 CPS525SL / CPS725SL 

Guaranteed Uninterruptible Power System 

 

 

INSPECTION 

The box should contain the following: 
(1) PowerPanel™ software (floppy disk); (1) serial interface cable (DB-9);  
(1) telephone communication cable; (1) user manual; (1) warranty registration card; 
(1) USB adapter ; (1) UPS unit. 

 

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 

1.  Make sure that the total Volt-Amp (VA) requirements of your computer, monitor and peripheral 

equipment does not exceed 1440 VA. 

2.  Insure that the equipment plugged into the three battery power-supplied outlets does not exceed 

the UPS unit’s rated capacity( 525VA/300W for CPS525SL,  725VA/400W for CPS725SL).  If 
rated unit capacities are exceeded, an overload condition may occur and cause the UPS unit to 
shut down and the circuit breaker to trip.   

3.  If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert 

Watts (W) or Amps (A) into VA by doing the calculations below.  Note:  The below equation only 
calculates the maximum amount of VA that the equipment can use, not what is typically used by 
the equipment at any one time.  Users should expect usage requirements to be approximately 
60% of below value to estimate power requirements: 
           Watts (W) x 1.82 =            VA or            Amps (A) x 120 =            VA 
Add the totals up for all pieces of equipment and multiply this total by .6 to calculate actual 
requirements. 
There are many factors that can effect the amount of power that your computer system will 
require.  The total load that you will be placing on the battery-powered outlets should not exceed 
80% of the unit’s capacity.

   

 

Hardware Installation Guide 

1.  Your new UPS may be used immediately upon 

receipt.  However, 

recharging the battery for at 

least four hours

 is recommended to insure that 

the battery’s maximum charge capacity is 
achieved.  Charge loss may occur during 
shipping and storage.  To recharge the battery, 
simply leave the unit plugged into an AC outlet.  
The unit will charge in both the on as well as the off 
position. 

2.  If you wish to use the software, connect the 

enclosed serial interface cable to the serial port on 
the UPS and an open serial port on the computer.  
If you are not going to use the software, you do not 
need to connect the cable. 

3. 

With the UPS unit off and unplugged, connect your 
computer, monitor, and any externally powered data storage device 
(Zip drive, Jazz drive, Tape drive, etc…) into the battery power 
supplied outlets.  Plug your peripheral equipment (printer, scanner, 
speakers) into the full-time surge protection outlets.  

DO NOT plug a 

laser printer, copier, space heater, vacuum or other large 
electrical device into the UPS.  The power demands of these 
devices will overload and possibly damage the unit. 

4.  To protect a fax, phone or modem, connect a telephone cable from 

the wall jack outlet to the in jack of the UPS.  Connect a telephone 
cable from the out jack with the CPU icon to the modem port on your 

 

Содержание CPS525SL

Страница 1: ...CPS525SL CPS725SL Guaranteed Uninterruptible Power System 1 User Manual for CPS525SL CPS725SL with USB Interface and PowerPanel Software ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT ...

Страница 2: ...ctions completely This UPS is designed to provide guaranteed power protection for connected electronic equipment The accompanying PowerPanel software saves data closes open applications and automatically shuts down your computer system in an intelligent and orderly manner Safety Instructions 1 Description 1 Determining Power Requirements 2 Hardware Installation Guide 2 Software Installation Guide ...

Страница 3: ...uce the risk of fire or electric shock do not use with or near an aquarium Condensation from the aquarium can cause the unit to short out DESCRIPTION Battery Surge Outlets Provides three battery powered surge outlets for connected equipment and insures temporary uninterrupted operation of your equipment during a power failure Full Time Surge Protection Outlets Provides three always on surge suppre...

Страница 4: ...equirements There are many factors that can effect the amount of power that your computer system will require The total load that you will be placing on the battery powered outlets should not exceed 80 of the unit s capacity Hardware Installation Guide 1 Your new UPS may be used immediately upon receipt However recharging the battery for at least four hours is recommended to insure that the batter...

Страница 5: ...PANEL SOFTWARE INSTALLATION GUIDE Note Use of the software is optional The UPS will provide surge suppression and battery backup without the software You must use the software if you wish to have the automatic shutdown feature Software Installation Optional Cyber Power UPS can provide surge suppression and battery backup without the software However if you need to schedule for UPS Auto shutdown th...

Страница 6: ...k and restart your computer When your computer restarts the PowerPanel software will appear on your screen for a few seconds and then minimize It will appear as a blue and white battery icon located in the system tray near the clock FOR WINDOWS 2000 1 Click on Start point to Settings and then click Control Panel 2 Double click on Power Options 3 On the UPS Tab click Select 4 In the UPS Selection D...

Страница 7: ... can be downloaded from www cyberpowersystems com downloads htm It works in conjunction with the UPS to provide full protection of valuable computer systems applications and data In the event of a power failure PowerPanel automatically saves and closes open files under auto assigned file names or existing files names after a software controlled delay The computer 8 put 8o err 8 pu auso 5 7 m 1illy...

Страница 8: ... an item to the schedule 6 Clear Button This button is used to delete the selected item 7 Cancel Shutdown This button is used to cancel the current shutdown 8 Day Date and Time This is the area where you select the day date and time that you want the shutdown to occur Once you have selected it click the Add Button to add the item to the schedule Please note The use of the schedule is optional and ...

Страница 9: ...then save the file to the PCTemp folder which is located in the root directory of your C drive where C is the name of your main hard drive Once all open files have been saved and closed PowerPanel will shutdown the operating system Once the operating system is shutdown the UPS will turn off within 90 seconds Wait until the UPS has turned off before plugging the UPS back into the outlet Once the te...

Страница 10: ...ing the red wire to the positive terminal of the battery and connecting the black wire to the negative terminal of the battery 9 Slide the battery back into the compartment 10 Replace the outlet cover and the 6 retaining screws 11 Recharge the unit for 4 8 hours to ensure the UPS performs expected runtime REMINDER Batteries are consider HAZARDOUS WASTE and must be disposed of properly Contact your...

Страница 11: ...it on On Off On Set None Electrical Wiring Fault This indicates a wiring problem with the AC outlet such as bad ground miss ground or reversed wiring User is advised to disconnect all electrical equipment from the outlet and have an electrician check the outlet to insure proper wiring ...

Страница 12: ...cted to an AC outlet The unit must be connected to a 110 120v 60Hz outlet The battery is worn out Contact CyberPower Systems about replacement batteries at tech cyberpowersystems com The UPS will not turn on Mechanical problem Contact CyberPower Systems at tech cyberpowersystems com The serial cable is not connected Connect the serial cable to the UPS unit and an open serial port on the back of th...

Страница 13: ...CPS525SL CPS725SL Guaranteed Uninterruptible Power System 11 Additional troubleshooting information can be found at www cyberpowersystems com FAQs htm ...

Страница 14: ...0 C to 35 C Operating Relative Humidity 0 to 95 NON CONDENSING Size Length x Width x Height 9 7 8 x 6 3 16 x 3 1 8 25 8cm x 15 9cm x 8 3cm Net Weight 13 lbs 15 lbs Typical Battery Recharge Time 8 hours typical from total discharge Typical Battery Life 3 to 6 years depending on number of discharge recharge cycles Battery Type 12V 7 0AH 12V 9 0AH Recommended Battery Spill proof Maintenance free seal...

Страница 15: ... as described below to have the benefits of this Limited Warranty Limited Warranty CyberPower warrants to you the Initial Purchaser that the Product will be free from defects in material and workmanship for three years from the date of original purchase subject to the terms of this Limited Warranty To be covered you must still be the owner of the Product at the time of the failure that results in ...

Страница 16: ...CPS525SL CPS725SL Guaranteed Uninterruptible Power System 14 or not the Initial Customer makes a claim for recovery including but not limited to a ...

Страница 17: ...s of the event for which you want to make a claim for warranty service 3 When you call write or E Mail identify the Product the Purchase Date and the item s of Connected Equipment Have information on all applicable insurance or other resources of recovery payment that are available to the Initial Customer for the Connected Equipment and the name of the power utility supplier for the location of th...

Страница 18: ...unded and code compliant 120 volt power lines in the United States and Canada transients surges or spikes on standard telephone land lines PBX telephone equipment lines or Base 10 100T Ethernet lines when properly installed and connected This exclusion applies for example to fluctuations in data transmission or reception by CATV or RF transmission or fluctuations or by transients in such transmiss...

Страница 19: ...limits for a Class B Digital Device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no g...

Отзывы: