background image

I.L. 29C508B

Page 9

Effective 9/00

GROUND FAULT TEST RECORD FORM

Ground Fault Test Record should be Retained by Those in Charge of the Building’s Electrical
Installation in order to be Available to the Authority having Jurisdiction

Test Date

Circuit 

Breaker

Number

Results

Tested By:

Figure 5-4  Typical Performance Test Record Form

Содержание Digitrip OPTIM 550

Страница 1: ...TY PROCEDURES CUTLER HAMMER IS NOT LIABLE FOR THE MISAP PLICATION OR MISINSTALLATION OF ITS PROD UCTS The user is cautioned to observe all recommendations warnings and cautions relating to the safety...

Страница 2: ...DC applications a thermal magnetic trip unit should be used The Digitrip OPTIM 550 Trip Unit for the L Frame is available in 3 different types and four different maximum ampere ratings Table 1 1 Groun...

Страница 3: ...ring channels Ground fault trip units are supplied from the factory with a wire harness with pigtail lead connections for a neutral current sensor white and gray wires A neutral current sensor is prov...

Страница 4: ...etaining slots of the trip unit I L 29C508B Page 4 Effective 9 00 Figure 3 3 Neutral Current Sensor Placement 1 50 Table 3 1 Digitrip L Frame OPTIM Rating Plugs Max Amps In Catalog Number of trip unit...

Страница 5: ...ed to avoid exceeding a safe terminal temperature operating range Consult Cutler Hammer for recommendations 4 1 GENERAL The Digitrip OPTIM 550 Trip Unit provides a tripping sig nal to the flux transfe...

Страница 6: ...RFORMANCE TESTING FOR GROUND FAULT TRIP UNITS 5 2 1 CODE REQUIREMENTS The National Electrical Code under Article 230 95 C requires that any ground fault protection system be per formance tested when f...

Страница 7: ...TING AND NOT FIELD CALIBRATION OF THE DIGITRIP OPTIM 550 GROUND FAULT TRIP UNIT ANY TEMPORARY CONNECTION MADE FOR THE PURPOSE OF CONDUCTING TESTS SHOULD BE RESTORED TO PROPER OPERATING CONDITIONS BEFO...

Страница 8: ...es which mount on the trip unit are available for use The number of the instruction leaflet covering the installation of each accessory is shown Alarm Signal Lockout ASL Switch I L 29C183 Auxiliary Sw...

Страница 9: ...round Fault Test Record should be Retained by Those in Charge of the Building s Electrical Installation in order to be Available to the Authority having Jurisdiction Test Date Circuit Breaker Number R...

Страница 10: ...I L 29C508B Page 10 Effective 9 00...

Страница 11: ...I L 29C508B Page 11 Effective 9 00...

Страница 12: ...Cutler Hammer Pittsburgh Pennsylvania U S A Effective 9 00 ISI Style 6603C85H03 Printed in U S A Page 12 I L 29C508B...