Set the external battery pack breaker in “OFF” position and
connect the 20 pieces of batteries in series.
Connect the external battery pack to the battery terminals.
Check the polarity of connection is correct.
Set the breaker of the battery pack in the “ON” position.
Set the mains input breaker in the “ON” position, the UPS
would power on and start to charge the battery pack.
4.5 EPO Connection
4.5.1 Introduction
Emergency power off function which the UPS supplies is, when the
emergency occurs, such as the failure of load, the UPS can cut off
the output at once by operating the EPO port manually.
4.5.2 The connection
Normally the EPO connector is closed with a wire on the rear panel,
which is supplied in the accessory. Once the connector is open, the
UPS would stop the output and enter EPO status.
Enable the EPO status
Disable the EPO status
Fig. 4-8 Default EPO status
To recover to normal status, first EPO connector should be closed,
and enter LCD menu (illustrated in the chapter of 5.3.3) to clear
EPO status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.