ELECTRICAL INSTALLATION CONT.
MBP DETECTION CABLE INSTALLATION
Connect the MBP detection cable to the specific UPS connector.
Important !
Only with compatible CyberPower UPS.
After installing the MBP detection cable to the UPS EPO port, the UPS signal input must be set up
for Manual Bypass. Refer to the UPS User Manual as following.
(1) OL5KRTHD/OL6KRTHD models :
Set up communication Signal input Manual Bypass Save Change?
(2) OL6KRT/OL8KRT/OL10KRT/OL6KRTF/OL8KRTF/OL10KRTF models :
Configure Signal input Manual Bypass Save ?
[NOTE] If MBP Detection Cable is installed, the UPS EPO and ROO functions will be disabled.
[NOTE] If MBP Detection Cable is not installed, the UPS will not automatically transfer to bypass mode.
[NOTE] TO AVOID DAMAGE! Follow the correct operation and start up procedures using either the
MBP Detection Cable (P12) or Retaining EPO & ROO Function (P18).
OPERATIONS WITH MBP DETECTION CABLE INSTALLED
UPS START-UP WITH MBP63A2 AND MBP DETECTION CABLE
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
[NOTE] If the UPS model name is OL6KRT/OL8KRT/OL10KRT/OL6KRTF/OL8KRTF/OL10KRTF,
Please check the MCU version* on LCD Panel by the following operations.
1. Press the “ENTER” button to enter the “Main Menu”.
2. Press the “
▲
” and “
▼
” buttons to scroll to the “Information” option.
3. Press the “ENTER” button to select the “Information” submenu.
4. Press the “
▲
” and “
▼
” buttons to scroll through the “Information” submenu to check the MCU
version*.
[NOTE]If the MCU version* is UE_V3Rn and the number of n is less than 6,(For Example: MCU Ver. =
UE_V3R5) Please contact CyberPower for assistance to upgrade the MCU version*.
MBP Detection port
UPS EPO port
MBP Detection cable