6. Insert connection bar into the YT-1000L feedback 

lever. The connection bar should be inserted at the 
50% point on the feedback lever, which would help to 

reduce hysteresis. 

(Figure 5) 

 

 
 
 
 

 
 
 
 

 

7. If the connection bar does not point at the 50% 

point, then adjust the bracket or feedback link bar  

position. Failure to position at 50% would lower the 

linearity of the positioner. 

(Figure 6) 

 

8. Check valve stroke. The stroke numbers are      

indicated on the feedback lever. Position the          

connection bar at the number on the feedback lever 

according to the valve stroke. To adjust, move the 
bracket or connection bar. 

(Figure 7) 

 Stroke 70mm 

 

NOTE: After installing the YT-1000L, operate the valve 

from 0% to 100% stroke by using the air filter regulator 

on the actuator. Both at 0% and 100%, the feedback 

lever should not touch the lever stopper, which is   

located on the backsideof the YT-1000L.  
(Figure 8)  

 
 
 

 

 

 

 

 

 

If the feedback lever touches the lever stopper,         

YT-1000L should be installed further away from the 
center of the yoke. 

 

9. After the proper installation, tighten all the bolts on 

the bracket, the feedback lever, and the connection 

bar. 

CVS Controls Ltd. 
Product Manual: CVS Rack & Pinion Actuator 

CVS Controls Ltd. 
Process Management 
And Instrumentation 

YT-200 

40 

50 

60 

50% 

20             30              40              50             60     

40             50              60             70                

 

20 

30 

70 

Stroke 30mm 

Содержание CVS1000L

Страница 1: ...he product or parts If alterations or modifications are required please contact CVS Controls Ltd The manufacturer warrants the product from the orig inal date of purchase for one 1 year except as othe...

Страница 2: ...ischarge through port OUT1 to the actuator 10 As the actuators inner pressure increases the actuator stem 12 will move pushing on the feedback lever 13 This movement is transferred to the cam 14 and p...

Страница 3: ...y 1 2 NPT Explosion Proof CSA Class 1 Zone 1 Group IIB T5 Protection IP66 40 60 C Linearity 1 0 F S Hysteresis 1 0 F S Sensitivity 0 2 F S 0 5 F S Repeatability 0 5 F S Air Consumption 3LPM Sup 1 4kgf...

Страница 4: ...nd Instrumentation ZERO UNIT TORQUE MOTOR BASE BODY JUNCTION BOX COVER PILOT VALVE FEEDBACK SHAFT SPAN UNIT VENT UNIT FEEDBACK LEVER 224 3 132 3 6 Conduit Entry PT NPT 1 2 PF G 1 2 Out 2 NONE 45 122 1...

Страница 5: ...se consider the following when making a bracket i Feedback level should be leveled at 50 of the valve stroke Refer to step 7 ii Feedback lever connection bar of actuator clamp should be installed at t...

Страница 6: ...troke To adjust move the bracket or connection bar Figure 7 Stroke 70mm NOTE After installing the YT 1000L operate the valve from 0 to 100 stroke by using the air filter regulator on the actuator Both...

Страница 7: ...hat has more than a 6mm inner diameter 4 Do not use an extremely long pipeline system It may affect flow rate due to the friction inside the pipeline Piping Connection with Actuator YT 1000 series sin...

Страница 8: ...or 20mA and rotate adjuster clockwise or counter clockwise to adjust the actuator s initial point When setting the initial point the specification of valve and system must be taken into account Please...

Страница 9: ...tting change 4 If OUT2 in single acting actuator or double acting actuator is used the A M switch will not operate Adjustment Seat Adjuster 1 Seat adjustment is set according to the customers request...

Страница 10: ...nozzle and the flapper If damaged pleae contact CVS Controls Ltd The pressure is exhausted only by the A M switch 1 Check if the positioners nozzle has been blocked Also check if the pressure is supp...

Страница 11: ...11 Ordering Information CVS Controls Ltd Product Manual CVS Rack Pinion Actuator CVS Controls Ltd Process Management And Instrumentation...

Страница 12: ...eet Edmonton Alberta Canada T6E 0A5 Office 780 437 3055 Fax 780 436 5461 Calgary Sales Office 3516 114 Avenue SE Calgary Alberta Canada T2Z 3V6 Office 403 250 1416 Fax 403 291 9487 Website www cvs con...

Отзывы: