background image

Pub 49004

Effective 9/00

Page 3

Operating Temperature Range

-

40

o

C to 50

o

C (-40

o

F to 122

o

F)

Storage Temperature Range

-50

o

C to 70

o

C (-58

o

F to 158

o

F)

Elevation

Above 2000 Meters (6600 feet) consult factory

Humidity

Functional to 95% non-condensing

Operating Orientation

Any

Pollution Degree IEC 947-1

3

Shock Resistance

15g in any direction

Vibration Resistance

3g in any direction

Environmental Requirements

Mounting Instructions for Models S801N and S801R

The IT Soft Starter is easy to mount. It does not require

any special tools.
To aid you with panel layout, refer to the dimension

drawings on page 2 of this leaflet. Drill and tap holes per

mounting hole location as shown.
To mount the unit, use all the hardware specified in Table

1 on page 2 of this leaflet. Tighten to the torque specified.

TO AVOID SHOCK HAZ-
ARD, DISCONNECT ALL
POWER BEFORE ANY
FUNCTIONS ARE PER-
FORMED ON THIS
EQUIPMENT.

POUR EVITER TOUT
CHOC ELECTRIQUE,
COUPLER L’ALIMENTA-
TION DE CET EQUIPE-
MENT AVANT D’Y EF-
FECTUER DES
TRAVAUX.

AVERTISSEMENT

WARNING

Hazard of Burn or
Electrical Shock

Risque de Brulure ou de
Choc Electrique

Wiring Diagrams

Each diagram illustrates a typical wiring scheme for the

options described. The soft starter is represented by the

terminal board. The additional items shown on the dia-

grams are not included, but they may be purchased from

Cutler-Hammer.

Fig. 3    Elementary Diagram for Soft Starter with

START/STOP/RESET/JOG with 120VAC
Alarm and Run Indication

261348

Table 3

Содержание S801N

Страница 1: ...stors connected in a full wave power bridge The voltage and current applied to the motor is controlled by varying the thyristor conduction period This in turn controls the torque supplied by the motor...

Страница 2: ...Required S801N 10 32 x 0 5 Standard 10 4 1 7 N m 65mm Lockwasher and 15 in lb 2 55 in Flat Washer S801R 1 4 20 x 0 625 Standard 1 4 4 2 8 N m 110mm Lockwasher and 25 in lb 4 33 in Flatwasher Required...

Страница 3: ...es per mounting hole location as shown To mount the unit use all the hardware specified in Table 1 on page 2 of this leaflet Tighten to the torque specified TO AVOID SHOCK HAZ ARD DISCONNECT ALL POWER...

Страница 4: ...UNE TENSION DE 24V C C AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE POURRAIT CAUSER DES DOMMAGES IMPORTANTS AU...

Страница 5: ...OULD RE SULT IN SEVERE DAMAGE TO THE CONTROLLER CAUTION APPLIQUER UNE TENSION DE 24V C C AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSER...

Страница 6: ...ce the unit is energized it will communicate with the CIM and load the program into the Soft Starter Allow the unit 2 seconds to ensure communication checks complete and values are set To verify CIM i...

Страница 7: ...stantaneous overcurrent 41 24V power supply low 42 Timer system fault 43 Watchdog reset occurred 44 PLL DSP 45 Illegal address DSP Effective 9 00 Table 7 Fig 6 Soft Start Control Interface Module CIM...

Страница 8: ...15 30 33 15 15 20 15 40 40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor kW Rating 50 Hertz hp Rating 60 Hertz 200V 230V 460V 575V 15 Second Ramp 4 Starts per Hour 450...

Страница 9: ...42 11 18 5 22 10 10 15 10 30 25 40 30 N66N3S 110 mm 65 15 30 33 15 15 20 15 50 40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor hp Rating 60 Hertz kW Rating 50 Hertz 20...

Страница 10: ...800 356 1243 For service or start up assistance 24 hours day 7 days week please call 1 800 498 2678 Cutler Hammer Solid State Reduced Voltage Motor Starter Aftermarket Services Technical telephone su...