Over Charge

Battery is over
charged

The UPS will turn off the

is normal

Model Pin Error

UPS internal fault

Consult dealer.

Ambient Over
Temperature

The ambient
temperature is too
high

Check the environment
ventilation.

Heatsink Over
Temperature

Inside temperature of
UPS is too high

Check the ventilation of UPS
and the ambient temperature.

Ambient NTC abnormal

UPS internal fault

Consult dealer.

Para Cable Male Loss

The parallel cable is
disconnected

Check the parallel cable.

Para Cable Female
Loss

The parallel cable is
disconnected

Check the parallel cable.

Para Bat Differ

The battery packs of
some UPSs are
disconnected

Check if all the battery pack is
connected.

Para Line Differ

The mains input of
some UPSs is
disconnected

Check the building wiring and
input cable.
Check if the input breaker is
closed.
Ensure the UPSs are
connected to same input
source.

Para Work Mode Differ

There are different
power strategy setting
in parallel system

The UPSs with different power
strategy setting (Ex. one Line

are forbidden to parallel.

Para Rate Power Differ

There are different
UPSs in parallel
system

The UPSs with different
capacity (Ex. one 6KVA and
one 10KVA) are forbidden to
parallel.

ECO In Para

ECO function is
enabled in parallel
system

ECO function is forbidden in
parallel system.

IP Fuse Open

Input fuse break

Check the input fuse status

36

Содержание 10K On-Line series

Страница 1: ...User s Manual...

Страница 2: ...9 4 Installation 11 4 1 Moving to The Installation Site 11 4 2 Unpacking and Inspection 11 4 3 Input and Output Power Wires and Protective Earth Ground Installation 12 4 4 Operating Procedure for Con...

Страница 3: ...7 3 Trouble Shooting In Else Cases 38 8 Battery Maintenance 39 9 Communication Port 40 9 1 USB Interface 40 9 2 Dry contact Interface optional 40 9 3 RS 232 Interface 40 9 4 Intelligent slot 40...

Страница 4: ...ed to direct sunlight or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step...

Страница 5: ...source batteries In order to fully disconnect the UPS first turn the input breaker in the OFF position then disconnect the mains lead Indiscriminate operation of switches may cause output loss or dam...

Страница 6: ...ips and handles When changing batteries replace with the same quantity and the same type of batteries Do not attempt to dispose of batteries by burning them It could cause explosion The UPS may be con...

Страница 7: ...40 2 Category C3 EMS Level 3 Level 3 Level 4 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips IEC EN 61000 4 11 Low Frequency Signals IEC EN 61000 2 2 Warning This is a pro...

Страница 8: ...miliarize yourself with them and understand their meaning 5 Symbol and Explanation Symbol Explanation Symbol Explanation Alert you to pay special attention Caution of high voltage Alternating current...

Страница 9: ...maintenance free batteries power the inverter This manual covers the UPS listed as follows Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model...

Страница 10: ...to the worst mains input condition Extra wide input voltage frequency range and waveform avoid excessive dissipating limited battery energy Internal charger could be up to 4Amps to decrease rechargin...

Страница 11: ...Storage temperature 15 C to 50 C BATTERIES Model No 6K 8K 10K Internal BAT number and type 20 12V 28W 20 12V 28W 20 12V 34W BAT pack 28A 37 4A 47A The load capacity would be derated to 90 automaticall...

Страница 12: ...708 x 550 70 6KXL 260 x 708 x 550 25 8K 260 x 708 x 550 86 8KXL 260 x 708 x 550 28 10K 260 x 708 x 550 86 10KXL 260 x 708 x 550 28 Model No 100 Load 6K 5 8K 5 10K 4 3 4 Typical Backup Time Typical val...

Страница 13: ...PO Port Dry contact optional Intelligent Slot Fan Parallel Port Maintenance Switch Input Breaker Terminal Block 6K XL 10K XL Fig 3 1 Back View of 6K XL 10K XL The back view of 8K XL models are same as...

Страница 14: ...allet jack or a truck before unpacking the UPS 4 2Unpacking and Inspection 1 At the installation site the utmost care shall be taken when removing the packaging in order to avoid damaging the equipmen...

Страница 15: ...ler immediately if there is any damage or lacking of some parts 4 3 Input and Output Power Wires and Protective Earth Ground Installation 4 3 1 Notes for installation 1 The UPS must be installed in a...

Страница 16: ...ry Cabinet Breaker in Positive Pole Negative pole Neutral Pole 32A 240VDC 50A 240VDC Torque for fixing above terminals 3 95 4 97Nm 35 44 1b in 4 3 2 Installation For safety please cut off the mains po...

Страница 17: ...ommended to select the UL1015 8AWG 6mm 2 or other insulated wire which complies with AWG Standard for the UPS input and output wirings 5 For 8 10KVA UPS it is recommended to select the UL1015 6AWG 10m...

