Copyright ©  2017 Cyber Power Systems, Inc.

 

IMPORTANT SAFETY INSTRUCTIONS

 

1

 

This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual 
thoroughly before attempting to unpack, install, or operate the UPS. 

CAUTION!   

The  UPS  must  be  connected  to  a  grounded  AC  power 

outlet with fuse or circuit breaker protection. DO NOT plug the UPS into 
an outlet that is not grounded. If you need to power-drain this equipment, 
turn off and unplug the unit.

 

CAUTION!   

The  battery  can  power  hazardous  components  inside  the 

unit, even when the AC input power is disconnected.

 

CAUTION!   

The UPS should be placed near the connected equipment 

and easily accessible. 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a 

temperature  and  humidity  controlled  indoor  area,  free  of  conductive 
contaminants. (Please see specifications for acceptable temperature and 
humidity range).

 

CAUTION!    (No  User  Serviceable  Parts):

  Risk  of  electric  shock,  do 

not  remove  cover.  No  user  serviceable  parts  inside.  Refer  servicing  to 
qualified service personnel.

 

CAUTION!    (Non-Isolated  Battery  Supply): 

Risk  of  electric  shock, 

battery circuit is not isolated from AC power source; hazardous voltage 
may exist between battery terminals and ground. Test before touching.

 

CAUTION!   

To  reduce  the  risk  of  fire,  connect  the  UPS  to  a  branch 

circuit with 40 amperes (OL6000) / 50 amperes (OL8000) / 70 amperes 
(OL10000)  maximum  over-current  protection  in  accordance  to  CE 
requirement.

 

CAUTION!   

The AC outlet where the UPS is connected should be close 

to the unit and easily accessible. 

CAUTION!   

Please use only VDE-tested, CE-marked mains cable, (e.g. 

the mains cable of your equipment), to connect the UPS to the AC outlet.

 

CAUTION!   

Please  use  only  VDE-tested,  CE-marked  power  cables  to 

connect any equipment to the UPS. 

CAUTION!   

When installing the equipment, ensure that the sum of the 

leakage  current  of  the  UPS  and  the  connected  equipment  does  not 
exceed 3.5mA.

 

CAUTION! 

The  OL6000  /  OL8000  /  OL10000  models  are 

permanently-connected  equipment  and  only  qualified  maintenance 
personnel may carry out installations.

 

CAUTION!   

Do not unplug the unit from AC Power during operation, as 

this will invalidate the protective ground insulation. 

CAUTION!   

To avoid electric shock, turn off and unplug the unit before 

installing  the  input/output  power  cord  with  a  ground  wire.  Connect  the 
ground wire prior to connecting the line wires! 

CAUTION!   

Do not  use an improper size power cord  as it may cause 

damage to your equipment and cause fire hazards. 

CAUTION!   

Wiring must be done by qualified personnel.

 

CAUTION!    DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT 
EQUIPMENT!

    Under  no  circumstances  this  unit  should  be  used  for 

medical applications involving life support equipment and/or patient care.

 

CAUTION!    DO NOT USE WITH OR NEAR AQUARIUMS!

    To reduce 

the risk of fire, do not use with or near aquariums.    Condensation from 
the  aquarium  can  come  in  contact  with  metal  electrical  contacts  and 
cause the machine to short out. 

CAUTION!   

Do  not  dispose  of  batteries  in  fire  as  the  battery  may 

explode. 

CAUTION!   

Do not open or mutilate the battery, released electrolyte is 

harmful to the skin and eyes. 

CAUTION!   

A battery can present a risk of electric shock and high short 

circuit  current.  The  following  precaution  should  be  observed  when 
working on batteries 
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.

CAUTION!   

The  unit  has  a  dangerous  amount  of  voltage.  When  the 

UPS  indicators  is  on,  the  units  may  continue  to  supply  power  thus  the 
unit’s outlets may have a dangerous amount of voltage even when it’s not 
plugged in to the wall outlet. 

CAUTION!   

Make  sure  everything  is  turned  off  and  disconnected 

completely before conducting any maintenance, repairs or shipment. 

CAUTION!   

Connect the Protection Earth (PE) safety conductor before 

any other cables are connected. 

CAUTION!   

The  UPS  is  a  professional  equipment  with  a  total  rated 

power  larger  than  1kW.  The  equipment  complies  with  IEC61000-3-12 
provided  that  the  short-circuit  ratio  is  larger  than  or  equal  to  66  at  the 
interface point between the user’s power supply and the power grid. It is 
the responsibility of the installer or user of the equipment to ensure, by 
consultation with the power supply department if necessary, that the UPS 
is connected only to a power supply with a short-circuit ratio Rsce larger 
than or equal to 66. 

WARNING!    (Fuses): 

To  reduce  the  risk  of  fire,  replace  only  with  the 

same type and rating of fuse. 

DO  NOT  INSTALL  THE  UPS  WHERE  IT  WOULD  BE  EXPOSED  TO 
DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE! 

