7
PIPING CONNECTION
NOTE:
•
To avoid moisture, oil, or dust from entering the
product, please carefully select the supply
pressure compressor.
Supply Pressure Condition
1. Dry air with at least 10°C lower than ambient
temperature.
2. Keep away from dusty air. Filter can only sort 5
micron or larger.
3. Avoid oil.
4. Comply with ANSI/ISA-57.3 1975(R1981).
5. Not to be used beyond the range of
1.4 - 7 kgf/cm
2
(20 - 100 Psi).
6. Set air filter regulator’s supplied pressure 10% high-
er than actuator’s spring range pressure.
Pipe Condition
1. Make sure the inside of the pipe is empty.
2. Do not use pipeline that is squeezed or has holes.
3. To maintain flow rate, use the pipeline that has
more than a 6mm inner diameter.
4. Do not use an extremely long pipeline system. It
may affect flow rate due to the friction inside the
pipeline.
Piping Connection with Actuator
YT-1000 series single acting type is set out to use
OUT1 port. OUT1 port should be connected with the
supply pressure port from the actuator when using
single acting type spring return actuator. For double
acting, the piping connection can be changed due to
the operation direction. Please refer to the following
diagrams when piping.
(Figures 9 - 11)
CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
CVS Controls Ltd.
Process Management
And Instrumentation
OUT1
OUT1
SUP.
AIR
SUPPLY
YT-200
OUT
AIR
SUPPLY
YT-200
OUT
OUT 1
OUT 2
OUT 2 SUP.
OUT 1
OUT 1
OUT 2
AIR
SUPPLY
AIR
SUPPLY
OUT 2
SUP
.
OUT 1
INPUT
SIGNAL
4~20mA
DIRECT
ACTION
REVERSE
ACTION
OUT 2
OUT 1
OUT 2
SUP.
OUT 1