Copyright © 2012 CyberPower Systems, Inc.
Installation
7
For CPSPV3600ETL: From #12 AWG to #10 AWG (3mm
2
to
6mm
2
).
For CPSPV3000ETL: From #14 AWG to #12 AWG (2mm
2
to
3mm
2
).
For CPSPV2000ETL: From #14 AWG to #12 AWG (2mm
2
to
3mm
2
).
-
The wires to DC connectors:
Recommended Type:
For PV (+): PV-KBT4/2,5I with 1.5~2.5mm^2 cable
(double-isolation)
For PV (-): PV-KST4/2,5I with 1.5~2.5mm^2 cable
(double-isolation)
IMPORTANT:
Wiring should be not undersized. Undersized wiring can result in
significant power losses and reduction in system efficiency.
2.
AC Circuit breaker
This breaker must be sized to handle the rated maximum output
voltage and current of the On-grid Solar Power Generating
System. (Please refer to the On-grid Solar Power Generating
System specification)
Recommended AC Circuit Breaker:
For CPSPV3600ETL: 23 Amps / 250 Vac.
For CPSPV3000ETL: 20 Amps / 250 Vac.
For CPSPV2000ETL: 13 Amps / 250 Vac
WARNING! Fire
、
Shock and Energy Hazard
Before installing the On-grid Solar Power Generating System, read
all instructions and cautionary markings located in this manual,
on the PV array, and on the main service panel.
!