DO  NOT  BLOCK  OFF  VENTILATION  OPENINGS  AROUND  THE 
HOUSING! 

DO  NOT  CONNECT  DOMESTIC  APPLIANCES  SUCH  AS  HAIR 
DRYERS TO UPS OUTPUT SOCKETS! 

SERVICING  OF  BATTERIES  SHOULD  BE  PERFORMED  OR 
SUPERVISED  BY  PERSONNEL  KNOWLEDGE  OF  BATTERIES  AND 
THE 

REQUIRED 

PRECAUTIONS. 

KEEP 

UNAUTHORIZED 

PERSONNEL AWAY FROM BATTERIES!

Содержание OL10000ERT3UM

Страница 1: ...User s Manual OL6000ERT3UP OL8000ERT3UP OL10000ERT3UP OL6000ERT3UM OL8000ERT3UM OL10000ERT3UM Cyber Power Systems Inc www cyberpower com K01 0000508 01 ...

Страница 2: ...power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards CAUTION Wiring must be done by qualified personnel CAUTION DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT Under no circumstances this unit should be used for medical applications involving life supp...

Страница 3: ...SB communication cable Serial Interface Cable RS 232 Battery module Rackmount ears Stands 2 2 sets Tie plate 1 1 set Flat head screws M5X7L 8 2 sets Pan head screws M5X12L 4 2 sets Pan head screws M5X6L 14 2 sets Guide screws M5X10L 2 2 sets Plastic washers 8 2 sets Screw hole dust covers 14 2 sets Power cord PowerPanel Business Edition software is available on our website Please visit www cpsww c...

Страница 4: ...ch the mounting brackets RACKMOUNT INSTALLATION Step 1 Remove the dust covers Remove the dust covers 10pcs from the screw holes Step 2 Rackmount ears hanging brackets installation Attach two rackmount ears to the UPS using the provided M5X7L 8pcs screws and tighten two hanging brackets with the M5X6L 6pcs screws Step 3 Rackmount rail Installation The rails adjust to mount in 48 cm 19 inch racks fr...

Страница 5: ... the rear of the rack with two M5X6L screws and two plastic washers Step 5 Place and secure the UPS on the rails Slide the hanging brackets on the UPS into the rails mounted in the rack with the front of the unit facing toward you Secure the UPS to your rack with four M5X12L 4pcs screws at the front of the rack Located in position 5 position 7 How to slide the UPS out from the rack The UPS will be...

Страница 6: ...ecure the tie bracket with the screws M5X7 4pcs Insert dust covers into the screw holes that are not being used Step 3 Rotate the Multifunction LCD Module Unscrew the upper panel of the UPS Separate the upper panel from the UPS Gently lift the LCD module out Rotate it to the tower orientation Reinstall it for a tower configuration ELECTRICAL INSTALLATION After completing the hardware installation ...

Страница 7: ...er completing the hardware installation of the UPS you are now ready to plug in the UPS and connect your equipment SAFETY PRECAUTIONS CAUTION Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity rang...

Страница 8: ...S to the modem computer telephone fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the un...

Страница 9: ...Mains Battery N L PE N L PE Manual Bypass SAFETY PRECAUTIONS CAUTION Input and Output circuit breakers must be OFF during the building installation CAUTION An additional two pole disconnect device is necessary during the building installation CAUTION Disconnected EPO will immediately shut down the logic circuit output of the UPS Wiring the EPO signal is optional CAUTION Local safety rules may requ...

Страница 10: ...ut terminal block Step 4 Output configuration Insert the output cable through the appropriate cable gland not included and connect the three wires to the output terminal block Step 5 Fix the terminal block cover on the PDU s Tighten the four screws to fix the terminal block cover on the PDU s Step 6 Fix the inspection window cover on the PDU s Tighten the four screws to fix the inspection window c...

Страница 11: ...er1 Jumper2 on Backfeed Protection Connector UPS L N PSDR AC L AC N IP L IP N Backfeed 1 2 4 5 3 L N I P EMI L N L N PE Mains PE Jumper2 Jumper1 WITH BACKFEED PROTECTION CONFIGURATION 1 Customers should provide an external isolation device Magnetic Contactor which is upstream and outside the UPS and capable of supporting the UPS input current 2 Remove the interconnection wires Jumper1 Jumper2 on B...

Страница 12: ...port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 7 Surge Protected Communication Ports RJ 45 RJ 11 These ports are used to protect standard RJ 45 RJ 11 based products ADSL LAN Phone Modem Lines and cabling systems ...

Страница 13: ...6 Input Output Connectors Use these connectors to attach the PDU or HW PDU to the Power module 7 Connectors Cover Provides safety protection when removing the PDU or HW PDU 8 Output Circuit Breaker Provides output overload and fault protection 9 Battery Backup Surge Protected Outlets Provides battery backup and surge protection They ensure power is provided to connected equipment over a period of ...

Страница 14: ...this input connector to daisy chain the next Battery module Remove the connector cover for access 6 Output Cable Use this output cable to connect the Battery module to the Power module or to the next Battery module BPE240V30ART3U BPE240V50ART3U CONNECTION 1 POWER MODULE WITH ONE BATTERY MODULE Step 1 Loosen the two screws to remove the battery cable retention bracket of the power module Step 2 Use...

Страница 15: ...he two screws to remove the battery cable retention bracket of the 1st battery module Step 3 Use the output cable of the 2nd Battery module to connect the 2nd Battery module to the 1st Battery module Step 4 Rotate the battery cable retention bracket and tighten the two screws to fix battery cable Step 5 Use a power cord to plug AC input inlet of the 2nd battery module into AC output outlet of the ...

Страница 16: ...RY Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description O...

Страница 17: ...o UPS Status Information Submenu Description O P Volt XXX XV Displays the Output Voltage O P Freq XX XHz Displays the Output Frequency I P Volt XXX XV Displays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Display...

Страница 18: ...ness or RMCARD with PowerPanel Business or RMCARD Event Content MULTI LANGUAGE INTERFACE Users can configure 1 of the 4 available languages for display English Español Spanish Français French Deutsch German 1 Press the ENTER button to activate the MAIN MENU 2 Press the and buttons to scroll to the Configure option 3 Press the ENTER button to select the Configure submenu 4 Press the and buttons to ...

Страница 19: ... 10 20 15 10 15 15 15 20 10 15 Bypass Condition Check Freq Volt Check Volt Only No Bypass Check Freq Volt ECO Mode 1 Disable Enable Disable V Range 15 V Range 10 for Enable V Range 10 Manual Bypass Disable Enable Disable UPS Diagnostic Battery Test Alarm Test Indicator Test Fan Test Battery Test Activate None Audible Alarms Disable Enable Enable EBM Number 0 1 2 3 4 5 6 7 8 9 10 0 Wiring Fault Dis...

Страница 20: ...ondition This condition will still result in an audible alarm 2 Configure Audible Alarms as Disable on the LCD module and it will stop warning of any malfunction audibly MANUAL BATTERY TEST Configure Battery Test as Active on the LCD module and it will perform the Manual Battery Test Graphical Load Battery Capacity Display 1 Press the ESC button to return to UPS Status 2 Press the and buttons to s...

Страница 21: ... figure WALL MOUNTING INSTRUCTIONS Step 1 Remove the Multifunction LCD Module Unscrew the right panel of the Power module Separate the right panel from the UPS Gently lift the LCD module out Reinstall the right panel Step 2 Rotate the DB26 Connector of LCD Module Step 3 Connect the DB26 Cable Connect a DB26 cable not included from LCD module to the Remote Control Port on the front panel as shown i...

Страница 22: ...ry terminals Replacement Batteries Please refer to the front side of the Battery module for the model number of the correct replacement batteries For battery procurement log onto www CPSww com or contact your local dealer Battery Disposal Batteries are considered hazardous waste and must be disposed of properly Contact your local government for more information about proper disposal and recycling ...

Страница 23: ... Switch to Bypass Step 4 Press ON OFF button to turn off UPS Step 5 Pull the PDU or HW PDU away from the Power module Loosen the four screws that hold the PDU or HW PDU to the Power module Pull the PDU or HW PDU away from the Power module and loosen the two screws that hold the cover Step 6 Fix the cover on the PDU or HW PDU Tighten the two screws and fix the cover on the PDU or HW PDU to hide the...

Страница 24: ...de the Interlock Bracket to the right Slide the Interlock Bracket to the right Tighten the one screw that fix the Interlock Bracket in the right Step 6 Check the Power module auto transfer to Line Mode After Sliding the Interlock Bracket to the right the Power module will auto transfer to Line Mode Check the LCD screen shows Line Mode SAFETY PRECAUTIONS CAUTION It must be done by qualified personn...

Страница 25: ...Battery Mode 105 130 Load for 10 sec 131 150 Load for 2 sec Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 20 12V 7 2AH 20 12V 9 0AH Recharge Time Typically 4 hours 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that Supports Multi Language Interface 23 Types of R...

Страница 26: ...ty is sufficient and acceptable If batteries have been recently replaced then reset the Battery Replacement Date using PowerPanel Business Edition Agent software RMCARD interface if installed or through the LCD control panel on the UPS See LCD Setting Configuration EPO OFF Missing the EPO connection Check the EPO connection Wiring Fault Line and neutral wires are reversed Exchange line and neutral...

Страница 27: ...Systems Inc www cyberpower com Entire contents copyright 2017 Cyber Power Systems Inc All rights reserved Reproduction in whole or in part without permission is prohibited PowerPanel Business Edition and PowerPanel Personal Edition are trademarks of Cyber Power Systems Inc ...

Отзывы: