32
TECHNICAL SPECIFICATIONS
Models
OLS1000ERT2UA OLS1500ERT2UA OLS2000ERT2UA OLS3000ERT2UA
Configuration
Capacity (VA)
1000
1500
2000
3000
Capacity (Watts)
900
1350
1800
2700
Form Factor
Rackmount/Tower
Energy-saving
Technology
Yes, ECO Mode Efficiency
≧
95%
Input
Input Voltage Range
80~ 300 Vac
Input Frequency
Range
40~70Hz
Input Power Factor
≧
0.99
Cold Start
Yes
Output
Output Waveform
Pure Sine Wave
Output Voltage
208, 220, 230, 240Vac ±1%
Output Frequency
50 / 60Hz (Auto-Sensing or Configurable) ±0. 5Hz *
Transfer Time
(Typically)
0ms
Rated Power Factor
0.9
Harmonic Distortion
THD < 3% at Linear Load, < 5% at Non-linear Load
Crest Factor
3 : 1
ECO Mode Voltage
Regulation
±10%, ±15% (Configurable)
UPS Outlets
(4+4) IEC C13
(4+4) IEC C13
(4+4) IEC C13
(4+4) IEC C13
(1) IEC C19
Protection
Surge Protection
Surge Suppression
≧
350(Joules)
Phone /
Network Protection
RJ11/RJ45 (One In/One Out)
Overload Protection
Line Mode:
105~110% Overload warning only
110~120% Warning, transfer to bypass after 60s
>120% Transfer to bypass immediately
Battery Mode:
105~110% Overload warning only
110~120% Warning, shutdown after 10s
>120% Shutdown immediately
Short Circuit Protection UPS Output Cut off Immediately / Circuit Breaker Protection