MONITOR PARAMETER PROFILE OBJECTS
The Monitor Parameter Profile Objects are shown in Table 4.
5 — SDO: Monitor Profile Objects
Table 4 Monitor Profile Object Dictionary
sdo
location
range
parameter
index
sub
-
index
can
value
description
Analog1 Resistor Value
0x3100
0x00
0 – 7500 Ω
Resistive type analog input value.
0 – 7500
Scale returned as 1 ohm per count.
Analog2 Resistor Value
0x3101
0x00
See above.
See above.
Analog3 Resistor Value
0x3102
0x00
See above.
See above.
Analog4 Resistor Value
0x3103
0x00
See above.
See above.
Analog5 Resistor Value
0x3104
0x00
See above.
See above.
Analog1 Voltage Value
0x3110
0x00
0.00 – 15.60 V
Voltage type analog input value.
0 – 1560
Scale returned as 0.01 volt per count.
Analog2 Voltage Value
0x3111
0x00
See above.
See above.
Analog3 Voltage Value
0x3112
0x00
See above.
See above.
Analog4 Voltage Value
0x3113
0x00
See above.
See above.
Analog5 Voltage Value
0x3114
0x00
See above.
See above.
Battery Voltage
0x3120
0x00
0.0 – 120.0 V
Voltage as read by the 1356 / 1356P.
0 – 1200
Driver1 Current
0x3130
0x00
0.00 – 3.00 A
Present current sunk by Driver 1.
0 – 300
Driver2 Current
0x3131
0x00
0.00 – 1.00 A
Present current sunk by Driver 2.
0 – 100
Total Driver Current
0x3132
0x00
0.00 – 4.00 A
Present current sunk by both drivers.
0 – 400
PWM1
0x3140
0x00
0.0 – 100.0 %
Present PWM % of Driver 1.
0 – 1000
PWM2
0x3141
0x00
See above.
Present PWM % of Driver 2.
Hour Meter
0x3150
0x00
0 – 65535 h
Present value of the hour meter.
0 – 65535
Switch Input Status
0x3160
0x00
0 – 0x1FFF
Status of switch inputs (LSB for switch
0 – 0x1FFF
Input 1: 1 = High, 0 = Low.
Virtual Digital Input Status
0x3170
0x00
0 – 0x1F
Status of virtual switch inputs (LSB for
0 – 0x1F
input 1: 1 = High, 0 = Low.
5V Voltage
0x3180
0x00
0.0 – 6.3 V
Voltage value of the +5V output.
0 – 63
12V Voltage
0x3181
0x00
0.0 – 16.0 V
Voltage value of the +12V output.
0 – 160
Ext Current
0x3182
0x00
0 – 250 mA
Total current on +5V and +12V
0 – 250
outputs.
Current encoder pulse count.
Pulse Count
0x3190
0x00
-2
29
– 2
29
-1
Negative count indicates the
-
2
29
– 2
29
-1
encoder is running in the reverse
direction of the zero position.
Encoder RPM in revolutions per
RPM
0x3191
0x00
0 – 65535 rpm minute when encoder is configured
0 – 65535
as RPM type.
-32.768 – 32.767 m Calculated position value according
Position
0x3192
0x00
to the pulse per meter when encoder
-32768 – 32767
is configured as Position type.