65
HSTP3T 60-500 KE User Manual
Chapter 5 Maintenance
9) Turn off the maintenance bypass breaker.
10) After 30S, the rectifier starts, the rectifier indicator LED goes green, and then
inverter starts.
11) After 60S, the system transfers to Normal mode.
5.4 Battery Setting
The setting of battery needs to be done after the first time of powering off or any
changes done on the batteries.
The battery configure ration can be done through the LCD control panel (Fig.5-1)
or though monitoring software (Fig.5-2).
Fig.5-1 Configuration through LCD control panel
Fig.5-2 Configuration through monitoring software
5.4.1 Setting of Battery Type
The battery type can be only set through the monitoring software. The system at
present supports lead acid battery and Lithium iron phosphate battery (LFPB).
5.4.2 Setting of Battery Number
1) Setting battery number for Lead- Acid battery
The nominal voltage of one block battery is 12V and for each block of battery, it
consists of 6 cells (each cell of 2V).For the setting, as is shown in Fig.5-1, if the