Adjustment

 - Span 

 

1. After setting zero, supply 20mA or 4mA of signal. 

Check the actuator’s stroke. If the stroke is too low, 

adjust the span towards the (+) direction. 

If the stroke point is too high, adjust the span towards 
the (-) direction. (Figure 18) 

2. Changing span points affects the zero point setting, 

so the zero setting must be set again.  After setting 

zero point, confirm the span point. This step must be 

repeated until both points are properly set.  

3. After setting is completed, tighten lock screw. 

 
 
 

 
 
 
 

 
 
 
 

 
 

Adjustment

 - A/M Switch (Auto/Manual) 

 

1. A/M switch adjusts the valve operation to automatic 

or manual. 

2. When produced, YT-

1000L is set at  “A(Automatic)”. 

If user prefers the positioner    setting as “M(Manual)”, 

the setting can be changed by turning the switch coun-

ter-clockwise.  (Figure 19) 

3. If it is set as “M(Manual)”, the air pressure will be 

supplied to the actuator directly. Always set back to   

“A(Automatic)” after setting change.

 

4. If OUT2 in single acting actuator or double acting 

actuator is used, the A/M switch will not operate. 

 

 
 
 
 

 
 
 
 

 
 
 
 

 

 

Adjustment

 - Seat Adjuster 

 
1. Seat adjustment is set according to the customers 

request before the positioner is delivered. Please do 

not adjust the seat adjuster. 

2. Seat adjuster is always used for double acting    

actuators and adjusted when the pressure balance 

point must be changed. Please do not touch the seat 

adjuster, because it can affect the positioner’s        

performance. 

 

Adjustment

 - Orifice 

 

1. If the size of the actuator is too small relative to the 

flow rate, the positioner can have hunting. In order to 

avoid hunting, orifice can be used. There are three 
types of orifice. 

CVS Controls Ltd. 

Product Manual: CVS Rack & Pinion Actuator 

CVS Controls Ltd. 

Process Management 

And Instrumentation 

Lock Screw 

Lock Screw 

Seat Adjuster 

Auto Manual Switch 

Output 

Pressure 

Output 

Pressure 

Output 

Pressure 

High Pressure Balance 
(0.9~1.0Ps) - Normal 

Med. Pressure Balance 
(0.5Ps) - Normal 

Low Pressure Balance 
(0.4~0.5Ps) - Normal 

Balanced Point 

Balanced Point 

Balanced Point 

Input Pressure 

Ps=Supply Pressure 

Содержание CVS1000L

Страница 1: ...he product or parts If alterations or modifications are required please contact CVS Controls Ltd The manufacturer warrants the product from the orig inal date of purchase for one 1 year except as othe...

Страница 2: ...ischarge through port OUT1 to the actuator 10 As the actuators inner pressure increases the actuator stem 12 will move pushing on the feedback lever 13 This movement is transferred to the cam 14 and p...

Страница 3: ...y 1 2 NPT Explosion Proof CSA Class 1 Zone 1 Group IIB T5 Protection IP66 40 60 C Linearity 1 0 F S Hysteresis 1 0 F S Sensitivity 0 2 F S 0 5 F S Repeatability 0 5 F S Air Consumption 3LPM Sup 1 4kgf...

Страница 4: ...nd Instrumentation ZERO UNIT TORQUE MOTOR BASE BODY JUNCTION BOX COVER PILOT VALVE FEEDBACK SHAFT SPAN UNIT VENT UNIT FEEDBACK LEVER 224 3 132 3 6 Conduit Entry PT NPT 1 2 PF G 1 2 Out 2 NONE 45 122 1...

Страница 5: ...se consider the following when making a bracket i Feedback level should be leveled at 50 of the valve stroke Refer to step 7 ii Feedback lever connection bar of actuator clamp should be installed at t...

Страница 6: ...troke To adjust move the bracket or connection bar Figure 7 Stroke 70mm NOTE After installing the YT 1000L operate the valve from 0 to 100 stroke by using the air filter regulator on the actuator Both...

Страница 7: ...hat has more than a 6mm inner diameter 4 Do not use an extremely long pipeline system It may affect flow rate due to the friction inside the pipeline Piping Connection with Actuator YT 1000 series sin...

Страница 8: ...or 20mA and rotate adjuster clockwise or counter clockwise to adjust the actuator s initial point When setting the initial point the specification of valve and system must be taken into account Please...

Страница 9: ...tting change 4 If OUT2 in single acting actuator or double acting actuator is used the A M switch will not operate Adjustment Seat Adjuster 1 Seat adjustment is set according to the customers request...

Страница 10: ...nozzle and the flapper If damaged pleae contact CVS Controls Ltd The pressure is exhausted only by the A M switch 1 Check if the positioners nozzle has been blocked Also check if the pressure is supp...

Страница 11: ...11 Ordering Information CVS Controls Ltd Product Manual CVS Rack Pinion Actuator CVS Controls Ltd Process Management And Instrumentation...

Страница 12: ...eet Edmonton Alberta Canada T6E 0A5 Office 780 437 3055 Fax 780 436 5461 Calgary Sales Office 3516 114 Avenue SE Calgary Alberta Canada T2Z 3V6 Office 403 250 1416 Fax 403 291 9487 Website www cvs con...

Отзывы: