INSTALLING YOUR UPS SYSTEM

 

7

 

SYSTEM BLOCK DIAGRAM

Output

Input

Filter

PFC

AC/DC

BUS

Inverter

DC/AC

STS

Charger

AC/DC

Internal

Bypass

Battery

Output

Filter

Input

Line Mode

Battery Mode

Bypass Mode

Control

&

Monitoring

LCD Module

USB & DB9

SNMP Slot

Bypass

Switch

Maintenance

Bypass

Maintenance Bypass

HARDWARE INSTALLATION GUIDE

 

1.

Battery  charge  loss  may  occur  during  shipping  and  storage.  Before

using  the  UPS,  it’s  strongly  recommended  to  charge  batteries  for  four
hours to ensure the batteries’ maximum charge capacity. To recharge the
batteries, simply plug the UPS into an AC outlet.

2.

When  using  the  included  software,  connect  either  the  serial  or  the

USB cable between the computer and the corresponding port on the UPS.
Note: If the USB port is used, the serial port will be disabled. They cannot 
be  used  simultaneously.  After  connecting  to  either  the  USB  port  or  the
Serial  port  on  the  UPS,  a  computer  with  the  PowerPanel

®

  Business

Edition  Agent  software  installed  can  control  the  operating  schedule,
battery test, outlets, as well as obtain UPS status information. However,
other computers with PowerPanel

®

 Business Edition Client software can

only obtain UPS status information via LAN connection.

3.

Connect  your  computer,  monitor,  and  any  externally-powered  data

storage  device  (Hard  drive,  Tape  drive,  etc.)  into  the  outlets  only  when
the UPS is off and unplugged. DO NOT plug a laser printer, copier, space
heater, vacuum, paper shredder or other large electrical device into the
UPS.  The  power  demands  of  these  devices  will  overload  and  possibly 
damage the unit.

4.

To  protect  a  fax  machine,  telephone,  modem  line  or  network  cable,

connect the telephone  or network cable from  the  wall jack outlet to the
jack marked “IN” on the UPS and connect a telephone cable or network
cable from the jack marked “OUT” on the UPS to the modem, computer,
telephone, fax machine, or network device.

5.

Press the ON/OFF switch to turn the UPS on. The Power-On indicator 

light  will  display  when  activated.  If  an  overload  is  detected,  an  audible
alarm  will  sound  and  the  UPS  will  continuously  emit  two  beeps  per 
second. For resetting the unit, unplug some equipment from the outlets.
Make  sure  your  equipment  carries  a  load  current  within  the  unit’s  safe
range, (refer to the technical specifications).

6.

This UPS is equipped with an auto-charge feature. When the UPS is

plugged  into  an  AC  outlet,  the  battery  will  automatically  charge,  even
when the unit is switched off.

7.

To maintain an optimal battery charge, leave the UPS plugged into an

AC outlet at all times.

8.

Before storing the UPS for an extended period of time, turn the unit

OFF. Then cover it and store it with the batteries fully charged. Recharge
the  batteries  every  three  months  to  ensure  good  battery  capacity  and
long  battery  life.  Maintaining  a  good  battery  charge  will  help  prevent
possible damage to the unit from battery leakage.

9.

The UPS has one USB port (default) and one Serial port that allows

connection  and  communication  between  the  UPS  and  any  attached
computer running the PowerPanel

®

 Business Edition Agent software. The

UPS  can  control  the  computer’s  shutdown  during  a  power  outage
through the connection while the computer can monitor the UPS and alter
various  programmable  parameters. Note: Only  one  communication  port
can  be  used  at  a  time.  The  port  not  in  use  will  automatically  become 
disabled or the serial port will be disabled if both ports are attached.

10.

EPO (Emergency Power Off) Port:

EPO ports allow administrators the capability to connect the UPS unit to
customer-supplied  EPO  switches.  These  installations  give  operators  a
single access point to immediately power-off all equipment connected to
the UPS during an emergency.

11.

To avoid electric shock, turn the unit OFF and disconnect the  unit

from  utility  power  before  hardwiring  the  UPS  (in/out  power  cord).  The
in/out power cord MUST be grounded.

Содержание OL10000ERT3UM

Страница 1: ...User s Manual OL6000ERT3UP OL8000ERT3UP OL10000ERT3UP OL6000ERT3UM OL8000ERT3UM OL10000ERT3UM Cyber Power Systems Inc www cyberpower com K01 0000508 01 ...

Страница 2: ...power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards CAUTION Wiring must be done by qualified personnel CAUTION DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT Under no circumstances this unit should be used for medical applications involving life supp...

Страница 3: ...SB communication cable Serial Interface Cable RS 232 Battery module Rackmount ears Stands 2 2 sets Tie plate 1 1 set Flat head screws M5X7L 8 2 sets Pan head screws M5X12L 4 2 sets Pan head screws M5X6L 14 2 sets Guide screws M5X10L 2 2 sets Plastic washers 8 2 sets Screw hole dust covers 14 2 sets Power cord PowerPanel Business Edition software is available on our website Please visit www cpsww c...

Страница 4: ...ch the mounting brackets RACKMOUNT INSTALLATION Step 1 Remove the dust covers Remove the dust covers 10pcs from the screw holes Step 2 Rackmount ears hanging brackets installation Attach two rackmount ears to the UPS using the provided M5X7L 8pcs screws and tighten two hanging brackets with the M5X6L 6pcs screws Step 3 Rackmount rail Installation The rails adjust to mount in 48 cm 19 inch racks fr...

Страница 5: ... the rear of the rack with two M5X6L screws and two plastic washers Step 5 Place and secure the UPS on the rails Slide the hanging brackets on the UPS into the rails mounted in the rack with the front of the unit facing toward you Secure the UPS to your rack with four M5X12L 4pcs screws at the front of the rack Located in position 5 position 7 How to slide the UPS out from the rack The UPS will be...

Страница 6: ...ecure the tie bracket with the screws M5X7 4pcs Insert dust covers into the screw holes that are not being used Step 3 Rotate the Multifunction LCD Module Unscrew the upper panel of the UPS Separate the upper panel from the UPS Gently lift the LCD module out Rotate it to the tower orientation Reinstall it for a tower configuration ELECTRICAL INSTALLATION After completing the hardware installation ...

Страница 7: ...er completing the hardware installation of the UPS you are now ready to plug in the UPS and connect your equipment SAFETY PRECAUTIONS CAUTION Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity rang...

Страница 8: ...S to the modem computer telephone fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the un...

Страница 9: ...Mains Battery N L PE N L PE Manual Bypass SAFETY PRECAUTIONS CAUTION Input and Output circuit breakers must be OFF during the building installation CAUTION An additional two pole disconnect device is necessary during the building installation CAUTION Disconnected EPO will immediately shut down the logic circuit output of the UPS Wiring the EPO signal is optional CAUTION Local safety rules may requ...

Страница 10: ...ut terminal block Step 4 Output configuration Insert the output cable through the appropriate cable gland not included and connect the three wires to the output terminal block Step 5 Fix the terminal block cover on the PDU s Tighten the four screws to fix the terminal block cover on the PDU s Step 6 Fix the inspection window cover on the PDU s Tighten the four screws to fix the inspection window c...

Страница 11: ...er1 Jumper2 on Backfeed Protection Connector UPS L N PSDR AC L AC N IP L IP N Backfeed 1 2 4 5 3 L N I P EMI L N L N PE Mains PE Jumper2 Jumper1 WITH BACKFEED PROTECTION CONFIGURATION 1 Customers should provide an external isolation device Magnetic Contactor which is upstream and outside the UPS and capable of supporting the UPS input current 2 Remove the interconnection wires Jumper1 Jumper2 on B...

Страница 12: ...port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 7 Surge Protected Communication Ports RJ 45 RJ 11 These ports are used to protect standard RJ 45 RJ 11 based products ADSL LAN Phone Modem Lines and cabling systems ...

Страница 13: ...6 Input Output Connectors Use these connectors to attach the PDU or HW PDU to the Power module 7 Connectors Cover Provides safety protection when removing the PDU or HW PDU 8 Output Circuit Breaker Provides output overload and fault protection 9 Battery Backup Surge Protected Outlets Provides battery backup and surge protection They ensure power is provided to connected equipment over a period of ...

Страница 14: ...this input connector to daisy chain the next Battery module Remove the connector cover for access 6 Output Cable Use this output cable to connect the Battery module to the Power module or to the next Battery module BPE240V30ART3U BPE240V50ART3U CONNECTION 1 POWER MODULE WITH ONE BATTERY MODULE Step 1 Loosen the two screws to remove the battery cable retention bracket of the power module Step 2 Use...

Страница 15: ...he two screws to remove the battery cable retention bracket of the 1st battery module Step 3 Use the output cable of the 2nd Battery module to connect the 2nd Battery module to the 1st Battery module Step 4 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable Step 5 Use a power cord to plug AC input inlet of the 2nd battery module into AC output outlet of the ...

Страница 16: ...RY Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description O...

Страница 17: ...o UPS Status Information Submenu Description O P Volt XXX XV Displays the Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Display...

Страница 18: ...ness or RMCARD with PowerPanel Business or RMCARD Event Content MULTI LANGUAGE INTERFACE Users can configure 1 of the 4 available languages for display English Español Spanish Français French Deutsch German 1 Press the ENTER button to activate the MAIN MENU 2 Press the and buttons to scroll to the Configure option 3 Press the ENTER button to select the Configure submenu 4 Press the and buttons to ...

Страница 19: ... 10 20 15 10 15 15 15 20 10 15 Bypass Condition Check Freq Volt Check Volt Only No Bypass Check Freq Volt ECO Mode 1 Disable Enable Disable V Range 15 V Range 10 for Enable V Range 10 Manual Bypass Disable Enable Disable UPS Diagnostic Battery Test Alarm Test Indicator Test Fan Test Battery Test Activate None Audible Alarms Disable Enable Enable EBM Number 0 1 2 3 4 5 6 7 8 9 10 0 Wiring Fault Dis...

Страница 20: ...ondition This condition will still result in an audible alarm 2 Configure Audible Alarms as Disable on the LCD module and it will stop warning of any malfunction audibly MANUAL BATTERY TEST Configure Battery Test as Active on the LCD module and it will perform the Manual Battery Test Graphical Load Battery Capacity Display 1 Press the ESC button to return to UPS Status 2 Press the and buttons to s...

Страница 21: ... figure WALL MOUNTING INSTRUCTIONS Step 1 Remove the Multifunction LCD Module Unscrew the right panel of the Power module Separate the right panel from the UPS Gently lift the LCD module out Reinstall the right panel Step 2 Rotate the DB26 Connector of LCD Module Step 3 Connect the DB26 Cable Connect a DB26 cable not included from LCD module to the Remote Control Port on the front panel as shown i...

Страница 22: ...ry terminals Replacement Batteries Please refer to the front side of the Battery module for the model number of the correct replacement batteries For battery procurement log onto www CPSww com or contact your local dealer Battery Disposal Batteries are considered hazardous waste and must be disposed of properly Contact your local government for more information about proper disposal and recycling ...

Страница 23: ... Switch to Bypass Step 4 Press ON OFF button to turn off UPS Step 5 Pull the PDU or HW PDU away from the Power module Loosen the four screws that hold the PDU or HW PDU to the Power module Pull the PDU or HW PDU away from the Power module and loosen the two screws that hold the cover Step 6 Fix the cover on the PDU or HW PDU Tighten the two screws and fix the cover on the PDU or HW PDU to hide the...

Страница 24: ...de the Interlock Bracket to the right Slide the Interlock Bracket to the right Tighten the one screw that fix the Interlock Bracket in the right Step 6 Check the Power module auto transfer to Line Mode After Sliding the Interlock Bracket to the right the Power module will auto transfer to Line Mode Check the LCD screen shows Line Mode SAFETY PRECAUTIONS CAUTION It must be done by qualified personn...

Страница 25: ...Battery Mode 105 130 Load for 10 sec 131 150 Load for 2 sec Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 20 12V 7 2AH 20 12V 9 0AH Recharge Time Typically 4 hours 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that Supports Multi Language Interface 23 Types of R...

Страница 26: ...ty is sufficient and acceptable If batteries have been recently replaced then reset the Battery Replacement Date using PowerPanel Business Edition Agent software RMCARD interface if installed or through the LCD control panel on the UPS See LCD Setting Configuration EPO OFF Missing the EPO connection Check the EPO connection Wiring Fault Line and neutral wires are reversed Exchange line and neutral...

Страница 27: ...Systems Inc www cyberpower com Entire contents copyright 2017 Cyber Power Systems Inc All rights reserved Reproduction in whole or in part without permission is prohibited PowerPanel Business Edition and PowerPanel Personal Edition are trademarks of Cyber Power Systems Inc ...

Отзывы: