Model
6k
8/10k
Protective earthing conductor
Min cross section
6mm
2
(8AWG)
10 mm
2
(6AWG)
Input L, N, G
Min conductor cross section
6mm
2
(8AWG)
10 mm
2
(6AWG)
Input breaker
40A/250VAC
63A/250VAC
Output L,N,
Min conductor cross section
6mm
2
(8AWG)
10 mm
2
(6AWG)
External Battery Cabinet
Positive Pole(+), Negative pole(-),
Neutral Pole
Min conductor cross section
6mm
2
(8AWG)
10 mm
2
(6AWG)
External Battery Cabinet Fuse
in Positive Pole(+), Negative pole(-),
Neutral Pole
30A/240VDC
60A/240VDC
External Battery Cabinet Breaker
in Positive Pole(+), Negative pole(-),
Neutral Pole
32A/240VDC
50A/240VDC
Torque for fixing above terminals
3.95~4.97Nm
(35~44 1b in)
4.3.2 Installation
For safety, please cut off the mains power switch before
installation!
Use cable cross section and protective device specification
1) It is suggested to install an external isolating device against
current backfeed between Mains input and UPS (see Fig.4-6).
After the device is installed, it must add a warning label with the
following wording or the equivalent on the external AC contactor:
RISK OF VOLTAGE BACKFEED. Isolate the UPS before
operating on this circuit, then check for hazardous voltage
between all terminals.