CPS3500&CPS5000 Series 

 

Copyright © 2009 CyberPower Systems, Inc.

 

 

*

Note: 

Circuit breaker 5a provides max 40A protection for 1a socket.   

*

Note: 

Circuit  breaker  5b  provides  max  12A  protection  for  UK  socket  or  16A  for  Schuko  and  France 

socket. 

 

6. AC Input Circuit Breaker

 

Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection. 

 
7. Battery Input Wiring Fault LED 

Battery  input  wiring  fault  LED  will  illuminate  and  make  an  audible  alarm  to  indicate  the  wiring  polarity  is 
reversed. 
 

8. Output Selector 

Output  Selector  provides  four  most  common  operation  situations  for  switch  include  Normal,  Bypass  with 
AVR, Bypass, Off. No matter under what situations, the charger would keep charging external batteries if 

utility power is still alive.

 

Normal :The unit will provide all functions of uninterruptible power supply include charger. 
Bypass  with  AVR:  The  unit  will  bypass  the  utility  power  with  voltage  regulator  and  shutdown  the  unit 

when the utility power exceed 300Vac or below 140Vac. 

Bypass: The unit will bypass the utility power to output directly. 

*

Note:

  Bypass  model  wouldn

t  provide  any  overvoltage  protection  .Utility  power  may  damage 

equipments plugged to EPS, make sure equipment safe before switch to this model.

 

Off: The unit will interrupt all outlets power output. 

*

Note: 

The charger would still work under these four switch modes. 

 

 
*For PIE and STD Series, the unit provides specific Bypass function.

 

Bypass:  The  switch  provides  the  bypass  for  charge  only  and  shutdown  the  unit  when  the  utility  power 

exceeds 300Vac or below 140Vac. In charger only mode, AVR and battery backup will not work.

 

 
9. Power Switch 

Used as the master on/off switch for equipment connected to the battery power supplied outlets. 
 

10. Power On Indicator

 

This LED is above the power switch. It illuminates when the utility condition is normal and the EPS outlets 
are providing power, free of surges and spikes. 

 

11. LCD Display Toggle / Selected Switch

 

Users can

 

monitor EPS status and set up functions using the toggle.

 

 

12. Multifunction LCD Readout

 

High resolution and intelligent LCD display shows all the EPS information with icons and messages. For 
more information please check the DEFINITIONS FOR ILLUMINATED LCD INDICATORS section. 

 

13.

 SNMP/DB9/USB Network slot 

Remove  the  cover  panel  to  install  optional  SNMP/DB9/USB  CARD  that  allows  remote  monitoring  and 
control of your UPS through network or cable. 

*

 

Note: 

This function only provide on PRO Series.

 

 

Содержание CPS3500PIE

Страница 1: ...t Suite 400 Shakopee MN 55379 Tel 877 297 6937 Fax 952 403 0009 Website http www cyberpowersystems com E mail sales cyberpowersystems com CyberPower Europe CyberPower Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu com K01 0000137 02 ...

Страница 2: ...NPACKING 4 AUTOMATIC VOLTAGE REGULATOR 4 HARDWARE INSTALLATION GUIDE 4 DESCRIPTION 5 INSTALLATION GUIDE 7 REPLACING THE BATTERY 9 DEFINITIONS FOR ILLUMINATED LCD 10 EPS STATUS INQUIRY AND FUNCTIONS SETUP 11 1 GENERAL MODE 11 2 SET UP MODE 11 FAULT WARNING DISPLAY AND ALARM 13 TROUBLE SHOOTING 14 TECHNICAL SPECIFICATIONS 15 ...

Страница 3: ...ith the CE requirement CPS3500PIE Series include CPS3500PIE CPS3500PIE FR CPS3500PIE UK and other versions CPS3500PRO Series include CPS3500PRO CPS3500PRO FR CPS3500PRO UK and other versions CPS3500STD Series include CPS3500STD CPS3500STD FR CPS3500STD UK and other versions CPS5000PIE Series include CPS5000PIE CPS5000PIE FR CPS5000PIE UK and other versions CPS5000PRO Series include CPS5000PRO CPS5...

Страница 4: ...power demands of these devices will overload and possibly damage the unit DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR HEAT DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS S HOUSING DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO EPS OUTPUT SOCKETS SAFETY EN62040 1 1 EMI Conducted Emission IEC EN 62040 2 Category C2 Radiated Emission IEC EN 62040 2 Categor...

Страница 5: ...unit will charge in both the ON and OFF positions 2 DO NOT plug a laser printer paper shredder copier space heater vacuum or other large electrical device into the EPS The power demand of these devices may overload and damage the unit DO NOT use with medical or life support equipment DO NOT use with or near aquariums as condensation may cause the unit to short 3 After connecting the hard wires plu...

