Fault Diagnosis 

 

Symptom Check 

List Tick 

Check remote handset  is working properly and battery is 
charged 

 

Check power supply has not been switched off 

 

Check fuses in spur 

 

Unit does 

not respond 

Check wiring is correct on fire and hardwire switch 

 

Check battery power 

 

Remote 

handset 

does not 

work 

 

Check remote eye is visible and facing in the correct 
position 

 

Check switch is wired properly 

 

Hardwire 

manual 

switch does 

not work 

Check hardwire switch’s green block is wired correctly 

 

Check spark lead is connected properly 

 

Unit clicks 

but no 

spark or 

weak spark 

Check spark electrode is in the correct area and the gap 
correctly distanced 

 

Check for a good spark 

 

Check the spark is in the right area 

 

Unit sparks 

but does not 

light pilot 

Check the ventilation is not too strong and the flame is not 
blowing off the thermocouple 

 

Check isolation tap/shut off valves are free from grease 

 

Check isolation tap/shut off valve are on 

 

Check for blockages 

There is no 

gas 

Check gas working pressure is correct:  

 

Check gas working pressure is correct:  

 

Check for blockages in pipes 

 

Check for draughts which can reduce pilot flame 

 

There is gas 

but pilot 

does not 

light 

Check the pilot gas slot is clear of debris 

 

Check the pilot flame is heating the thermocouple and there 
is a draft shield fitted if required 

 

Check the thermocouple nut is properly tightened into the 
valve/interrupter block 

 

Check that the pilot lights early on ignition clicks 

 

Check ventilation is not too strong and the flame is not 
blowing off the thermocouple 

Pilot lights 

but does not 

light main 

burner 

Check gas working pressure is correct: NG – 20mBar, LPG 
37mBar 

 

Check thermocouple nut is properly secured to the 
interrupter block on the valve and flame failure device is 
operating correctly 

 

Check ventilation is not too strong and the flame is not 
blowing off the thermocouple 

 

Burner 

lights but 

turns off 

after a few 

minutes 

Check gas working pressure is correct:  

 

Содержание 0558bl5590

Страница 1: ...commended even if you have fitted these appliances before that you take the time to read through these instructions and ensure that you follow them step by step Serial Number Please quote this serial...

Страница 2: ...emote Control Information Page 6 General Requirements Page 7 Installation Instructions Page 10 Commissioning the Fire Page 11 Re setting the Appliance Page 13 Remote Control Options Page 14 Lighting t...

Страница 3: ...460 7 4 17 4 NG I2E 20 95 9 5 15 4 DE LU 460 7 0 21 7 NG I2L 25 95 8 8 19 1 NL PROP I3P 30 1 45 6 6 18 5 NL PROP I3P 37 1 45 7 0 19 6 BE ES FR GB IE PT PROP I3P 50 1 27 7 9 31 9 AT NL DE High Flame Pi...

Страница 4: ...he installation should only be carried out by a Gas Safe Registered fitter and in accordance with national and local regulations for both gas electricity The installation must also be in accordance wi...

Страница 5: ...Hz Max power consumption 20VA cos 0 6 Peak Stand by power consumption 1W Ambient Temperature 0 80 C Protection IP 20 Humidity Max 95 at 40c Electrical protection Not required Connections STELVIO STOC...

Страница 6: ...ge and unnecessary service costs Before the fire is installed a flue test in accordance with National Regulations should be carried out The unit must not be installed unless the chimney flue length is...

Страница 7: ...xceeds 1 5mtrs it is recommended that after this point the gas pipe work is increased to 15mm and possibly 22mm to avoid pressure problems and nuisance shutdowns Step 3 The bowl must be secured within...

Страница 8: ...the fire bowl into the enclosure by the use of screws and rawl plugs See Diagram below Failure to secure the bowl will result in an unstable installation which may cause gas leaks By feeding the gas...

Страница 9: ...system A 240V 3A Fused spur is required to connect the mains supply for the remote This must be position in a location so the property owner can check and replace the fuse should this be required Con...

Страница 10: ...nce of 1mb Now turn off all the other gas appliances and turn the fire down to pilot only the pressure must still be in the tolerance of 1mbar If it is not TRANSCO BORD GAIS or the propane supplier mu...

Страница 11: ...a minimum of three seconds until the ignition process begins which will run for 19 20 seconds before it turns onto the main burner After the burner has ignited it can then be switched to high or low...

Страница 12: ...he small junction terminal there you will find three wires green yellow brown and blue Note Using a small electrician s screwdriver release all three wires from the terminal block It is very important...

Страница 13: ...ing an option it is done correctly in order for the option left to function correctly on its own Oxygen Depletion Pilot System There is a highly sensitive oxygen depletion sensor designed into the pil...

Страница 14: ...ature to ensure that the appliance cannot be remotely lit from another room Hardwired Wall Mounted Switch Press the ON OFF bottom left side for 2 3 seconds until the spark ignition sequence begins and...

Страница 15: ...Page 15 of 31 Press the HIGH LOW button right side for 2 3 seconds the appliance will change to low rate This operation is repeated to switch between high and low...

Страница 16: ...ge 16 of 31 Infra Red Remote Operation Infrared IR systems require Line of sight between the handset and the appliance This is a standard feature to ensure the appliance cannot be lit from another roo...

Страница 17: ...Page 17 of 31 Infra Red Remote Replacing the Battery The Remote Controls Black Box...

Страница 18: ...ld be 3 5 4 5mm and normally adjustment is not necessary the electrode is very brittle The spark should jump across the gap between the electrode and the gas outlet on the pilot head If the ignitor fa...

Страница 19: ...he factory including being run for a number of minutes on full gas supply to ensure that the unit functions correctly It is highly unlikely that if the unit has been installed correctly as set out in...

Страница 20: ...valves are free from grease Check isolation tap shut off valve are on Check for blockages There is no gas Check gas working pressure is correct Check gas working pressure is correct Check for blockage...

Страница 21: ...h these instructions and ensure that you follow them step by step Serial Number Please quote this serial number when calling our Customer Service team regarding Warranty issues or to order spare parts...

Страница 22: ...of 31 Contents Page 23 General Instructions Page 24 Exchangeable Components List Page 25 Servicing Instructions Page 26 Cleaning Instructions Page 29 Fire Guards Other Information Page 30 Warranty Inf...

Страница 23: ...stion products is interrupted If the fire shuts itself off do not use the fire and have the flue and fire checked by a suitably qualified person Once the flue and fire units have been checked and reme...

Страница 24: ...emote Injector CVO 460 Yes No AC097 Small Flame Picture LPG 30 37 Remote Injector CVO 1 45 Yes No AC021 Large Flame Picture NG Remote Injector CVO 460 Drilled Yes No AC097 Large Flame Picture LPG 30 3...

Страница 25: ...s not adjustable and must not be disabled Servicing procedure Step 1 Turn off the fire and allow it to cool Step 2 Turn off the gas supply at the isolation tap Step 3 Disconnect the gas pipe from the...

Страница 26: ...Components Once installed the unit should be dusted periodically to remove naturally collecting dust particles from its surfaces this can be done using a duster or vacuum cleaner Note where a vacuum u...

Страница 27: ...by the iron will be drawn away from the surface of the surround by the blotting paper It may be necessary to repeat this process several times until all the wax has been successfully removed If blott...

Страница 28: ...gas fire must be switched off when cleaning the burner surface The burner surface is made from carbon coated glass material the gas passes through the matting and is ignited above the burner surface a...

Страница 29: ...e the user against placing combustible material directly in front of the appliance Floor coverings such as carpets are considered to be acceptable Hearths For some countries a non combustible hearth m...

Страница 30: ...m you will be required to supply the serial number of the appliance as shown on the front of this booklet and full details of the GAS SAFE registered engineer who installed and commissioned the applia...

Страница 31: ...tment on 01325 327221 Spirit Fires Ltd Unit 4 Beaumont Square Aycliffe Industrial Park Newton Aycliffe County Durham DL5 6XN Tel 01325 327221 Fax 01325 327292 Email info cvo co uk Web www cvo co uk Th...

Отзывы: