![CyberPower CPS3500PIE Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/cyberpower/cps3500pie/cps3500pie_user-manual_2702241006.webp)
CPS3500&CPS5000 Series
Copyright © 2009 CyberPower Systems, Inc.
5
BASIC OPERATION
operation
DESCRIPTION
1. AC Outlets
EPS PRO/PIE Series have two general plug-in outlets (UK/Schuko/ France) and one terminal outlet for
connected equipment which ensures temporary uninterrupted operation of the equipment during a power
failure.
Max. Output of 1a is 40A ; Max. Output of 1b is 12A for UK socket, 16A for Schuko/France socket.
Max. Output wattage of (1a+1b) is 2450W (CPS3500PIE/CPS3500PRO/CPS3500STD Series)/ 3500W
(CPS5000PIE /CPS5000PRO/CPS5000STD Series).
*Note:
Maximum cord length is 10 meters and the cable O.D. must be 10AWG
(CPS3500PIE/CPS3500PRO/CPS3500STD & CPS5000PIE/CPS5000PRO/CPS5000STD Series) or
greater.
2. AC Inlet
AC input terminals
*
Note
:
:
:
:
The O.D. of the distribution cables must be 10AWG (CPS3500PIE/CPS3500PRO/CPS3500STD
& CPS5000PIE/CPS5000PRO/CPS5000STD) or greater.
3. DC Inlet
Battery input terminals
*Note
:
Maximum battery wiring cable length is 2 meters and the cable O.D. must be 4AWG or greater.
4. DC Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
5. AC Output Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
CPS3500PRO/CPS5000PRO
CPS3500PIE/CPS3500STD
CPS5000PIE/CPS5000STD
* STD Series only use soft pad