Страница 6: ...s 10 meters and the cable O D must be 10AWG CPS3500PIE CPS3500PRO CPS3500STD CPS5000PIE CPS5000PRO CPS5000STD Series or greater 2 AC Inlet AC input terminals Note The O D of the distribution cables must be 10AWG CPS3500PIE CPS3500PRO CPS3500STD CPS5000PIE CPS5000PRO CPS5000STD or greater 3 DC Inlet Battery input terminals Note Maximum battery wiring cable length is 2 meters and the cable O D must ...

Страница 7: ...ltage protection Utility power may damage equipments plugged to EPS make sure equipment safe before switch to this model Off The unit will interrupt all outlets power output Note The charger would still work under these four switch modes For PIE and STD Series the unit provides specific Bypass function Bypass The switch provides the bypass for charge only and shutdown the unit when the utility pow...

Страница 8: ...2 Make sure the POWER SW Output Selector and the BATTERY SW are turned off Step1 EPS will not function if the Output Selector is OFF Make sure the Selector on Normal position after all installation procedures 3 Connect the AC OUTPUT connections AC plugs or terminal connections Step2 4 Connect the AC power source to AC INPUT Make sure AC power is off first Step3 Step 1 Step 2 Step 3 ...

Страница 9: ...on the LCD Module Display should be 220V This completes the start up process Step 6 9 Press and hold the Display toggle switch for 4 seconds then release The machine will begin a self test and enter Battery Mode for 6 seconds before returning to Line Mode Make sure the self test is ready or see the Definitions for illuminated LCD on page 10 for a list of alarm code definitions 10 After ensuring th...

Страница 10: ...S5000PRO and CPS5000STD of DC protective device CPS3500PIE Series include CPS3500PIE CPS3500PIE FR CPS3500PIE UK and other versions CPS3500PRO Series include CPS3500PRO CPS3500PRO FR CPS3500PRO UK and other versions CPS3500STD Series include CPS3500STD CPS3500STD FR CPS3500STD UK and other versions CPS5000PIE Series include CPS5000PIE CPS5000PIE FR CPS5000PIE UK and other versions CPS5000PRO Serie...

Страница 11: ...te This function of specified models cannot work 4 NORMAL MODE Icon This icon will illuminate when the EPS is working under normal conditions 5 ON BAT On Battery Icon During a severe brownout or blackout this icon illuminates and an alarm sounds 2 short beeps followed by a pause to indicate the EPS is operating from its external batteries During a prolonged brownout or blackout the alarm will soun...

Страница 12: ...play toggle for 4 seconds If the machine is in the Battery Mode it enters the status of Mute If the machine is in the Line Mode it proceeds to Self Test c If the Display toggle remains untouched for over 30 seconds the LCD backlight will turn off automatically 2 Set up Mode Step 1 The machine enters Set Up Mode after holding the Display toggle for 10 second Icon 4 5 6 7 8 9 lights indicate that Se...

Страница 13: ...the UPS shutdown point according to the battery voltage There are 5 settings 38V 39V 40V 41V 42V and the default setting is 40V g Mode Select There are 2 settings Robust 1 Standard 2 The robust mode and the standard mode are provided to select Using the generators is suggested to select the robust mode and using the computers is suggested to select the standard mode The default setting is Robust 1...

Страница 14: ...heck total load to confirm the rating of EPS Battery Icon Flash Rapid Beep Battery Missing In Line Mode Battery Missing Turn the EPS off check battery wiring and presence of battery High Temperature Output Off Over 70 Check fans function and air vent clearances Rapid Beep Low Battery Output Off Insufficient battery capacity Recharge the battery Recurring Beep Over Charge or AVR Error In Line Mode ...

Страница 15: ...damage that rapidly turns it off and on Turn the EPS off Wait 10 seconds and then turn the EPS on The unit is not connected to an AC outlet The unit must be connected to a 220 230 240v outlet The battery is worn out Contact CyberPower Systems about replacement batteries at service cyberpower eu com The EPS will not turn on Mechanical problem Contact Cyberpower Systems via phone or visit our websit...

Страница 16: ...50 60 Hz 1 Overload Protection On Utility Circuit Breaker On Battery Internal Current Limiter Transfer Time 10 ms Typical Output Receptacles UK Type 2 Terminal Block Note Schuko 2 Terminal Block for Germany type External Battery Voltage x Recommended Rating X Quantity 12V x 200Ah X 2 12V x 200Ah X 4 External Battery Voltage 24V 48V External Battery Type Sealed Maintenance Free Lead Acid Battery Ex...

Страница 17: ...CPS3500 CPS5000 Series Copyright 2009 CyberPower Systems Inc 16 ...

Страница 18: ... 403 0009 Website http www cyberpowersystems com E mail sales cyberpowersystems com CyberPower Europe CyberPower Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu com Entire contents copyright 2009 CyberPower Systems Inc All rights reserved Reproduction in whole or in part without ...

Отзывы: