HARDWARE INSTALLATION

 

 

 

 

 

HARDWARE INSTALLATION

 

These versatile UPS systems can be mounted in a rackmount or vertical 
tower  orientation.  This  versatility  is  especially  important  to  growing 
organizations  with  changing  needs  that  value  having  the  option  to 
position  a  UPS  on  a  floor  or  in  a  rackmount  system.  Please  follow  the 
instructions below for the respective mounting methods.

 

 

SAFETY PRECAUTIONS

 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  only  use  the 

supplied hardware to attach the mounting brackets.

 

 

RACKMOUNT INSTALLATION 

Step 1: Remove the dust covers 

Remove the dust covers *7pcs from the screw holes. 

 

Step 2: Rackmount ears & hanging brackets installation 

Attach two rackmount ears to the UPS using the provided M5X7L*8pcs 
screws and tighten two hanging brackets with the M5X6L*6pcs screws. 

 

Step 3: Rackmount rail Installation 

The  rails  adjust  to  mount  in  48-cm  (19-inch)  racks  from  52  to  91.5cm 
(20.5  to  36  inches)  deep.  Select  the  proper  holes  in  the  rack  for 
positioning  the  UPS  in  the  rack.  The  UPS  takes  up  3  rack  units,  rack 
holes positions 1 through 9. 

 

Position the guide screws on the rails into the rear rack square holes to 
temporarily support the rails in place. Tighten the front rail screws on the 
rack. 

 

 

Содержание OL10000RT3UPDU

Страница 1: ...L6000RT3UPDU OL8000RT3UPDU OL10000RT3UPDU OL6KRT3UHW OL8KRT3UHW OL10KRT3UHW CyberPower Systems USA Inc 4241 12th Avenue East Suite 400 Shakopee MN 55379 Phone 877 297 6937 Fax 952 403 0009 www CPSww com K01 0000597 00 ...

Страница 2: ...N Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage to your equipment and cause fire...

Страница 3: ... USB communication cable Serial Interface Cable RS 232 Battery module Rackmount ears Stands 2 2 sets Tie plate 1 1 set Flat head screws M5X7L 8 2 sets Pan head screws M5X12L 4 2 sets Pan head screws M5X6L 14 2 sets Guide screws M5X10L 2 2 sets Plastic washers 8 2 sets Screw hole dust covers 10 2 sets Power cord PowerPanel Business Edition software is available on our website Please visit www cpsww...

Страница 4: ...ch the mounting brackets RACKMOUNT INSTALLATION Step 1 Remove the dust covers Remove the dust covers 7pcs from the screw holes Step 2 Rackmount ears hanging brackets installation Attach two rackmount ears to the UPS using the provided M5X7L 8pcs screws and tighten two hanging brackets with the M5X6L 6pcs screws Step 3 Rackmount rail Installation The rails adjust to mount in 48 cm 19 inch racks fro...

Страница 5: ... the rear of the rack with two M5X6L screws and two plastic washers Step 5 Place and secure the UPS on the rails Slide the hanging brackets on the UPS into the rails mounted in the rack with the front of the unit facing toward you Secure the UPS to your rack with four M5X12L 4pcs screws at the front of the rack Located in position 5 position 7 How to slide the UPS out from the rack The UPS will be...

Страница 6: ...ecure the tie bracket with the screws M5X7 4pcs Insert dust covers into the screw holes that are not being used Step 3 Rotate the Multifunction LCD Module Unscrew the upper panel of the UPS Separate the upper panel from the UPS Gently lift the LCD module out Rotate it to the tower orientation Reinstall it for a tower configuration ELECTRICAL INSTALLATION After completing the hardware installation ...

Страница 7: ...er completing the hardware installation of the UPS you are now ready to plug in the UPS and connect your equipment SAFETY PRECAUTIONS CAUTION Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity rang...

Страница 8: ...arm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to the technical specifications 6 This UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will automatically charge even when the unit is...

Страница 9: ...Mains Battery L2 L1 PE L2 L1 PE Manual Bypass SAFETY PRECAUTIONS CAUTION Input and Output circuit breakers must be OFF during the building installation CAUTION An additional two pole disconnect device is necessary during the building installation CAUTION Disconnected EPO will immediately shut down the logic circuit output of the UPS Wiring the EPO signal is optional CAUTION Local safety rules may ...

Страница 10: ...ut terminal block Step 4 Output configuration Insert the output cable through the appropriate cable gland not included and connect the three wires to the output terminal block Step 5 Fix the terminal block cover on the PDU s Tighten the four screws to fix the terminal block cover on the PDU s Step 6 Fix the inspection window cover on the PDU s Tighten the four screws to fix the inspection window c...

Страница 11: ... Backfeed Protection Connector UPS L1 L2 PSDR AC L1 AC L2 IP L1 IP L2 Backfeed 1 2 4 5 3 L1 L2 I P EMI L1 L2 L1 L2 PE Mains PE Jumper2 Jumper1 WITH BACKFEED PROTECTION CONFIGURATION 1 Customers should provide an external isolation device Magnetic Contactor which is upstream and outside the UPS and capable of supporting the UPS input current 2 Remove the interconnection wires Jumper1 Jumper2 on Bac...

Страница 12: ...erial Port Serial port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 7 Surge Protected Communication Ports RJ 45 RJ 11 These ports are used to protect standard RJ 45 RJ 11 based products ADSL LAN Phone Modem Lines an...

Страница 13: ...Input Output Connectors Use these connectors to attach the PDU or HW PDU to the Power module 7 Connectors Cover Provides safety protection when removing the PDU or HW PDU 8 Output Circuit Breaker Provides output overload and fault protection 9 Battery Backup Surge Protected Outlets Provides battery backup and surge protection They ensure power is provided to connected equipment over a period of ti...

Страница 14: ...e the connector cover for access 6 Output Cable Use this output cable to connect the Battery module to the Power module or to the next Battery module 7 DC Breaker Use the DC breaker to disconnect battery output BP240V30ART3U BP240V50ART3U CONNECTION 1 POWER MODULE WITH ONE BATTERY MODULE Step 1 Turn off the DC breaker of the Battery module Step 2 Loosen the two screws to remove the battery cable r...

Страница 15: ...ep 5 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable Step 6 Use a power cord to plug AC input inlet of the 2nd battery module into AC output outlet of the 1st Battery module Step 7 Turn on the DC breaker of the 2nd Battery module Step 8 Set the EBM number to the respective setting to match the number of installed units To do this via the LCD control panel...

Страница 16: ...Y Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description ON...

Страница 17: ...iption O P Volt XXX XV Displays the Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Displays the Output VA BAT Volt XXX XV Displays th...

Страница 18: ...o select the Language submenu 6 Press the and buttons to scroll to the language that you want to select You may be prompted to save the selection if so press the ENTER button to save the setting 7 Press the ESC button to cancel or return to previous LCD menu LCD SETTINGS CONFIGURATION There are 24 UPS settings that can be configured by the user 1 Press the ENTER button to activate the MAIN MENU 2 ...

Страница 19: ...Fail I P Power Fail Converter Mode Converter Off O P Freq 50Hz O P Freq 60Hz Converter OFF Screen Saver Disable 1 Minutes 5 Minutes 5 minutes Clear Event Log Activate None Button OFF LOCK Disable Enable Disable Charger Function SBM Constant SBM Signal Inputs Disable EPO ROO Disable Charger Check Disable Enable Disable With Transformer Disable Enable Disable Backfeed Check Disable Enable Disable Th...

Страница 20: ...owing figure WALL MOUNTING INSTRUCTIONS Step 1 Remove the Multifunction LCD Module Unscrew the right panel of the Power module Separate the right panel from the UPS Gently lift the LCD module out Reinstall the right panel Step 2 Rotate the DB26 Connector of LCD Module Step 3 Connect the DB26 Cable Connect the DB26 cable from LCD module to the Remote Control Port on the front panel or rear panel as...

Страница 21: ... electric shock turn off and unplug the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please refer to the front side of the Battery module for the model number of the correct replacement batteries For battery procurement log onto www CPSww com or co...

Страница 22: ...Switch to Bypass Step 4 Press ON OFF button to turn off UPS Step 5 Pull the PDU or HW PDU away from the Power module Loosen the four screws that hold the PDU or HW PDU to the Power module Pull the PDU or HW PDU away from the Power module and loosen the two screws that hold the cover Step 6 Fix the cover on the PDU or HW PDU Tighten the two screws and fix the cover on the PDU or HW PDU to hide the ...

Страница 23: ...de the Interlock Bracket to the right Slide the Interlock Bracket to the right Tighten the one screw that fix the Interlock Bracket in the right Step 6 Check the Power module auto transfer to Line Mode After Sliding the Interlock Bracket to the right the Power module will auto transfer to Line Mode Check the LCD screen shows Line Mode SAFETY PRECAUTIONS CAUTION It must be done by qualified personn...

Страница 24: ...ut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 20 12V 7AH 20 12V 9 0AH Recharge Time 0 90 Typical 4 hours 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that Supports Multi Language Interface 19 Types of Read Out 24 Types of Function Setting 3 Event Logs LED Indicators Power On White Line Mode Green ...

Страница 25: ...e line and neutral wires Missing ground wire Connect ground wire No ground wire Disable Wiring Fault alarm on LCD panel Line Abnormal Wrong utility power backed up during UPS auto restart Check whether voltage or frequency of utility power is out of range Output Short Output short circuit Your attached equipment may have problems please remove them and check again Over Temperature High temperature...

Страница 26: ...e to us at Cyber Power Systems USA Inc 4241 12th Ave E STE 400 Shakopee MN 55379 or send us an e mail message at claims cpsww com for instructions within 10 days of the occurrence 2 When you contact CyberPower identify the Product the Purchase Date and the item s of Connected Equipment Have information on all applicable insurance or other resources of recovery payment that are available to the Ini...

Страница 27: ...g 1 Loss of or damage to data records or software or the restoration of data or records or the reinstallation of software 2 Damage from causes other than AC Power Line Transients spikes or surges on properly installed grounded and code compliant 120 volt power lines in the United States and Canada transients surges or spikes on standard telephone land lines PBX telephone equipment lines or Base 10...

Страница 28: ...terference in which case the user will be required to correct the interference at his own expense Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits This document is believed to be accurate but CyberPower reserves the right to change or correct the contents and does not assume any responsibility for omissions or errors Need Additional Help Feel f...