background image

CPS3500&CPS5000 Series 

 

Copyright © 2009 CyberPower Systems, Inc.

 

 

12 

setting is 200AH. 

Function description

: The charger will automatically adjust current to setting value. 

 

c. 

Nominal Output Voltage: Configures the correct electricity/voltage supplied in the area/country 
where the EPS will be used. 220V, 230V and 240V may be selected. The system default setting 

is 220V. 

Function description

: AVR Dynamic Voltage Compensation works automatically based on the 

system voltage settings. 

 

d. 

Static  Frequency  Tolerance:  There  are  6  settings  (1,2,4,6,8,10%),  and  the  default  setting  is 
+/-10%. 

Function description

: The settings may be adjusted to the quality of the electricity in use. 

 

e. 

Slew  Rate  (Dynamic  Frequency  Tolerance):  There  are  5  different  settings  (0.25,0.5,1,2,4 

Hz/Sec). The default value is 4Hz/sec. 

Function description

: “Slew Rate” indicates the tolerance of a device in accepting frequency 

variances. The lower “Slew Rate” results in less tolerance but better protection for the connected 

loads. 

 
f. 

Battery  Shutdown  Voltage:  This  function  adjusts  the  UPS  shutdown  point  according  to  the 

battery voltage. There are 5 settings(38V,39V,40V,41V,42V) and the default setting is 40V. 

 
g. 

Mode Select: There are 2 settings( Robust{1},Standard{2} ) ,The robust mode and the standard 

mode are provided to select. Using the generators is suggested to select the robust mode, and 
using the computers is suggested to select the standard mode. The default setting is Robust {1}. 
The settable items are sorted by unit as in the following table

 

 

Items 

Unit 

Icon Lit 

Delay Time 

Min 

ON BAT 

Battery AH 

ON BAT 

Nominal Output Voltage 

NORMAL MODE 

Static Frequency Tolerance 

NORMAL MODE 

Slew Rate 

None 

Battery Shutdown Voltage 

ON BAT 

Mode Select 

None 

None 

 

Step 3: 

Press and hold the toggle for 4 seconds. When the icons blink, the value of each item can be 

changed by slightly pressing the toggle. 

 

Step 4: 

To save the value and return to general mode, press and hold the toggle for 4 seconds. 

 

Note: If the machine is left idle for over 30 seconds during setup, it will turn off the backlight 

and return to general mode automatically.   

Note: If user wants to return to general mode without saving changes, there are two methods: 

1.  Wait for the backlight to turn off 

2. 

Press and hold the “Display” toggle for 10 seconds

 

Содержание CPS3500PIE

Страница 1: ...t Suite 400 Shakopee MN 55379 Tel 877 297 6937 Fax 952 403 0009 Website http www cyberpowersystems com E mail sales cyberpowersystems com CyberPower Europe CyberPower Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu com K01 0000137 02 ...

Страница 2: ...NPACKING 4 AUTOMATIC VOLTAGE REGULATOR 4 HARDWARE INSTALLATION GUIDE 4 DESCRIPTION 5 INSTALLATION GUIDE 7 REPLACING THE BATTERY 9 DEFINITIONS FOR ILLUMINATED LCD 10 EPS STATUS INQUIRY AND FUNCTIONS SETUP 11 1 GENERAL MODE 11 2 SET UP MODE 11 FAULT WARNING DISPLAY AND ALARM 13 TROUBLE SHOOTING 14 TECHNICAL SPECIFICATIONS 15 ...

Страница 3: ...ith the CE requirement CPS3500PIE Series include CPS3500PIE CPS3500PIE FR CPS3500PIE UK and other versions CPS3500PRO Series include CPS3500PRO CPS3500PRO FR CPS3500PRO UK and other versions CPS3500STD Series include CPS3500STD CPS3500STD FR CPS3500STD UK and other versions CPS5000PIE Series include CPS5000PIE CPS5000PIE FR CPS5000PIE UK and other versions CPS5000PRO Series include CPS5000PRO CPS5...

Страница 4: ...power demands of these devices will overload and possibly damage the unit DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR HEAT DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS S HOUSING DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO EPS OUTPUT SOCKETS SAFETY EN62040 1 1 EMI Conducted Emission IEC EN 62040 2 Category C2 Radiated Emission IEC EN 62040 2 Categor...

Страница 5: ...unit will charge in both the ON and OFF positions 2 DO NOT plug a laser printer paper shredder copier space heater vacuum or other large electrical device into the EPS The power demand of these devices may overload and damage the unit DO NOT use with medical or life support equipment DO NOT use with or near aquariums as condensation may cause the unit to short 3 After connecting the hard wires plu...

Страница 6: ...s 10 meters and the cable O D must be 10AWG CPS3500PIE CPS3500PRO CPS3500STD CPS5000PIE CPS5000PRO CPS5000STD Series or greater 2 AC Inlet AC input terminals Note The O D of the distribution cables must be 10AWG CPS3500PIE CPS3500PRO CPS3500STD CPS5000PIE CPS5000PRO CPS5000STD or greater 3 DC Inlet Battery input terminals Note Maximum battery wiring cable length is 2 meters and the cable O D must ...

Страница 7: ...ltage protection Utility power may damage equipments plugged to EPS make sure equipment safe before switch to this model Off The unit will interrupt all outlets power output Note The charger would still work under these four switch modes For PIE and STD Series the unit provides specific Bypass function Bypass The switch provides the bypass for charge only and shutdown the unit when the utility pow...

Страница 8: ...2 Make sure the POWER SW Output Selector and the BATTERY SW are turned off Step1 EPS will not function if the Output Selector is OFF Make sure the Selector on Normal position after all installation procedures 3 Connect the AC OUTPUT connections AC plugs or terminal connections Step2 4 Connect the AC power source to AC INPUT Make sure AC power is off first Step3 Step 1 Step 2 Step 3 ...

Страница 9: ...on the LCD Module Display should be 220V This completes the start up process Step 6 9 Press and hold the Display toggle switch for 4 seconds then release The machine will begin a self test and enter Battery Mode for 6 seconds before returning to Line Mode Make sure the self test is ready or see the Definitions for illuminated LCD on page 10 for a list of alarm code definitions 10 After ensuring th...

Страница 10: ...S5000PRO and CPS5000STD of DC protective device CPS3500PIE Series include CPS3500PIE CPS3500PIE FR CPS3500PIE UK and other versions CPS3500PRO Series include CPS3500PRO CPS3500PRO FR CPS3500PRO UK and other versions CPS3500STD Series include CPS3500STD CPS3500STD FR CPS3500STD UK and other versions CPS5000PIE Series include CPS5000PIE CPS5000PIE FR CPS5000PIE UK and other versions CPS5000PRO Serie...

Страница 11: ...te This function of specified models cannot work 4 NORMAL MODE Icon This icon will illuminate when the EPS is working under normal conditions 5 ON BAT On Battery Icon During a severe brownout or blackout this icon illuminates and an alarm sounds 2 short beeps followed by a pause to indicate the EPS is operating from its external batteries During a prolonged brownout or blackout the alarm will soun...

Страница 12: ...play toggle for 4 seconds If the machine is in the Battery Mode it enters the status of Mute If the machine is in the Line Mode it proceeds to Self Test c If the Display toggle remains untouched for over 30 seconds the LCD backlight will turn off automatically 2 Set up Mode Step 1 The machine enters Set Up Mode after holding the Display toggle for 10 second Icon 4 5 6 7 8 9 lights indicate that Se...

Страница 13: ...the UPS shutdown point according to the battery voltage There are 5 settings 38V 39V 40V 41V 42V and the default setting is 40V g Mode Select There are 2 settings Robust 1 Standard 2 The robust mode and the standard mode are provided to select Using the generators is suggested to select the robust mode and using the computers is suggested to select the standard mode The default setting is Robust 1...

Страница 14: ...heck total load to confirm the rating of EPS Battery Icon Flash Rapid Beep Battery Missing In Line Mode Battery Missing Turn the EPS off check battery wiring and presence of battery High Temperature Output Off Over 70 Check fans function and air vent clearances Rapid Beep Low Battery Output Off Insufficient battery capacity Recharge the battery Recurring Beep Over Charge or AVR Error In Line Mode ...

Страница 15: ...damage that rapidly turns it off and on Turn the EPS off Wait 10 seconds and then turn the EPS on The unit is not connected to an AC outlet The unit must be connected to a 220 230 240v outlet The battery is worn out Contact CyberPower Systems about replacement batteries at service cyberpower eu com The EPS will not turn on Mechanical problem Contact Cyberpower Systems via phone or visit our websit...

Страница 16: ...50 60 Hz 1 Overload Protection On Utility Circuit Breaker On Battery Internal Current Limiter Transfer Time 10 ms Typical Output Receptacles UK Type 2 Terminal Block Note Schuko 2 Terminal Block for Germany type External Battery Voltage x Recommended Rating X Quantity 12V x 200Ah X 2 12V x 200Ah X 4 External Battery Voltage 24V 48V External Battery Type Sealed Maintenance Free Lead Acid Battery Ex...

Страница 17: ...CPS3500 CPS5000 Series Copyright 2009 CyberPower Systems Inc 16 ...

Страница 18: ... 403 0009 Website http www cyberpowersystems com E mail sales cyberpowersystems com CyberPower Europe CyberPower Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu com Entire contents copyright 2009 CyberPower Systems Inc All rights reserved Reproduction in whole or in part without ...

Отзывы: