 

140mm(H)*100mm(W)*300mm(D) 

Weight   

4.77 kg   

5.33 kg   

5.42 kg   

Battery

 

Sealed Maintenance 
Free Lead Acid Battery 

12V/7AH x1 

12V / 9AH x1 

12V / 9AH x1 

Typical Recharge Time 

8 Hours 

Warning Diagnostics 

Indicators 

Power On / Using Battery 

Audible Alarms 

On Battery, Low Battery, Overload, Fault 

Environmental

 

Operating Temperature 

0

C to 40

Operating Relative 
Humidity 

0 to 90% 

Communication

 

PowerPanel®   
Personal Edition 
Software   

Windows 7/Vista/XP/2000/Server 2003/2008 

Management

 

Auto-Charger 

Yes 

Auto-Restart 

Yes 

USB 

Yes 

 

DEFINITIONS FOR ILLUMINATED LED INDICATORS 

 

 

       

       
 

LED 

 

 
 
 
 

Alarm 

 
 

 

 

Fuse 

 

Condition 

On 

Off 

Normal 

Normal 

Flash 

Two 

Beeps 

Normal 

Utility Failure - The UPS is providing battery power to outlets. 

Flash 

Rapid 

Beeps 

Normal 

Utility Failure - The UPS is providing battery power.    The 
rapid beeps indicate the battery will run out of power shortly. 

Off 

Long 

Beep 

Normal/ 

Blown 

Overload - Occurs when connected equipment exceeds the 
rating of the unit. Turn the UPS off and unplug at least one 
piece of equipment from the UPS. Check the fuse and do the 
replacement if necessary. Turn the UPS on. 

 