Страница 18: ...only for XL model 10 Install an output breaker between the output terminal of UPS and the load and the breaker should with leakage current protective function if necessary 11 Turn off all the loads fi...

Страница 19: ...e should be strictly followed For 6KVA select the UL1015 8AWG 6mm 2 respectively or other insulated wire which complies with AWG Standard for the UPS battery wirings For 8 10KVA select the UL1015 6AWG...

Страница 20: ...supplies is when the emergency occurs such as the failure of load the UPS can cut off the output at once by operating the EPO port manually 4 5 2 The connection Normally the EPO connector is closed wi...

Страница 21: ...on more than 1S to turn on Turn off When the unit has been turned on press this button more than 3S to turn off 5 Operation 5 1 Display Panel The UPS has a five button dot matrix LCD with white text a...

Страница 22: ...n to previous menu Up Press this button more than 200mS to move the focus to the up menu Down Press this button for more than 200mS to move the focus to the down menu UPS state Normal LED Green Batter...

Страница 23: ...nd settings through the front panel display During powering on the LCD would display the CyberPower logo for several seconds and then enter to the default page which shows the UPS status summary On th...

Страница 24: ...continuously for more than 1 second the buzzer will beep for 1s UPS starts to turn on 4 A few seconds later the UPS turns into Line mode If the mains power is abnormal the UPS will transfer to Battery...

Страница 25: ...down and no voltage is available from the UPS output 5 3 LCD Operation Except the default UPS status summary screen the user could get more useful information about UPS current status old events which...

Страница 26: ...Fig 5 2 status menu 23...

Страница 27: ...s Fault Clear all events Clear all faults Event 0001 12 00 00 Utility abnormal 1 10 Alarm 0002 12 00 00 Overload 1 10 Fault 0003 12 00 00 Over tempearture 1 5 Clear all events Yes No Clear all faults...

Страница 28: ...he same time Clear EPO status once EPO status is enabled the UPS output would be cut off To recover to normal status first EPO connector should be closed and enter this menu to clear EPO status then U...

Страница 29: ...ome settings would change the specification and some settings would enable or disable some functions The unsuitable option set by user may result in potential failures or protecting function loss even...

Страница 30: ...Short circuit clearance enabled disabled disabled Power strategy normal Rated output voltage 208 220 230 240V 230V Output frequency autosensing 50 60Hz autosensing Bypass voltage low range 10 15 20 15...

Страница 31: ...uld be gained in ECO mode Once the mains power is loss or abnormal the UPS would transfer to Line mode or Battery mode and the load is supplied continuously The great virtue is overall high efficiency...

Страница 32: ...e enabled through the LCD setting in Bypass mode Enter the power strategy setting menu by following chapter of 5 3 4 6 3 Parallel Function 6 3 1 Brief introduction of the redundancy N X is currently t...

Страница 33: ...port on the UPS connect each UPS one by one with the parallel cable and re screw the Parallel port cover which is supplied in the accessories Strictly follow the chapter of 4 the wiring requirement o...

Страница 34: ...Fig 6 1 Input and output Terminal Block wiring diagram 31...

Страница 35: ...hem is less than 1V If the difference is more than 1V check the wiring 11 Press the button of one UPS each UPS would start to turn on all the UPSs would transfer to the INV mode together Measure the o...

Страница 36: ...ce switch of each UPS from UPS to BPS Set the main maintenance switch or static switch from UPS to BPS switch off the main output breaker and the main input breaker the UPSs would shut down Ensure the...

Страница 37: ...the wanted UPS and reinstall the new UPS parallel system by following step 1 to 9 of last chapter install a new parallel UPS system If the removed UPS or the remained UPS will be used in a stand alon...

Страница 38: ...nnected to the UPS Check the battery breaker is turn on Battery low Battery voltage is low When audible alarm sounding empty Output Overload Overload Check the loads and remove some non critical loads...

Страница 39: ...fer The battery packs of some UPSs are disconnected Check if all the battery pack is connected Para Line Differ The mains input of some UPSs is disconnected Check the building wiring and input cable C...

Страница 40: ...dealer Bus Under Voltage UPS internal fault Consult dealer Bus Unbalance UPS internal fault Consult dealer Bus short UPS internal fault Consult dealer Bus Softstart Fail UPS internal fault Consult de...

Страница 41: ...he building wiring and input cable Check if the input breaker is closed Emergency supply period shorter than nominal value Batteries not fully charged batteries defect 12 hours and then check capacity...

Страница 42: ...ging and over discharging The UPS should be charged once every 4 to 6 months if it has not been used for a long time In the regions of hot climates the battery should be charged and discharged every 2...

Страница 43: ...contact interface Please contact your local distributor for details 9 3 RS 232 Interface The RS 232 port is available for UPS monitoring control and firmware updates 9 4 Intelligent slot This series i...

Отзывы: